Manuale d’uso / di manutenzione del prodotto S47-0079 del fabbricante Exide
Vai alla pagina of 20
1 GNB A division of Exide Technologies Industrial Battery Charger Installation and Operation Manual S47-0079 REV0410.
2 INDEX Page Section Description 3 - Safety Instructions 4 1.0 Installation 4 1.1 Receiving 4 1.2 Location 4 1.3 Line Voltage Adjustments 6 1.4 AC Service Requirements 6 1.5 Connecting AC Service to Charger 7 1.6 Grounding the Charger 7 1.7 Battery Connector and Charger Cable 7 1.
3 WARNING THIS EQUIPMENT CONTAINS LETHAL VOLTAGE LE VELS. INSTALLATION AND SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL IMPORTANT: SAVE THESE INSTRUCTIONS! READ AND FOLLOW ALL INSTRUCTIONS BEFORE I NSTALLING, OPERATING, OR SERVICING CHARGER. ANY DEVI ATION CAN CAUSE SERIOUS AND PERMANENT DAMAGE.
4 SECTION 1 - INSTALLATION 1.1. Receiving Immediately upon receipt of the charger, check it agai nst the shipping invoice to ensure the shipment is complete and undamaged. Examine the outside of the packing fo r signs of r ough ha ndling before accep ting the charger f rom the carrier.
5 575 POWER TRANSFORMER SETT ING 480 L2 L2 12 3 4 56 12 3 4 56 L1 L1 12 3 4 1 3 2 4 CONTROL TRANSFORMER CONTROL TRANSFORMER NOTE: When a 120/208/240 AC inpu t unit is set for 120VAC a f use neutral (brass tube ) is required in the Line 2 (neutral) fuse position.
6 TABLE 1-1 Line Amperes Disconnect Switch Fuse Size Amps 000.0 - 02.5 30A 05 003.0 - 04.5 30A 07 005.0 - 07.5 30A 10 008.0 - 11.0 30A 15 011.5 - 15.5 30A 20 016.0 - 18.0 30A 25 018.5 - 22.0 30A 30 022.5 - 27.0 60A 35 027.5 - 32.0 60A 40 032.5 - 40.0 60A 50 040.
7 1.6 Grounding the Charger The charger must be grounded to the A C syste m ground for personnel safety. The green ground wire in the AC input wiring must be connected to the charge r groun d stud (Identified by a green dot and ground symbol).
8 SECTION 2 - OPERA TION The charger utilizes a st andard ferro-resonant tran sformer , which provides isolation from the AC service line and regulates the charging cu rrent. The transformer output is con nected to a full-wave bridge of silicon diodes, which provides DC charging current to the battery .
9 observe any defective segment s or indicators. When t he self-diagnostic is com plete, the charge st art s if no delay is set, and the yellow ‘Charging’ indicator lights. The display sho ws the charging amp s and battery volts per cell along with a message to indicate the cha rger is in phase 1 of the char ge cycle.
10 The 046-0371 control ca n provide an auto-refr esh charge as long as the battery remains connected to the charge r if enabled. If AC power is lost during th e wait period, the cont rol resumes from where it left of f after power is restored . During t he auto-refresh charge, the a mp-hours and cha rge time are added to the origi nal charge.
11 2.1.9 Charge Indications The fo llowing indications are n ot necessarily a result of a charger problem . Th ey are typically caused by external problems such as AC line, poor battery conditi ons, connections , etc.
12 Note: F3 and F4 clear automatically if the battery voltage falls wit hin acceptabl e limits. All indications except F8, F9 and F10 can be cleare d by disconnecting the battery . For F8, F9 and F10, correct the condition that caused the i ndication an d disc onnect the battery to clear the indi cation.
13 2.1.12 Programming To enter p rogramming m ode, press and hold the EDIT butto n and while holding it, press the INFO button. The display sho ws a m essage describing t he current paramet er followed by the param eter‘s value.
14 SECTION 3 - OPTIONAL FEATURES 3.1 Fusible Door-Interlock Switch (JIC Switch) The door interlock switch assembly connects the A C se rvice to the charger’s inp u t fuses for each AC line. The switch is mechanically latche d by the door so t hat it must be in the OFF position before the door can be opened.
15 4.3. AC fuse blows. POSSIBLE CAUSE A. Incorrect fuse rating. B. Incorrect AC voltage. C. Fuse Block holding clips loose. D. Shorted transformer winding. 4.4. DC fuse blows. POSSIBLE CAUSE A. Reversed battery conn ecto r. B. Incorrect fuse rating. C.
16 SECTION 5 – REPLACEABLE PARTS 5.1 Ordering Information The following information must be supp lied when orderi ng a repl acement pa rt from your service agent in order to ensure that the corre ct part is supplied: A. Model or Spec. number of char ger (Located on ch arger data plate) B.
17 5.3 Spare Parts List Part Number Description Condensers 008-0002 2 MFD 440 Volt 008-0004 4 MFD 440 Volt 008-0006 6 MFD 440 Volt 008-0008 8 MFD 440 Volt 008-0010 10 MFD 440 Volt 008-0012 12.
18 Three Phase Charger Schematic # 02 -400.
19 Single Phase Charger Schematic # 02 -416.
DWG. NO. WIRING DIAGRAM: DR. DATE: CHK: 12 11 10 987654321 2 CMP 3 PHASE, 4 TRANS, 4 GANG, STANDARD CONFIGURATION. (C1,C2,C3 AND C4) TYPICAL CIRCUIT 02-490 02-490 NOTES: * WATERING NOT AVAILABLE ON ALL CONTROLS.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Exide S47-0079 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Exide S47-0079 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Exide S47-0079 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Exide S47-0079 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Exide S47-0079, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Exide S47-0079.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Exide S47-0079. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Exide S47-0079 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.