May 2008 Rev. 11 FOR YOUR SAFETY The use and storage of gasoline or other flammabl e vapors and liquids in open containers in the vicinity of this appliance is hazardous .
.
3 TABLE OF CONTENTS WARRANTY ...................................................................................................................... ............................ 4 INSTALLA TION ..........................................................
4 WARRANTY This equipment is warranted to be free from defe cts in materials and workmanship, unde r normal use and service, for a period of 12 months from date of shipm ent. This warranty shall not apply if: 1. The equipment is not installed by a qualifi ed instal ler per the MANUFA CTURER’S installation instructions shipped with the product, 2.
5 INSTALLATION It is imperative that this unit is in stalled and ope rated with the designed airflow, gas, and electrical supply in accordance with this manual. If there are any questions about any items, please call the service department at 1-866-784-6 900 for warranty and technical support issues.
6 Recom men ded Suppl y Du ctwork Sizes Bl ower Si ze Duct Size St rai ght Duct Lengt h 10 14 x 14 48 i n. 12 16 x 16 54 i n. 15 20 x 20 72 i n. 18 24 x 24 86 i n.
7 Direct Fired Module Installation Indoor (INLINE) Installation Heat Module Add-On Installation Modular heat units shippe d to add heat onto existin g blower only application s require field mechanical and wiring installation. 1. Remove existing filter intake and lifting lugs from blower section in take side.
8 Gas Pressure Table Gas Pressure Type Gas Pressure Size 1-3 Inlet Pressure 7 in. w.c. – 14 in. w.c. Size 4-5 Inlet Pressure 7 in. w.c. – 5 psi. Max.
9 Copper Wire Ampacity Wire Size AWG Maximum Amps 14 20 12 25 10 30 8 40 6 55 4 70 Electrical Before connecting powe r to the heater, read and understand this entire section of this docume n t. As-built wiring diagrams are furnished with each fan b y the factory, and are atta ched to the door of the unit.
10 Remote Control Panel On units shipped with the optional remote control panel , an ele ctrical drop containing th e panel wiring is provided with the heate r. There is a terminal strip in side the remote panel th at matches the terminals in the heater unit.
11 Pilot Assembly OPERATION Prior to starting up or operating the heater, che ck al l fasteners for tightness. In particular, che ck the set screw in the wheel hu b, bearings and t he fan sheaves (pulleys).
12 Maxitrol M511 and M611 Low Fire Bypass Screw Mod Valve Voltage Summary Volts DC Firing Mode 0 to 5 VDC Low Fire 5 to 15 VDC Modulation 15 to 20 VDC High Fire Maxitrol MR212 Lo w Fire Bypass Scre w Average Man ifold Pressure vs. Firing Rate/Ft. of Bu rn er -1.
13 Adju st pilot flame. Lock u ni t in to hig h f i re. Ad ju s t incomi ng gas pressur e. Doe s h igh fi re pr oduce at least a 70°F temp rise an d produce the correct m anifold pressu re? A djust h igh fire No Lock unit in to low fire. Yes Does thin flame fill ent i re b urne r le ngt h? Adju s t low fire.
14 Maximum RPM and HP Chart Blower Size Maximum RPM Maximum HP 10” 1800 2 12” 1500 3 15” 1400 5 18” 1200 5 20” 1000 10 25” 900 20 Pulley Adjustment Illustration Pulley Setscrew Torque Thread Size Torque (IN/Lb) No. 10 (bushing) 32 1/4” (bushing) 72 5/16” 130 Final Start Up Procedure 1.
15 Pulley Combination Chart Motor RPM 1725 1/3 to 1-1/2 H P MOTOR PULL EY Dd1 Dd2 Pd1 Pd2 AX BELTS 1VL34 1.9 2.9 2 3 Open Closed BLOWER PULLEY DATUM DIAMETER PITCH DI A METER 5 4 1/2 4 3 1/2 3 2 1/2 2 1 1/2 1 1/2 0 AK114 11 11.2 308 323 339 354 370 385 400 416 431 447 462 1/3 to 2 HP MOTOR PULL EY Dd1 Dd2 Pd1 Pd2 AX BELTS 1VL40 2.
16 Flame Safety Controller Air Flow Switch DC Flame Signal DC Voltage Flame Status 0 to 5 VDC No Flame 6 to 11 VDC Weak Flame 12 to 18 VDC Strong Flame Sequence of Operation The direct-fired heater is most easily understood wh en broken down into smaller individual system s.
17 Maxitrol 14 Amplifier High Temperature Limit airflow switch to close. The high airflo w switch prot ects against profile plate fail ures that cause excessive airflow through the burne r.
18 9 Begins Pilot Trial For Ignition and turns on PTFI LED 9 The pilot g as solenoid valve is opene d, the sp ark igniter begins spar king, and the flamerod sensor watches for flame initiation 9 When .
19 Components The following image and list outlines the typical di rect fired heater components and their fun ctions. 1. Gas Inlet – Main gas supply conn ection 2. Motor Starter – Contactor with overload protec tion to start and prot ect motor. 3.
20 Remote Panel Option The Remote Panel is a device used to control the ope r ation of the heater from a remote location. This unit is available in both a “2 Position” or “3 Position ” configuration and with or with out a cooling output.
21 Troubleshooting The following tables list cause s and corrective actions for possibl e problems wit h direct fired heater units. Review these lists prior to consulting manufa cturer.
22 Burner Troubleshooting Chart Problem Potential Cause Corrective Action Pilot Does Not Light/Stay Lit Main gas if off Open main gas valve Air in gas line Purge gas line Dirt in pilot orifice Clean o.
23 Remote Panel Troubleshooting Chart Light Indication Condition Possible Cause No Lights Power not available to Remote Panel Bad voltage to unit Main disconnect i n “OFF” Position Circuit breaker.
24 Is Freeze-Stat open? Adjust or Replace Is end switch on Moto ri ze d Damp er closed? Adjust or Replace actuator YES YES NO Nothing Happe ns Is Overload tripped on starter? Reset & m easure FLA of m otor.
25 MAINTENANCE To guarantee trouble fre e operation of this heater, th e man ufacturer sugge sts following these guid elines. Most problems associated with fan failures are directly related to poor servi ce and maintenance.
26 Burner Orifice Drill Size Orifice Drill Size Gas Port 31 Air Port 43 2 weeks after startup 1. Belt tension should be checked after the first 2 weeks of fan ope ration. Belts tend to stretch and settle into pulleys after an in itial start-up sequence.
27.
May 2008 Rev. 11 28 Start-Up and Maintenance Documentation START-UP AND MEASUREMENTS SHOULD BE PERFORMED AFTER THE SYSTEM HAS BEEN AIR BALANCED AND WITH TH E HEAT ON (Warranty will be void without com.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Energy Tech Laboratories MR212 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Energy Tech Laboratories MR212 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Energy Tech Laboratories MR212 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Energy Tech Laboratories MR212 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Energy Tech Laboratories MR212, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Energy Tech Laboratories MR212.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Energy Tech Laboratories MR212. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Energy Tech Laboratories MR212 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.