S1C/S1H Single-Zone & S2C Dual-Zone SiDe DiSCHarge DuCtleSS Split SyStem ConDenSing unitS P/N# 240005897 Rev . B [05/08] Straight Cool/hea t pump S1C/S1h Nominal Circuit Capacities S1C/S1H: 9,000,.
www .enviromaster.com Side Discharge Condensers 2 inSt alla tion, opera tion anD maintenanCe manUal S1C/S1H Single-Zone & S2C DUal-Zone ConDenSing UnitS Shipping Damage MUST be Reported to the Carrier IMMEDIA TEL Y!!! Examine the exterior . Remove cover and examine compressor and piping for signs of damage.
www .enviromaster.com Side Discharge Condensers 3 proDUCt DeSCription The AmericaSeries S1C/H and S2C condensing units are, air-cooled, vertically arranged side discharge, high efciency units designed specically to meet or ex - ceed a 13 SEER rating.
www .enviromaster.com Side Discharge Condensers 4 itemS For ConSiDera tion • Locate the unit as close to the indoor section as possible. ( S ee T ubing Specications chart on pape 7.) • If the unit is used for low ambient cool - ing down to 32°F , this option must be specied to prevent system damage.
www .enviromaster.com Side Discharge Condensers 5 inSt alla tion inStrUCtionS Unit moUnting inStrUCtionS Continued 5. Insert lag bolts through the holes in the bottom of the unit and tighten to secure. 6. Insert lag bolts through the holes in the feet on the back of the unit and tighten to secure.
www .enviromaster.com Side Discharge Condensers 6 inSt alla tion inStrUCtionS c. Slide the side panel out to access the high/low electrical connections and wire diagram. Note: Remove the plastic edge guards from the holes and replace with a water- tight strain relief tting (High V) and a split grommet tting ( l ow V) 5.
www .enviromaster.com Side Discharge Condensers 7 inSt alla tion inStrUCtionS 10. T o replace side panel slide the slotted holes of the panel onto the loosened screws of the front panel so that the edge of th e front pa nel cove rs th e edge of the side panel.
www .enviromaster.com Side Discharge Condensers 8 Condenser Evaporator Figure 1 Condenser Evaporator 30' 15' p-trap inSt alla tion • A P-trap is recommended when the suc - tion riser is equal to or greater than 20 feet in height .
www .enviromaster.com Side Discharge Condensers 9 inSt alla tion inStrUCtionS reFrigerant piping Continued 2. Protect the valves by wrapping with a wet rag "heat sink" before brazing. 3. We recommend the use of a shield (can be made from some scrap metal) to protect the paint.
www .enviromaster.com Side Discharge Condensers 10 inSt alla tion inStrUCtionS 9. Refer to Charts on page 12 to “ne tune” the refrigerant charge to meet your conditions.
www .enviromaster.com Side Discharge Condensers 11 The units are delivered precharged with refrigerant for the condenser coil and the evaporator . Charging of the eld installed piping is required. Refer to the refrigerant charge table for the proper amount to be added for the applications interconect piping.
www .enviromaster.com Side Discharge Condensers 12 Single Zone opera tion CHartS.
www .enviromaster.com Side Discharge Condensers 13 Single Zone opera tion CHartS.
www .enviromaster.com Side Discharge Condensers 14 Single Zone opera tion CHartS.
www .enviromaster.com Side Discharge Condensers 15 Single Zone opera tion CHartS.
www .enviromaster.com Side Discharge Condensers 16 Single Zone Hea t pUmp opera tion CHartS.
www .enviromaster.com Side Discharge Condensers 17 Single Zone Hea t pUmp opera tion CHartS.
www .enviromaster.com Side Discharge Condensers 18 DUal Zone opera tion CHartS.
www .enviromaster.com Side Discharge Condensers 19 opera tion anD maintenanCe The S1C/H and S2C outdoor sections are the compressor bearing units of the system. It operates at the command of the indoor section or room thermostat. Therefore, the system operation will be described in the manual pertaining to the indoor section.
www .enviromaster.com Side Discharge Condensers 20 Single-Zone anD DUal-Zone SeqUenCe oF opera tion Note: For remote wall mounted ther - mostat operation be sure to select EMI p/n 240004180 or a suitable 24 v , two sage heating, heat pump thermostat.
www .enviromaster.com Side Discharge Condensers 21 DFT TST R and DF2 DeFroSt Control boarD teSting DeFroSt opera tion USing teSt pinS Single-Zone anD DUal-Zone SeqUenCe oF opera tion W arning! B ef or e re mo vi ng t he ac ce ss pa ne ls to the unit make sure that all power is dis - c on ne ct ed fr om th e un it .
www .enviromaster.com Side Discharge Condensers 22 moUnting DimenSionS model Size a b C D S1C/S1H 9, S1C/S1H 2 4 ⅝” 14 11 / 16 ” 3” 12 7 / 16 ” S1C/S1H 8, S1C/S1H 2 4 ⅝” 22 11 / 16 ” 3.
www .enviromaster.com Side Discharge Condensers 23 NOtE: All EMI products are subject to ongoing development. Design and specications may change without notice. CAC WLC/WLH * Important - This system has been designed and manufactured to meet ENERGY ST AR criteria for energy efciency .
www .enviromaster.com Side Discharge Condensers 24 S1C/S1H Single Zone S1H eleCtriCal SpeCiFiCa tionS model # V olts/HZ/pH Fan motor Compressor t otal ampS min V olt m.C.a. HaCr brKr ampS Hp rla lra S1H9A 1 15/60/1 1.4 0.125 6.6 39.2 8.0 104 9.7 15 S1H2A 1 15/60/1 1.
www .enviromaster.com Side Discharge Condensers 25 WLC CAC S2C Cooling SYStemS WitH S2C SiDe DiSCHarge Cassette Condenser btuh Seer SHr eer ref. CAC12 + CAC12 S2C99 18,000 13.0 .81 1 1.7 R22 CAC12 + CAC12 S2C22 23,000 13.0 .74 1 1.8 R22 CAC12 + CAC12 S2C92 21,000 13.
www .enviromaster.com Side Discharge Condensers 26 The T est Unit Performance Data sheet below is provided for use by a qualied service professional in the event that there is a problem with the unit. In order for our T echnical Service Department to better serve you, please complete and have this information ready when calling.
www .enviromaster.com Side Discharge Condensers 27 emi’S proDUCt line inDoor UnitS oUtDoor UnitS S1C & S1H Single Zone Side Discharge S2C &S2H Dual Zone Side Discharge WLC/WLH High Wall Air .
Phone: 1-800-228-9364 Fax: 1-800-232-9364 5780 Success Drive, Rome, NY 13440.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il EMI Volts/HZ/pH è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del EMI Volts/HZ/pH - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso EMI Volts/HZ/pH imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul EMI Volts/HZ/pH ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il EMI Volts/HZ/pH, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del EMI Volts/HZ/pH.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il EMI Volts/HZ/pH. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo EMI Volts/HZ/pH insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.