EMI AMErIcA SErIES Mul tI-ZonE HEA t PuMP condEnSIng unItS P/N# 240006458 Rev . B [10/08] Enviromaster International LLC 5780 Success Dr . Rome, NY 13440 www .
www .enviromaster .com 2 multi-zone Heat Pump Condensing units inST alla Tion, oPera Tion and mainTenanCe manual EMI AMErIcA SErIES Mul tI-zonE HEA t PuMP condEnSIng unItS Shipping Damage MUST be Repo.
www .enviromaster .com 3 multi-zone Heat Pump Condensing units EMI AMErIcA SErIES Mul tI-zonE HEA t PuMP condEnSIng unItS • Co mp re ss or a nd F a n Mo to r Co nt ac to r • Capacitor • Low V ol.
www .enviromaster .com 4 multi-zone Heat Pump Condensing units S2HB InSt AllA tIon InStructIonS SEctIon 1. Loosen the screws on left and right sides of the front panel. (Do not remove these screws.) 2. Remove the screws on the front of the panel. 3. T o remove front panel: 4.
www .enviromaster .com 5 multi-zone Heat Pump Condensing units S2HB ElEctrIcAl WIrIng InSt AllA tIon SEctIon 3. Use only HACR type breakers or time delay fuses. Select the wi re size accord - ing to the ampacity rating. 4. T o access electrical connections and wiring diagram: a) Remove the screws on the side panel adjacent to the back panel.
www .enviromaster .com 6 multi-zone Heat Pump Condensing units 8. Check wiring diagram for the re - quired number of low voltage wires to be run between indoor and out- door sections.
www .enviromaster .com 7 multi-zone Heat Pump Condensing units t2HB, t3HB , And t4HB InSt AllA tIon InStructIonS SEctIon noTe: For S2HB installation refer to the S2HB Installation Instruction in this manual. 1. Remove the screw on the back panel. 2. R emove pa ne l t o e xp os e el e tr ic al wiring.
www .enviromaster .com 8 multi-zone Heat Pump Condensing units 5. with a screw - d r i v e r p u n c h out and remo ve the knock-outs in the low & high V olt elec - trical connec - tion box. Note: Power should be run to a weather proof disconnect box usually within 3 feet of the unit.
www .enviromaster .com 9 multi-zone Heat Pump Condensing units The system will support refrigerant runs to the inside unit of up to 100' equivalent feet with a 35' rise included.
www .enviromaster .com 10 multi-zone Heat Pump Condensing units • A P-trap is recommended when the suc- tion riser is equal to or greater than 20 feet in height. • When the condenser is installed above the evaporator , the P-trap will help the return of oil back to the compressor .
www .enviromaster .com 11 multi-zone Heat Pump Condensing units 8. Evacuate line to 500 microns or less to ensure all moisture has been removed and there are no leaks. It is ill eg al to disc ha rge ref rig era nt into th e at mo sp her e. Us e pr op er re cl ai min g methods & equipment when installing or servicing this unit.
www .enviromaster .com 12 multi-zone Heat Pump Condensing units 9. Once ce rt ai n of a go od e va c ua ti on an d l ea k fr e e j oi nt s, b ac k- se at th e v al ve s ( co un te r- cl oc kw is e ) to op en an d al l ow factory charge to ll lines and indoor unit.
www .enviromaster .com 13 multi-zone Heat Pump Condensing units The use of the superheat method is highly recommended for eld charging or checking th e exi st in g re fr ig era nt cha rge in a sys tem . Because each installation is different in terms of ind oo r ai r flo w , ref ri ger an t lin e le ng th, etc .
www .enviromaster .com 14 multi-zone Heat Pump Condensing units Mul tI-zonE HEA t PuMP fIEld cHArgIng.
www .enviromaster .com 15 multi-zone Heat Pump Condensing units Mul tI-zonE HEA t PuMP fIEld cHArgIng.
www .enviromaster .com 16 multi-zone Heat Pump Condensing units Mul tI-zonE HEA t PuMP fIEld cHArgIng.
www .enviromaster .com 17 multi-zone Heat Pump Condensing units Mul tI-zonE HEA t PuMP fIEld cHArgIng.
www .enviromaster .com 18 multi-zone Heat Pump Condensing units ST arTing THe uniT • Before starting the unit in cool weather , power the system 24 hours before at - tempting to start. • Do a nal system check using the super- heat/subcooling method.
www .enviromaster .com 19 multi-zone Heat Pump Condensing units St Art -uP And trouBlESHoo tIng tESt ProcEdurE The T est Unit Performance Data sheet below is provided for use by a qualied service professional. In order for our T echni - cal Service Departme nt to better serve you, please complete and have this information ready when calling.
www .enviromaster .com 20 multi-zone Heat Pump Condensing units Mul tI-zonE condEnSEr SEquEncE of oPErA tIon EM I Amer ica Series m ulti- zone he at pum p conden sers are desi gned to oper ate with EMI America Series indoor air han - dlers. Both the condenser (outdoor unit) and evaporator (indoor unit) have a hi gh V olt service connection.
www .enviromaster .com 21 multi-zone Heat Pump Condensing units DFT TST R and DF2 deFroST ConTrol TeSTing deFroST oPera Tion uSing TeST PinS Single-Zone and dual-Zone SequenCe oF oPera Tion W arning! B ef or e re mo vi ng th e ac ce ss p an el s to the unit make sure that all power is dis - c on ne ct ed fr om t he un it .
www .enviromaster .com 22 multi-zone Heat Pump Condensing units Mul tI-zonE condEnSEr SEquEncE of oPErA tIon Refer to the indoor unit for the proper low V olt interconnect wiring. LOw VOL T INTERCONNECT DIAgRAMS oPera Tion and mainTenanCe The EMI America Series outdoor section is th e com pr es so r be ar in g uni t of the sy ste m.
www .enviromaster .com 23 multi-zone Heat Pump Condensing units S2HB dIMEnSIonS And SPEcIfIcA tIonS noTe: All EMI products are subject to ongoing development programs so design and specications may change without notice. S2HB eleCTriCal SPeCiFiCa TionS model (1) Vol TS/HZ/PHaSe Fa n ComPreSSor 1 ComPreSSor 2 ToT al amPS min.
www .enviromaster .com 24 multi-zone Heat Pump Condensing units S2HB Sy StEM PErforMAncE S2HB / CaH SYSTem PerFormanCe model Cooling Hea Ting S2HB (Outdoor) indoor units Btuh Seer SHr eer Btuh HSPF C.o.P . 9900 CAH12 + CAH12 18,600 13.0 79 1 1.4 14,600 7.
www .enviromaster .com 25 multi-zone Heat Pump Condensing units S2HB Sy StEM PErforMAncE S2HB / unH Side diSCHarge model Cooling Hea Ting S2HB (Outdoor) indoor units Btuh Seer SHr eer Btuh HSPF C.o.P . 9900 UNH09 + UNH09 18,600 13.0 .75 11.9 14,800 7.
www .enviromaster .com 26 multi-zone Heat Pump Condensing units t2HB, t3HB , And t4HB dIMEnSIonS And SPEcIfIcA tIonS noTe: All EMI products are subject to ongoing development programs so design and specications may change without notice. lInE SEt , Sound & WEIgHt dA t A model line Set diameters Sound Weight liquid Suction dBa lbs.
www .enviromaster .com 27 multi-zone Heat Pump Condensing units t2HB, t3HB , And t4HB SPEcIfIcA tIonS noTe: All EMI products are subject to ongoing development programs so design and specications may change without notice.
www .enviromaster .com 28 multi-zone Heat Pump Condensing units WlH / t2HB, t3HB , or t4HB SyStEM PErforMAncE d A t A model Cooling Heating outdoor indoor air Handler Btuh Seer SHr eer Btuh HSPF CoP T2HB8800 (2) WLH24 36000 13 0.72 12.1 26800 7.7 3.3 T2HB8400 (2) WLH24 42000 13 0.
www .enviromaster .com 29 multi-zone Heat Pump Condensing units CAH T2HB, T3HB, or T4HB T op Discharge t2HB, t3HB , And t4HB SPEcIfIcA tIonS cAH / t2HB, t3HB , or t4HB SyStEM PErforMAncE d A t A model Cooling Heating outdoor indoor air Handler Btuh Seer SHr eer Btuh HSPF CoP T2HB8800 (2) CAH24 36000 13 0.
www .enviromaster .com 30 multi-zone Heat Pump Condensing units UNH T2HB, T3HB, or T4HB T op Discharge unH / t2HB, t3HB , or t4HB SyStEM PErforMAncE d A t A Model Cooling Heating Outdoor Indoor Air Handler Btuh SEER SHR EER Btuh HSPF COP T2HB8800 (2) UNH24 36000 13 0.
www .enviromaster .com 31 multi-zone Heat Pump Condensing units emi’S HigH Seer ProduCT line eV aPora TorS CondenSerS wLC/wLH High wall Evaporator CAC/CAH Cassette Evaporator S1C & S1H Single Zo.
Phone: 1-800-228-9364 Fax: 1-800-232-9364 5780 Success Drive, Rome, NY 13440.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il EMI T2HB è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del EMI T2HB - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso EMI T2HB imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul EMI T2HB ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il EMI T2HB, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del EMI T2HB.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il EMI T2HB. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo EMI T2HB insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.