www .rosemount.com Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 Integral Mount or Remote Mount Magnetic Flowmeter System with F OUNDATION ™ fieldbus.
.
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Integral Mount or Remote Mount Magnetic Flo wmeter System with F OUNDATION ™ fieldb us NOTICE Read this manual before working with the prod uct.
.
Reference Manual 00809-0100- 4663, Rev BA January 2010 TOC -1 Rosemount 8732 SECTION 1 Introduction System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Safety Messages . . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 TOC -2 Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 TOC -3 Rosemount 8732 SECTION 6 Maintenance and Troubleshooting Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 Installation Check and Guide .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 TOC -4 APPENDIX D Digital Signal Processing Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1 Warnings . . . . . . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 TOC -5 Rosemount 8732 APPENDIX F Resource Block Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1 Parameters and Descriptions . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 TOC -6.
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 1 Introduction System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 1- 1 Safety Messages . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 1-2 SAFETY MESSAGES Procedures and instr uctions in this man ual may require special p recautions to ensure the safety of th e personnel pe rforming the opera tions. Refer to the safety messages listed at the beginni ng of each section before performing any operations.
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 2 Inst allation Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 T ransmitter Symbols . . . . . . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-2 TR A N S M I T T E R SYMBOLS Caution symbol — check product document ation for details Protective conductor (grou nding) ter.
Reference Manual 00809-0100- 4663, Rev BA January 2010 2-3 Rosemount 8732 Figure 2-1. Rosemount 8732 Dimensional Drawing ENVIRONMENT AL CONSIDERATIONS T o ensure maximum transmitter life, avoid temperature extremes and vibration.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-4 Surface Mounting T o surface mount the transmitte r: 1. Attach the 8732 to the mountin g location using the mounting screws. Identify O ptions and Configurations The st andard application of the Rosemount 8732 inclu des a F OUNDATION fieldbus output.
Reference Manual 00809-0100- 4663, Rev BA January 2010 2-5 Rosemount 8732 1. Disconnect power to the tran smitter . 2. Remove electronics cover . 3. Remove display if applicable. 4. Identify the location of each switch (see Figure 2- 2). 5. Change th e set tin g of th e de sir ed switch e s with a sm all scr ewd r iver .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-6 Conduit Cables Run the ap propriate si ze cable throug h the conduit connections in your magnetic flowmeter system. Run the po wer cable from the power source to the transmitter .
Reference Manual 00809-0100- 4663, Rev BA January 2010 2-7 Rosemount 8732 Requirement s for 12-42 V DC Power Su pply Units powe red with 12- 42 V DC may dr aw up to 1 amp of curren t. As a resu lt, the input powe r wire must meet cert ain gauge requiremen ts.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-8 Figure 2-5. AC T ransmitter Power Connections Connect F OUNDATION fieldbus Wiring The F OUNDATION fieldbus signal provides th e output information from the transmitter .
Reference Manual 00809-0100- 4663, Rev BA January 2010 2-9 Rosemount 8732 NOTE The number of devices on a fieldbus se gment is limited by the power supply voltage, th e resistance of the cable, an d the amount of current drawn by each device.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-10 Figure 2-7. Ros em o un t 87 32 T ransmitt er Field Wirin g Integrated Power Conditioner and Filter Te r m i n a t o r s 6234.
Reference Manual 00809-0100- 4663, Rev BA January 2010 2-1 1 Rosemount 8732 SENSOR CONNECTIONS This section covers the st eps required to physically install the transmitter including wiring and calibration.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-12 Rosemount recommends usin g the combination signal and coil drive for N5 , E5 approved sensors for optimum pe rformance. Remote transmitter inst allations require equal lengths of signal and coil drive cables.
Reference Manual 00809-0100- 4663, Rev BA January 2010 2-13 Rosemount 8732 Sensor to Remote Mount T ransmitter Connections Connect coil drive and electrode cables as shown in Figure 2-10. Do not connect AC power to the sensor or to terminals 1 and 2 of t he transmitter , or replacement of the electronics board w ill be necessary .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 2-14.
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 3 Configuration Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Local Operator Interface . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-2 Figure 3-1. Local Operator Interface Keypad Dat a Entry The LOI keypad does not have nu merical keys. Numerical data is en tered by the following proced ure. 1. Access the appropriate function .
Reference Manual 00809-0100- 4663, Rev BA January 2010 3-3 Rosemount 8732 T able V alue Example Setting the TUBE SIZE: 1. Press the DOWN arrow to access the menu. 2. Select line size from the B asic set-up menu. 3. Press the UP or DOWN arrow to increa se/decreas e (incrementally) the tube size to the next value.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-4 T able 3-2. LOI Menu T re e Dia g C o n t r o ls Ba s i c D i a g A dv a nc ed D i a g Va r i a b l e s Tr i m s St a t u s E .
Reference Manual 00809-0100- 4663, Rev BA January 2010 3-5 Rosemount 8732 DIAGNOSTIC MESSAGES The following error messages ma y appear on the LOI screen.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-6 Analog Output – The a nalog outpu t variab le provides the analog value for the flow rate. The analog outp ut refers to th e industry st andard output in th e 4–20 mA range.
Reference Manual 00809-0100- 4663, Rev BA January 2010 3-7 Rosemount 8732 Measured Reverse T ot al Measured reverse tot al provides the outp ut reading of th e tota lizer . This value is the amount of process fluid that has p assed through the flowmeter in the reverse direction since the tot alizer was la st reset.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-8 Options for Flow Rate Units Special Unit s The Rosemount 8732 provides a selection of standard unit configurations that meet the needs of most applications (see “Flow Unit s” on page 3-7).
Reference Manual 00809-0100- 4663, Rev BA January 2010 3-9 Rosemount 8732 Base V olume Unit Base volume unit is the unit from which the conver sion is being made. Set this variable to the appr op r iate op tio n. Conversion Nu mb er The special unit s conversion number is used to convert ba se un its to special units.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-10 PV URV (Upper Range V alue) The upper range value (UR V), or analog output range, is preset to 30 ft/s at the factory . The units that appear will be the same as thos e selected under the units parameter .
Reference Manual 00809-0100- 4663, Rev BA January 2010 3-1 1 Rosemount 8732 Calibration Number The tube calibratio n number is a 16-digit number us ed to identify flowtube sensors calib rated at the Rosemount fa ctory . T he calibration number is also printed inside the flowtube sensor terminal block or on the flowtube sensor name plate.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 3-12.
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 4 Operation Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Diagnostics . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-2 Empty Pipe Detection T urn the empty pipe diagnostic on or of f as req uired by the application.
Reference Manual 00809-0100- 4663, Rev BA January 2010 4-3 Rosemount 8732 EP T rigger Level Limits: 3 to 2000 Configure the thre shold limit that the empty p ipe value mu st exceed bef ore the diagnostic alert activates. De fault from the factory is s et to 100.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-4 8714i Result s Review the result s of the most recently performed 8714i Meter V erification test. Information in this section details th e measurements taken and i f the meter p assed the ve rification test.
Reference Manual 00809-0100- 4663, Rev BA January 2010 4-5 Rosemount 8732 Sensor Calibration Result Displays the result of the sensor ca libration verification test as p ass or fail. For more detai ls on this parameter see App end ix C: Diagnostics. Coil Circuit Result Displays the result of the coil circuit test as pass or fail.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-6 Re-Signature Meter Have the transmitter measure and stor e the sensor signature values.
Reference Manual 00809-0100- 4663, Rev BA January 2010 4-7 Rosemount 8732 Measurement s View the me asured values t aken during the meter veri fication process. These values are comp ared to the signature values to determine if the test p asses or fails.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-8 Diagnostic V ariables From this menu, all of the diagnostic variable values can be reviewed. This information can be used to get more in formation about the tran smitter , sensor , and process, or to get more det ail about an alert that may have activated.
Reference Manual 00809-0100- 4663, Rev BA January 2010 4-9 Rosemount 8732 8714i Result Displays the results of the 8714i Me ter V erification test as p ass or fail. For more detai ls on this parameter see App end ix C: Diagnostics. Simulated V elocity Displays the test velocity used to ve rify transmitter calibration.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-10 Electronics T rim Electronics trim is the function by whic h the factory calibrates the transmitter . This procedure is rarely needed by customers. It is only necessary if you suspect the Rosemount 8732E is no longer accu rate.
Reference Manual 00809-0100- 4663, Rev BA January 2010 4-1 1 Rosemount 8732 Auto Zero The auto zero function initializes th e transmitter for use with the 37 Hz coil drive mode only . Run this function on ly with the transmitter and sensor installed in the process.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-12 ADVANCED CONFIGURATION In addition to the basic configuration op tions and the diagnostic information and controls, the 8 732 has many advanced functions that can also be configured as req u ire d by th e ap plic ation.
Reference Manual 00809-0100- 4663, Rev BA January 2010 4-13 Rosemount 8732 Cal Min Sp an The PV minimum span is the minimum flow range that must separate the minimum and maximum configure d PV Range values. Reverse Flow Enable or disable the transmitte r ’s ability to read reverse flow .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-14 Control When ON is selected, the Rosemoun t 8732 E output is derived using a running average of the indivi dual flow in puts. Signal processing is a sof tware algorithm that examines th e quality of the electrode signal against user-specified tolerances.
Reference Manual 00809-0100- 4663, Rev BA January 2010 4-15 Rosemount 8732 For example, if the number of samples se lected is 100, then the response time of the system is 10 seconds.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-16 Sensor T ag Sensor tag is the quickest and shortest way of identifying an d distinguishing between sensors. Sensors can be t agged according to the re quirements of your application.
Reference Manual 00809-0100- 4663, Rev BA January 2010 4-17 Rosemount 8732 Electrode T ype Electrode type enables you to select t he electrode type for your magnetic transmitter system. This variable only needs to b e changed if you ha ve replaced electrodes or if you have replaced your sensor .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 4-18 Block Mode: T arget Operator requested m ode for the functi on bl ock. Only one selection may be made. Options include: Auto Use this mode when all configuratio n changes to the block are complete and the transmitter is ready to be returned to service.
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 5 Sensor Inst allation Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Sensor Handling . . . . . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-2 Explosions could resu lt in death or serious injury: Installation of this transmitter in an explosiv e environment must be in accordance with the appropriate local, national, and international standards, codes, and prac tices.
Reference Manual 00809-0100- 4663, Rev BA January 2010 5-3 Rosemount 8732 SENSOR HANDLING Handle all part s carefully to prevent damage. Whenever possible, transport the system to the installa tion site in the original shipping cont aine rs.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-4 SENSOR MOUNTING Physical mounting of a sensor is similar to installing a typical section of pipe. Conventional tools, equip ment, and accessories (bolt s, gaskets, and grounding hard ware) are required.
Reference Manual 00809-0100- 4663, Rev BA January 2010 5-5 Rosemount 8732 Figure 5-4. Incline or Decline Orientation Horizontal installation should be restri cted to low piping sections that are normally full. Orient the electr ode plan e to within 45 degrees of horizont al in horizontal inst allations.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-6 The electrodes in the Rosemount 871 1 are properly oriented wh en the top of the sensor is either vertica l or horizo ntal, as shown in Figure 5-6.
Reference Manual 00809-0100- 4663, Rev BA January 2010 5-7 Rosemount 8732 INST ALLATION (FLANGED SENSOR) The followin g section shou ld be used as a guide in t he installation of the flange-type Rosemount 870 5 and Rose mount 8707 High-Signal Sensors.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-8 NOTE Do not bolt one side at a time. T ighten each sid e si multaneously . Example: 1. Snug left 2. Snug righ t 3. T ighten left 4. T ighten right Do not snug and tighten the up stream side and then snug and tighten the downstream side.
Reference Manual 00809-0100- 4663, Rev BA January 2010 5-9 Rosemount 8732 Figure 5-10. Flange Bolt T orquing Sequence T able 5-2. Flange Bolt T orque and Bolt Load S pecifications for Rosemount 8705 P.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-10 INSTALLATION (W AFER SENSOR) The following section should be use d as a guide in the installation of t he Rosemount 871 1 Sensor . Refer to page 5-7 for inst allation of the flange-type Rosemount 8705 and 8707 High-Signal sensor .
Reference Manual 00809-0100- 4663, Rev BA January 2010 5-1 1 Rosemount 8732 3. Place the sensor between the flanges. Make sure that the ce ntering rings are properly placed in the stu ds. The studs should be aligned with the markings on the rings tha t correspond to the flange you are using.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-12 INST ALLATION (SANIT ARY SENSOR) Gasket s The sensor requires a gasket at each of its connections to a djacent devices or piping. The gasket material selected must be compatible with the process fluid and operating co nditions.
Reference Manual 00809-0100- 4663, Rev BA January 2010 5-13 Rosemount 8732 NOTE Consult factory for installations requirin g cathodic protection or situations where ther e are high cu rrents or high pot ential in the pro cess. The sensor case should alwa ys be earth groun ded in accordance with national and local electrica l codes.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-14 Figure 5-14. Grounding with Grounding Rings or Lining Protectors Figure 5-15.
Reference Manual 00809-0100- 4663, Rev BA January 2010 5-15 Rosemount 8732 Figure 5-16. Grounding with Grounding Electrodes.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-16 PR OCESS LEAK PR OTECTION (OPTIONAL) The Rosemount 8705 and 8707 High- Signal Sensor housing is fabricated from carbon steel to perform two sepa rate functions.
Reference Manual 00809-0100- 4663, Rev BA January 2010 5-17 Rosemount 8732 Relief V alves The first optional configuration, identif ied by the W1 in the model number option code, uses a completely welded coil housing. This configuration doe s not provide sep arate electrode comp artments with externa l el ectrod e a ccess.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 5-18 Figure 5-19. Housing Configuration — Sealed Electrode Compartmen t (O ption Code W3) If necessary , capture any process fluid lea kage, connect the appropriate piping to the d rainports, and p rovide for proper disp osal (see Figure 5-19).
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Section 6 Maintenance and T roubleshooting Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 6-1 Inst allation Check and Guide .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 6-2 INST ALLATION CHECK AND GUIDE Use this guide to check new installatio ns of Rosemount magnetic flowmeter systems that appear to malfunction. Before Y ou Begin Tr a n s m i t t e r Apply power to your system before ma king the following transmitt er checks.
Reference Manual 00809-0100- 4663, Rev BA January 2010 6-3 Rosemount 8732 DIAGNOSTIC MESSAGES Problems in the magnetic flo wmeter system are u sually indicated by incorr ect output readings from the syste m, error me ssages, or failed te st s. Consider all sources in identifyin g a pr ob lem in you r sys te m.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 6-4 T able 6-2. Rosemount 8732 Advanced Diagnos tic Messag es (Suite 1 - Option Cod e D01) T able 6-3.
Reference Manual 00809-0100- 4663, Rev BA January 2010 6-5 Rosemount 8732 TR A N S M I T T E R T ROUBL ESHOOTING T able 6-4. Advanced T roubleshooting–Rosemount 8 732 Symptom Potential Cause Correct.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 6-6 Meter output is unstable Medium to low conductivity flu ids (10– 25 microsiemens/cm) combined with cable vibration or 60 Hz .
Reference Manual 00809-0100- 4663, Rev BA January 2010 6-7 Rosemount 8732 QUICK T ROUBL ESHOOTING Step 1: W iring Errors Th e most common magmeter problem is wiring between the se nsor and the transmitte r in remote moun t inst allations.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 6-8 T o test the sensor , a multimeter cap able of measuring conductance in nanosiemens is pref erred.
Reference Manual 00809-0100- 4663, Rev BA January 2010 6-9 Rosemount 8732 Figure 6-1. Sensor Cir cuit Diagram Step 4: Uninst alled Sensor T est s An uninstalle d sensor can also be used for sensor troubleshooting. T o interpret the result s, the hazardous locatio n certification for the sensor must be known.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 6-10 Figure 6-2. 45° Elec trode Plane T o insure accuracy of re sistance re adings, zero out multimeter by shorting and touching the leads together .
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix A Reference Dat a Functional Specificat ions . . . . . . . . . . . . . . . . . . . . . . . . . p age A-1 Foundation™ fieldbus S pecifications . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 A-2 Figure A-2. Ap parent Power DC Supply Current Requirements Units powe red by 12 -4 2 V DC po wer sup ply may dr aw up to 1 amp of current steady state.
Reference Manual 00809-0100- 4663, Rev BA January 2010 A-3 Rosemount 8732 Enclosure Ra tin g NEMA 4X CSA T ype 4X, IEC 60529, IP66 (transmitter), Pollution Degree 2 Output Sign al Manchester-encoded digit al signal that conforms to IEC 1 158-2 and ISA 50.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 A-4 F OUNDATION ™ FIELDBUS SPECIFICATIONS Schedule Entries Seven (7) Links T wenty (20) Virtual Communications Relationship s (VCRs) One (1) predefined (F6, F7 ) Nineteen (19) configurable (see T able 1) T able A-1.
Reference Manual 00809-0100- 4663, Rev BA January 2010 A-5 Rosemount 8732 8732E transmitters and other manufacture r ’s sensors can be calibrated at known process conditions or at the Ro semount NIST -T raceab le Flow Facility . T ransmitters calibrated on site require a two-step procedure to match a known flow rate.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 A-6 Optional high accuracy is ±0.15% of ra te ±1.0 mm/sec from 0.04 to 13 ft/s (0.01 to 4 m/s); above 13 ft/s (4 m/s), the system has an accuracy of ±0.18% of rate. Rosemount 8732E with 8721 Senso r: S tan dard system accuracy is ±0.
Reference Manual 00809-0100- 4663, Rev BA January 2010 A-7 Rosemount 8732 St ability ±0.1% of rate over six months Ambient T emperature Effect ±0.25% change over operating temper ature range EMC Compliance EN61326-1 1997 + A1/A2/A3 (Industria l) electromagnetic compatibility (EMC) for process and laborato ry apparatus.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 A-8.
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix B Approval Information Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age B-1 Approved Manufacturing Locations . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-2 Rosemount 8721 Sanitary Magmeter Sensors in line sizes of 1 1 / 2 in. and larger: Module A Conformity Assessment All other Rosemount 8705/8707/87 1 1/8721 Sensors — in line sizes of 1 in.
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-3 Rosemount 8732 HAZARDOUS LOCATIONS PRODUCT APPROVALS OFFERING The Rosemount 8700 Series mag netic flowmeters offer many different hazardous locations certifications. The table below provides an overview of the available hazardous are a approv al options.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-4 T able B-3. A TEX Approvals Offering T able B- 4. IECEx Approva ls Offering T ransmitter 8732E 8712D (1) (1) Remote T ransmitt.
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-5 Rosemount 8732 HAZARDOUS LOCATION CERTIFICATIONS Equivalent Hazardous Loc ation Certification s for sensor an d transmitte r must match in integrally-mounted magnetic flowmeter systems. Remote-mounted systems do not require matched hazardou s location certification o ption codes.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-6 North American Certifications Factory Mutual ( FM) NOTE For intrinsically safe (IS) outputs on the 8732E output option code B must be selected. IS outputs for Class I, Division 1, Groups A, B, C, D.
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-7 Rosemount 8732 European Certifications E1 A TEX Flameproof Hydrogen gas group 8732 - Certificate No.: KEMA 07A TEX0073 X II 2G Ex de [ia] IIC T6 (-50 °C Ta +60 °C) with LOI T6 (-20 °C Ta +60 °C) V max = 250 V AC or 42 V DC 0575 ED A TEX Flameproof 8732 - Certificate No.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-8 INSTALLATION INSTRUCTIONS: The cable and conduit entry devices and the closing elements shall be of a certified increased safety type, suitable for the conditions of use and correctly installed.
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-9 Rosemount 8732 SPECIAL CONDITIONS FOR SAFE USE (KEM 07.0038X): If the Rosemount 8732 Flow Transmitter is used integrally with the Rosemount 8.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-10 North American Certifications Factory Mutual ( FM) N0 Division 2 Approval for Non-Flammable Flui ds (All Sensors) Class I, Di.
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-1 1 Rosemount 8732 SPECIAL CONDITIONS FOR SAFE USE (X): The relation between ambient temperatur e, process temperature and temperature class is to be taken from the table under (15-description) above.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-12 T able B-7. Electrical Data Ro semount 8732 Flow T ransmitter Power supply: 250 V AC, 1 A or 42 Vdc, 2,5 A, 20 W maximum Foun.
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-13 Rosemount 8732 T able B-8. Relation between ambient temperature, pr ocess temperature, and temperatur e class (1) T able B-9.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-14 1.5 in. sensor size 149°F (65°C) 297°F (147°C) 160°F (71°C) 88°F (31°C) 55°F (1 3°C) 140°F (60°C) 307°F (153°C).
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-15 Rosemount 8732 Figure B-1. A T EX Installation (1 of 6).
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-16 Figure B-2. A T EX Installation (2 of 6).
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-17 Rosemount 8732 Figure B-3. A T EX Installation (3 of 6).
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-18 Figure B-4. A T EX Installation (4 of 6).
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-19 Rosemount 8732 Figure B-5. A T EX Installation (5 of 6).
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-20 Figure B-6. A T EX Installation (6 of 6).
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-21 Rosemount 8732 Figure B-7. FM Certified I.S. Output (1 of 4).
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-22 Figure B-8. FM Certified I.S. Output (2 of 4).
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-23 Rosemount 8732 Figure B-9. FM Certified I.S. Output (3 of 4).
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-24 Figure B-10. FM Certified I.S. Output (4 of 4).
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-25 Rosemount 8732 Figure B-1 1. CSA Certified I.S. Output (1 of 2).
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-26 Figure B-12. CSA Certified I.S. Output (2 of 2).
Reference Manual 00809-0100- 4663, Rev BA January 2010 B-27 Rosemount 8732 Figure B-13. CSA Installation.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 B-28 Figure B-14 . Factory Mu tual Hazardous Locations.
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix C Diagnostics Diagnostic A vailabil ity . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age C-1 Licensing and Enabling . . . . . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-2 LICENSING AND ENABLING All non-basic diagnostics must be licensed by order ing option code D01, D02, or both. In the event that a diagno stic optio n is not ordered, advanced diagnostics can be license d in the field through the use of a license key .
Reference Manual 00809-0100- 4663, Rev BA January 2010 C-3 Rosemount 8732 Empty Pipe V alue Reads the current Empty Pipe V alue. This is a read-only value. This number is a unitless number and is calculated based on multiple inst allation and process variables such as sensor type, line size, p rocess fluid propertie s, and wiring.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-4 T r oubleshooting Empty Pipe The following actions can be t aken if Empty Pipe detection is unexpe cted. 1. V erify the sensor is full. 2. V erify that the sensor has no t been installed with a measurement electrode at the top of the pipe .
Reference Manual 00809-0100- 4663, Rev BA January 2010 C-5 Rosemount 8732 T r oubleshooting Ground/Wiring Fault The transmitter detected high leve ls of 50/60 Hz noise caused by improper wiring or poor process grounding . 1. V erify that the transmitter is earth grou nded.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-6 High Process Noise Parameters The High Process Noise diagno stic has tw o read -only p arameters. It does no t have any configurable par ameters. This diagnostic requires that flow be present in the pipe and the velocity be > 1 ft/s.
Reference Manual 00809-0100- 4663, Rev BA January 2010 C-7 Rosemount 8732 1. Tu rn on the Digital Signal Process ing (DSP) technolo gy and follow the setup procedure (r efer to Appen dix D: Digital Signal Process ing).
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-8 The transmitter continuously mon itors signal amp litu des over a wide rang e of frequencies. For the high process noise diagnostic, the transmitter specifically looks at the signal amplitude at fr eque ncies of 2.
Reference Manual 00809-0100- 4663, Rev BA January 2010 C-9 Rosemount 8732 8714i Meter V erification T est Parameters The 8714i has a multitude of paramete rs that set the test criteria, test conditions, and scope of the calibration verification test.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-10 Empty Pipe Set the test criteria for the Empty Pipe condition. The factor y default for this value is set to three percent with limit s configurable between one and te n percent.
Reference Manual 00809-0100- 4663, Rev BA January 2010 C-1 1 Rosemount 8732 Viewing the 8714i Meter V erification Res ults Depending on the method us ed to view the results, they will be display ed in either a menu structure , as a method, or in th e repor t format.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-12 Actual V elocity Displays the velocity measured by the transmitte r during the transmitter calibration v erification proc ess. V elocity Deviat ion Displays the deviation in the actual velocity compared to th e simulated velocity in terms of a percentage.
Reference Manual 00809-0100- 4663, Rev BA January 2010 C-13 Rosemount 8732 Optimizing the 8714i Meter V erification The 8714i Meter V erification diagnostic can be optimized by setting the test criteria to the desired leve ls necessary to meet the co mpliance requ irements of the application.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-14 T r oubleshooting the 8714i Meter V erification T est In the event that the 8714i Meter V eri fi cation test fails, the following step s can be used to determin e the appropriate co urse of action.
Reference Manual 00809-0100- 4663, Rev BA January 2010 C-15 Rosemount 8732 Electrode Circuit Resist ance The Electrode Circuit Resist ance is a measurement of the electro de circuit health. This value is used as a baseline to determine if the electrode circuit is still operating correctly w hen the 8714i Meter V erification diagnostic is initiated.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 C-16 ROSEMOUNT MAGNETIC FLOWMETER CALIBRATION V ERIFICATION REPORT Calibration V erification Report Parameters User Name: ________.
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix D Digit al Signal Processing Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page D-1 Procedures . . . . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 D-2 PROCEDURES If the output of your Ro semount 8732 is unstable , first check the wiring and grounding associated with the magnetic flowmeter system.
Reference Manual 00809-0100- 4663, Rev BA January 2010 D-3 Rosemount 8732 This software techn ique, known as signal proc essing, “qua lifies” individual flow signals based on historic flow infor ma tion and three user-definable paramete rs, plus an on/off c ontrol.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 D-4 x : Input flow signal from sensor . o : Average flow signals and tra nsmitter output, determined by the “number of samples” parameter . T olerance band, determined by the “perce nt limit” parameter .
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix E Universal Sensor W iring Diagrams Rosemount Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age E-3 Brooks Sensors . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-2 T able E-1. Sensor Cross References Rosem ount T ransmitter Sensor Manufa cturer Page Number Rosemount Rosemount 8732 Rosemoun.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-3 Rosemount 8732 ROSEMOUNT SENSORS Rosemount 8705/8707/871 1/8721 Sensors to Rosemount 8732 T ransmitter Connect coil drive and electrode cables as shown in Figure . Figure E-1. Wiring Diagra m to a Rosemount 8732 T ransmitter T able E-2.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-4 Rosemount 8701 Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-2 on page E-4. Figure E-2. Wiring Diagra m for Rosemount 8701 Sensor and Rosemount 8732 T ransmitter T able E-3.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-5 Rosemount 8732 Connecting Sensors of Other Manufacturers Before connecting another manufacture r ’s sensor to the Rosemount 8732 transmitter , it is necessary to perform the following functions.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-6 BROOKS SENSORS Connect coil drive and electrode cables as shown in Figure E-3. Model 5000 Sensor to Rosemount 8732 T r ansmitter Figure E-3. Wiring Diagra m for Brooks Sensor Model 5000 an d Rosemount 8732 T able E-4.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-7 Rosemount 8732 Model 7400 Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-4. Figure E-4. Wiring Diagra m for Brooks Sensor Model 7400 an d Rosemount 8732 T able E-5.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-8 ENDRESS AND HAUSER SENSORS Connect coil drive and electrode cables as shown in Figure E-5. Endress and Hauser Sensor to Rosemount 8732 T r ansmitter Figure E-5. Wiring Diagra m for Endress and Hauser Sensors and Rosemount 8732 T able E-6.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-9 Rosemount 8732 FISCHER AND PORTER SENSORS Connect coil drive and electrode cables as shown in Figure E-6. Model 10D1418 Sensor to Rosemount 8732 T r ansmitter Figure E-6. Wiring Diagra m for Fischer and Porter Sensor Model 10D1418 an d Rosemount 8732 T able E-7.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-10 Model 10D1419 Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-7. Figure E-7. Wiring Diagra m for Fischer and Porter Sensor Model 10D1419 and Rosemoun t 8732 T able E-8.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-1 1 Rosemount 8732 Model 10D1430 Sensor (Remote) to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-8. Figure E-8. Wiring Diagra m for Fischer and Porter Sensor Model 10D1430 (Remote) and Rosemount 8732 T able E-9.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-12 Model 10D1430 Sensor (Integral) to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-9. Figure E-9. Wiring Diagra m for Fischer and Porter Sensor Model 10D1430 (Int eg ra l) an d Rosemount 8732 T able E-10.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-13 Rosemount 8732 Model 10D1465 and Model 10D1475 Sensors (Integral) to 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-10. Figure E-10. Wiring Diagram for Fischer and Porter Sensor Model 10D1465 and Model 10D1475 (Integral) an d Rosemount 8732 T able E-1 1.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-14 Fischer and Porter Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-1 1. Figure E-1 1. Generic Wiring Diagram for F ischer and Porter Sensors and Rosemount 873 2 T able E-12.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-15 Rosemount 8732 FOXBORO SENSORS Connect coil drive and electrode cables as shown in Figure E-12. Series 1800 Sensor to Rosemount 8732 T r ansmitter Figure E-12. Wiring Diagram for Foxboro Series 1800 and Rosemount 8732 T able E-13.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-16 Series 1800 (V ersion 2) Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-13. Figure E-13. Wiring Diagram for Foxboro Series 1 800 (V ersion 2) and Rosemount 8732 T able E-14.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-17 Rosemount 8732 Series 2800 Sensor to 8732 T ransmitter Connect coil drive and electrode cables as shown in Figure E-14. Figure E-14. Wiring Diagram for Foxboro Series 2800 and Rosemount 8732 T able E-15.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-18 Foxboro Sensor to 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-15 . Figure E-15. Generic Wiring Diagram for F oxboro Sen sors and Rosemount 8732 T able E-16.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-19 Rosemount 8732 KENT V ERIFLUX VTC SENSOR Connect coil drive and electrode cables as shown in Figure E-16. V eriflux VTC Sen sor to 8732 T ransmitter Figure E-16. Wiring Diagram for Kent V e riflux VTC Sensor and Rosemount 8732 T able E-17.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-20 KENT SENSORS Connect coil drive and electrode cables as shown in Figure E-17. Kent Sensor to Rosemount 8732 T r ansmitter Figure E-17. Generic Wiring Diagram for Ke nt Sensors an d Rosemount 8732 T able E-18.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-21 Rosemount 8732 KROHNE SENSORS Connect coil drive and electrode cables as shown in Figure E-18. Krohne Sensor to Rosemount 8732 T r ansmitter Figure E-18. Generic Wiring Diagram for Krohne Sensor s and Rosemount 8732 T able E- 19.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-22 T AYLOR S ENSORS Connect coil drive and electrode cables as shown in Figure E-19. Series 1 100 Sensor to Rosemount 8732 T r ansmitter Figure E-19. Wiring Diagram for T aylo r Series 1 100 Sensors and Rosemount 8732 T able E-20.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-23 Rosemount 8732 T aylor Sensor to Rosemount 8732 T r ansmitter Connect coil drive and electrode cables as shown in Figure E-20. Figure E-20. Generic Wiring Diagram for T aylor Sensors and Rosemount 8732 T able E-21.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-24 Y AMATAKE HONEYWELL SENSORS Connect coil drive and electrode cables as shown in Figure E-21. Y amatake Honeywell Sensor to Rosemount 8732 T r ansmitter Figure E-21. Generic Wiring Diagram for Y amatake Honeywell Sensors and Rosemount 8732 T able E- 22.
Reference Manual 00809-0100- 4663, Rev BA January 2010 E-25 Rosemount 8732 Y OKOGAWA SENSORS Connect coil drive and electrode cables as shown in Figure E-22. Y okogawa Sensor to Rosemount 8732 T r ansmitter Figure E-22. Generic Wiring Diagram for Y okogawa Sensors and Rosemount 8732 T able E-23.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 E-26 GENERIC MANUFACTURER SENSORS Generic Manufacturer Sensor to Rosemount 8732 T r ansmitter Identify the T erminal s First check the sensor manufacture r ’s manual to identify the appropr iate terminals.
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix F Resource Block Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . p age F-1 Resource Block Errors . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 F-2 BLOCK_ALM 36 The block alarm is used for all co nfigur ation, hardware, connection failure, or system problems in the block. The cau s e of the alert is entered in the subcode field.
Reference Manual 00809-0100- 4663, Rev BA January 2010 F-3 Rosemount 8732 FREE_SP ACE 24 This p arameter re presents the percent of memory available for further configuration (zero in a preconfigured device) . FREE_TIME 25 This parameter represents the percent of t he block processing time that is free to process additional blocks.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 F-4 REST AR T 16 Allows a manual restart to be initiated. Several degrees of restart are possible: 1 Run: Nominal state when not r.
Reference Manual 00809-0100- 4663, Rev BA January 2010 F-5 Rosemount 8732 RESOURCE BLOCK ERRORS T able F-2 lists conditions reported in the BLOCK_ERR parameter . Conditions in italics are inactive for the resource block and are given here only for your reference.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 F-6 Alarm Detection A block alarm will be generated whenev er the BLOCK_ER R has an error bit set. The types of block error for the reso urce block are defined in T able F-2. A write alarm is generated whene ver the WRITE_LOCK parameter is cleared.
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix G T ransducer Block Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . p age G-2 Flow-Speci fic Block Configuration V alu es . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 G-2 PARAMETERS AND DESCRIPTIONS T able G-1 lists all of the configu rable parameters of the tr ansducer block, indicating the descriptions and ind ex numbers for each parameters. T able G-1.
Reference Manual 00809-0100- 4663, Rev BA January 2010 G-3 Rosemount 8732 FLOW-SPECIFIC BLOCK CONFIGURATION VA L U E S Once the transmitter is in stalled and communication is est ablished, configuration must be completed .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 G-4 T RANSDUCER BLOCK ERRORS The following conditions are reported in the BLOCK_ERR and XD_ERROR paramete rs. Conditions in italics are inactive for the transducer block and are given here only for your r eference.
Reference Manual 00809-0100- 4663, Rev BA January 2010 G-5 Rosemount 8732 T RANSDUCER BLOCK DIAGNOSTICS In addition to the BLOCK_ERR an d XD_ERROR parameters, more detailed information on the measu rement status can be obtain ed via DET AILED_ST A TUS.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 G-6 In Auto mode, OUT reflects the value and status quality of the output channels. T R OUBLESHOOTING Refer to T able G-6 to troubleshoot tr ansducer block problems. T able G-6. T roubleshooting Symptom Possible Causes Corrective Action Mode will not leave out of service ( OOS).
Reference Manual 00809-0100-4 663, Rev BA January 2010 Rosemount 8732 www .rosemount.com Appendix H 375 Field Communicator Operation HandHeld Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . page H-1 Connections and Hardware . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 H-2 CONNECTIONS AND HARDWARE The 375 Field Communicator exch anges information with the transmitter from the control room, the instrument site, or any wiring terminatio n point in the loop.
Reference Manual 00809-0100- 4663, Rev BA January 2010 H-3 Rosemount 8732 BASIC FEATURES The basic features of the Handh eld Communicator include Action Keys, Function Keys, and Alphanu meric and Shift Keys.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 H-4 Function Key Use the four sof tware-defined function keys, located below the LCD, to perform sof tware functions. On any given menu, the label appe aring above a function key indicates the fu nction of that key f or the curren t menu.
Reference Manual 00809-0100- 4663, Rev BA January 2010 H-5 Rosemount 8732 Main Menu The Main Men u pr ov ide s th e follo win g op tio n s: • Offline - The Of fline option provide s access to offlin e configuration dat a and simulation functions. • Online - The Online option checks for a device and if it finds one, brings up the Online Menu.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 H-6 Diagnostic Messages The following is a list of messages us ed by the Ha ndheld Communicator (HC) and their correspo ndi ng descriptions. V ariable parameters within the text of a message are indicated with <variable par ameter> .
Reference Manual 00809-0100- 4663, Rev BA January 2010 H-7 Rosemount 8732 OFF KEY DISABLED Appears when the user attempts to turn the HC off before sending modified data or before completing a method On-line device disconnected with unsent data – RETRY or OK to lose data There is unsent data for a previo usly connected device .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 H-8.
Reference Manual 00809-0100- 4663, Rev BA January 2010 Index-1 Rosemount 8732 A Action Keys Handheld Communicator .H - 3 Alphanumeric Keys Handheld Communicator .H - 4 Analog Output Range . . . . . . . . . . . . . 3-10 Zero . . . . . . . . . . . . . .
Reference Manual 00809-0100- 4663, Rev BA January 2010 Rosemount 8732 Index-2 Lower Range Value (LRV) . . 3-10 M Mechanical Considerations 2-2 , 2-6 Menu Handheld Communicator .H - 4 Messages Safety . . . . . . . . . . . . . . 1-2 Mode Transducer Block .
.
Emerson Process Management 00809-0100-4663 Rev BA, 1/10 The Emerson logo is a trade mark and se rvice mar k of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. PlantWeb is a registered trademark of one of t he Emerson Process Management group of companies.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Emerson Process Management 8732 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Emerson Process Management 8732 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Emerson Process Management 8732 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Emerson Process Management 8732 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Emerson Process Management 8732, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Emerson Process Management 8732.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Emerson Process Management 8732. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Emerson Process Management 8732 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.