P OWER A VAILABIL ITY 2U Har dwir e POD™ U SER M ANUAL Power Output Distribution 120 V olt.
.
i T ABLE OF CONTENTS I MPORT ANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . 1 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 I NTRODUCTION AN D S YSTEM D ESCRIPTION . . . . . . . . . . . . . . . 4 System Description .
FIGURES Figure 1 UPS mode of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Figure 2 Utility/main tenance bypass mode . . . . . . . . . . . . . . . . . . . 4 Figure 3 2U Hardwire POD with rack mounting brackets . . . . . . . 5 Figure 4 Attaching POD securing brackets to rear of UPS .
1 I MPORT ANT S AFETY I NSTRUCTIONS SA VE THESE INSTRUCTIONS This manual contains importa nt instructions that should be followed during ins tallation and ope ration of the 2U Hardwire POD™. This product is designed for commercial / industrial use only, with Liebert UPS systems.
2 ! CAUTION This device receives power fr om multiple sources. Before servicing this device, remove all connections and cut power from the utility branch input. Bef ore servicing the UPS, follow “Mainte nance of UPS” instructions in the u ser manual for your UP S.
3 G LOSSARY OF S YMBOLS Equipment grounding conductor Bonded to ground Electric phase Indicates AC input Indicates AC output.
4 I NTRODUCTION AND S YSTEM D ESCRIPTION Congratulations on your choice of the Liebert 2U Hardwire POD™ . The 2U Hardwire POD provides maintenance bypass capab ility as well as power output distribution . The Liebert 2U Hardwire POD can be used on UPS in the rack mount or tower configuration.
5 R ACK M OUNT I NST ALLATION 1. Rack mount installation of the 2U POD is poss ible with the use of the rack mounting brackets (shipped with the POD). See Figure 3 .
6 I NST ALLATION ON GXT 2U UPS 1. Unpack the 2U POD careful ly, no ting the packing method. Retain the box and packing mat erial for possible future sh ipments. 2. Visually inspect the 2U POD for freight damage. Report damag e to the carrier and your local de aler or Liebert representative.
7 H ARDWIRE C ONNECTIONS Electrical Inst allati on Considerations The front and bottom of the POD provide alternate conduit entry points for both the UTILITY and LOAD connections. Figure 5 Conduit entry ! CAUTION This UPS must be installed by compet ent electrical personnel and wired in accordance with local/national electrical codes.
8 Wiring access doors on each end of the POD allow access to the wiring compartments by opening the top an d rear of the POD. Each access door is retained using two Phillips head screws.
9 Wiring Instructions 1. Remove the wiring access doors by removing the two Phillips head screws that secure them. 2. Determine which of the two avail able conduit entry points are to be used. Knock out the conduit entr y hole for the loca tion and size of conduit to be used.
10 A PPLY F EED P OWER 1. Next attach the POD to the secu ring brackets (see Fig ure 7). The POD can be installed to face one of three different directions utiliz- ing the same mounting procedures . Select the direction of mount- ing to accommodate the co nduit entry connections.
11 S TA RT E QUIPMENT 1. Turn on all loads hardwired to the output of the POD. The 2U POD now powers your eq uipm ent in the UTILITY mode. 2. Turn ON the loads and ensure al l are up and operating properly. 3. Start the UPS according to its specific user manual.
12 I NDICATOR L AMPS Utility This amber lamp i s illuminated when utility power is present. It sig- nals that you may tr ansfer the lo ads to maintenance bypass (UTILITY mode) operation via the rotary switch.
13 O PERATION T ransfer to Maintenance Bypass To transfer to maintenance bypass (UTILITY) from UPS, follow the following s teps: 1. Ensure the Utility lamp (amber la mp) is illuminated. If the lamp is not illumina ted, refer to the Troubleshooting section.
14 T ROUBLESHOOTING Problem Cause Solution UTILITY lamp (amber) not illuminated. UTILITY not present. Call qualified service personnel to restore power . Utility Branch Circuit Breaker may be open. V erify that the branch circuit breaker is closed. 2U Hardwire POD input power not connected to UTILITY .
15 S PECIFICATIONS This POD is intended for use with a UPS meeting all of the following requirements: • UPS input cord is compatible with the rating and ty pe of receptacle on the POD labeled “CONNECT UPS LINE CORD HERE.” • UPS output receptacle is compat ible with the POD input power con- nector labeled “UPS.
16.
.
T echnical Support / Service Web S ite www .liebert.com Monitoring 800-222-5877 monitoring@liebert.com Outside t he US: 614-841-6 755 Single-Phase UPS 800-222-5877 upstech@liebe rt.com Outside t he US: 614-841-6 755 Three-Phase UPS 800-543-2378 powertech@liebert.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Emerson MP2-115HW è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Emerson MP2-115HW - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Emerson MP2-115HW imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Emerson MP2-115HW ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Emerson MP2-115HW, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Emerson MP2-115HW.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Emerson MP2-115HW. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Emerson MP2-115HW insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.