RTU-EN01 Modbus TCP Remote I/O Communication Module Operation Manual DVP-0213920-01.
.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 1 Intr oduction 3 This operation manu al only provides introductory inform ation on electrical specification, inst allation and wiring.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 2 6 SETTING UP SOFTW ARE ................................................................................................... 16 6.1 Setting up Communications & Searching for Communication Modules in DCISoft .
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 3 1 Introduction T o ensure correct installation and operation of R TU-EN01, please read this manual carefully before u sing your RTU-EN01. R TU-EN01is an Ethernet remote I/O module for remote setting thro ugh Delta’ s DCISoft.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 4 Environment Noise immunity ESD (IEC 61 131-2, IEC 61000-4-2): 8KV Air Discharge EFT (IEC 61 131-2, IEC 61000-4-4): Po wer Line:±2KV , Digital Inpu t: ±2KV , Communication I/O: ±2KV RS (IEC 61 131-2, IEC 61000-4-3): 80MHz ~ 100M Hz, 10V/m.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 5 2.2 Product Profile 1. POWER indicator 12. RS-485 communication port 2. RUN indicator 13. Extension module positioning hole 3. BA T .LOW indicator 14. Nameplate 4. RUN/ST OP switch 15.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 6 2.4 RUN/STOP Switch Status Explanation 1. RUN indicator on RTU-EN01 is ON. 2. Analog input/output module is in RUN status. RUN 3. Smart PLC function is running. 1. Analog input/output module switches from RUN to STOP status.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 7 D V P - 1 6 S P D V P - 0 2 D A D V P - 1 6 S P D V P - 0 2 D A PO WER RUN BA T .L OW RUN ST OP R T U - E N 0 1 LA N R S - 2 3 2 R S - 4 8 5 3.2 Installing R TU-EN01 and DVP Slim Series Digit al Input/Output Module onto DIN Rail z Use standard 35mm DIN rail.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 8 DVP28SV RUN STOP D V P - 0 2 D A D V P - 0 8 S T D V P - 1 6 S P D V P - 0 4 A D D V P - 0 4 T C D V P - 0 4 P T Eth ern et RTU- EN0 1 D I/D O AI/A O DVP2 8S V COM2 PC DV PEN0 1-S L 4 Word Devices & Bit Devices in RTU-EN01 4.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 9 BR# Attribute Content Explanation Default Latched 24 R ID of the 1st analog I/O module ID of the 1st analog I/O module.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 10 BR#5: COM2 Communica tion Settings Explanations: b0 ~ b3 Interface Explanation Data Baud rate (bps) Data Baud rate (b.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 11 Code Indication How to correct F0 Returning to default setting -- F1 RTU-EN01 being powered -- F2 Power supply in lo w voltage Check if the power supply of the module works normally .
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 12 BR#50 ~ BR#57: RTC Sett ings Explanations: For setting up the real-time clock (R TC). When BR#9 = 1, R TU-EN01 will stop to update the R TC values to BR#10 ~ #16. Once the setup is comple ted, RTU-EN01 will set BR#9 to 0.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 13 RCR# Attribute Content Explanation Default Latched 200 ~ 249 R/W T he 5 th analog I/O module Control register for the.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 14 T#1 ~ #15: T imer 1 ~ 15 Explanations: Please refer to T#0. 4.7 Word Devices & Bit Devices for Cou nters (C) C# A.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 15 R# Attribute Content Explanatio n Default Latched 6 R/W RTC 6 Real-time clock OFF NO 7 R/W RTC 7 Real-time clock OFF .
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 16 5.3 Device T ype & Device Address Discrete input Device type Modbus address (Hex) 6-digit Modbus addre ss (Dec) N.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 17 2. Y ou will see the communication module found..
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 18 3. Double-click on the module to be set up to enter the se tup page. The first page overviews the basi c status of the module and information on the right -side module.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 19 IP list: In the list, you will see the network IPs already us ed. Click “Add” to record the known IP address into the list and next search for the module on the network by desig nated IP .
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 20 1. Module name: There can be many R TU-EN01 modules on the network. Thus, you can set up a module name for each module to identify the module when you need to use them.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 21 the communication. The IP of the gateway ha s to be in the same subnet as RTU-EN01. The default gateway of RTU-EN01 is 192.168.1.1. 3. T imer setting: For setting up TCP connection idle time, Modbus time-out and minimum delay time for every communication dat a.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 22 4. Enter “192.168.0.2” into IP address. Click “OK” to complete the IP address setting of the PC. 6.5 Setting up T ime Server RTU-EN01 of fers real-time clock (R TC) functions.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 23 1. Enable time server: RTU-EN01 e xecute automatic time correction f rom the NTP server on the network every 6 hours to ensure the time is correct in the R TC.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 24 Check the box to enable IP filter . 2. Begin IP address: S t art IP addresses allowed to establish connection. Max. 8 IPs are allowed. 3. End IP addre ss: End IP addre sses allowed to establish connection.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 25 Y ou can move the IF-THEN setting upwards or d ownwards to change the execution order of them. 6.8 Smart PLC Setting: T imer RTU-EN01 has the indepe ndent Smart PLC function.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 26 1. Enable: Decide whether to enable the co unter in this column. 2. Count up/count down: Decide whether the counter will be count ing up or counting down. 3. Up bound/low bound: The upper bound and lowe r bound of the counting.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 27 1. Enable: Decide whether to trigger the R TC in this column. 2. Cyclic: Decide to trigger the R TC only once, or trigge r it on a daily , weekly or monthly basis.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 28 1. Corresponding table: Open DCISof t and it will automatically load in t he control register information on the analog I/O modules. (When using We b settings, you have to load in the EDS file for analog I/O module by yourself.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 29 6.12 I/O Monitoring T able RTU-EN01 is able to monitor internal registers on -line. Sc roll the table to monitor bit devices RX, R Y , T , C, R, RCR and BR and the bit st atus and present value in the register .
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 30 T#0 ~ T#15, tot al 16 bits a nd 16 registers. C#0 ~ C#15, tot al 16 bits and 16 registers. R#0 ~ R#15, tot al 16 bits and 16 registers. RCR#0 ~ RCR#399, tot al 400 registers.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 31 Parity Data length S top bit s S t ation address: The Modbus address. 2. Bit device For setting up the addresses for the bit type se rial slave device and reading o r the content in the designated slave.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 32 3. Word device For setting up the addre sses for the word type seri al slave device and reading or the content in the designated slave. S t ation address: Enter the address of slave to be monitored.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 33 6.14 Virtual COM The virtual COM converts the dat a sent to RS-232 port into Ethernet. Select Virtual COM for COM2 mode (RS-485). The default setting for listen port is 20001.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 34 Press “Search”, and you will see all t he connected devices on the network Select the device and click “OK”. Information on the device will be loaded in automatically .
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 35 6.15 Security Setting T o prevent the set values in RTU-EN01 from being modi fied, you can set up passwords to lock the setting s in RTU-EN01. Setting up password 1.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 36 However , if you set up RTU-EN01 by RS-232, you can return the setting to default one whether the password is l ocked or not.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 37 D V P - 0 2 D A D V P - 0 8 S T D V P - 1 6 S P D V P - 0 4 A D D V P - 0 4 T C D V P - 0 4 P T Ether net RT U- EN01 DI/ DO AI/A O CO M 2 R T U - E N 0 1 P C 2. Open Internet Explorer and enter IP address “19 2.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 38 3. To use the page of analog input/output module s on the web, download “DeltaR-Side-S_ENU.eds” file from Delta’s website first and im port the file to the page. Ot her settings are the same as the settings in DCISoft.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 39 2. Select “Connections” and Click “LA N Settings…". 3. Uncheck “Proxy server” options and click "OK”.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 40 Set up exceptions: 1. Click “Advanced…” on Local Ar ea Network (LAN) Set tings page. 2. Enter the IP address “192.168.1. 5” of RTU-EN01 in Exceptions. 3. Click “OK”.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 41 2. In “General” page, clic k “Delete Files… ” in Temporary Internet files column. 3. Check “Delete all offline co ntent” and click "OK” to start the deletion.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 42 7 Application Examples – DCISof t 7.15 Smart PLC: IF-THEN Application Setting up IF-THEN in Smar t PLC functions by using DCISoft. Steps 1. When RX#0 and RX#1 are ON, set RY0 to output.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 43 7.16 Smart PLC: Timer Application Setting up Smart PLC functions by DCISoft. After RY0 is On for 1 second, it will turn Off for 500 ms. This will repeat in cycle. Steps (1) Set up the timer: Timer 0 1s, Timer 1 500ms.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 44 7.17 Smart PLC: Counter Application Setting up the counter by DCISoft. On ce RX#1 counts for 5 times, RY0 will output. Steps (1) Set up counter C0: RX#1 counts up 5 times and re aches the target.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 45 7.18 Smart PLC: R TC Application Setting up Smart PLC function by DCISo ft. RY0 turns On at 08:00 and Off at 09:00 every day. Steps (1) Set up the RTC to be On at 08:00 ever y day and continue to be On for 1 hour.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 46 3. Switch to “IF-THEN” page. Check the “Enable ” box and select “RT0 On” in the IF column and “RY 0 Set” in the THEN column. Press “Add” to add t he settings to the table below.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 47 The default setting for listen port is 20001. Open the setup page for V irtual COM. Press “Search” and you will see all the connected devices on the network.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 48 Select the device and click “OK”. Information on the device will be loaded in automatically . Press “OK” to complete the setup. Once the setup is completed, you will then be able to see the virtual COM just set in “Compute r Management”.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 49 Set up communication format Use the Virtu al COM (COM2) previously set for the setting of “Com Port”. Next, enter the communication format (38400, 7, E, 1) for VFD-E.
Modbus TCP Remote I/O Co mmunication Module R TU-EN 01 DVP-PLC Operation Manual 50.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Delta Electronics RTU-EN01 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Delta Electronics RTU-EN01 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Delta Electronics RTU-EN01 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Delta Electronics RTU-EN01 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Delta Electronics RTU-EN01, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Delta Electronics RTU-EN01.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Delta Electronics RTU-EN01. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Delta Electronics RTU-EN01 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.