Manuale d’uso / di manutenzione del prodotto DVPEN01-SL del fabbricante Delta Electronics
Vai alla pagina of 54
DVPEN01-SL Ethernet Communication Module Application Manual.
.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 1 Warning 3 Please r ead this instruction car efully befor e use and follow th is instruction to operate the device in or der to pr event damages on the device or injuries to staff. 3 Switch off the power befor e wiring.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 2 5.6 IP Filter ..................................................................................................................................... 23 5.7 S tatic ARP T able .......
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 3 1 Introduction Thank you for choosing DVPEN01-SL module. T o correctly inst all a nd operate DVPEN01-SL, please read the manual carefully before using the module. DVPEN01-SL is an Ethernet communication module for remote setting and communication through WPLSoft.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 4 Item S pecification Vibration/ Shock Resistance S tandard: IEC61 13 1-2, IEC 68 -2-6 (TEST Fc)/IEC61 131-2 & IEC 68-2-27 (TEST Ea) Electrical specifications Item S pecification Power supply voltage 24VDC (-15% ~ 20%) (Power is supplied by the internal bus of MPU.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 5 2.3 LED Indicators Indicator Color Indication POWER Green Power indication RS-232 Red Communication st atus of the series port 100M Orange Network connection st atus LINK Green Network communication speed 2.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 6 Connect DVPEN01-SL to the Network Connect DVPEN01-SL to t he Ethernet Hub by twisted pair cable CA T -5e. DVPEN01-SL has Auto MDI/MDIX function; therefore, DVPEN01-SL do es not need to use a crossing cabl e between the PC and DVPEN01-SL.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 7 CR# HW LW Attribute Content Explanation #7 R S tatus of E-Mail 1, 2 b0 ~ b7: Current status of E-Mail 2 b8 ~ b15: Current st atus .
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 8 CR# HW LW Attribute Content Explanation #1 19 R/W Modbus TCP data length Setting up the data length for Modb us TCP transaction #2.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 9 CR value E-Mail status 10 Fail to c onnect to SMTP-Server 1 1 Incorrect recipient E-Mail addre ss 12 SMTP-Server communication error 13 Exceeding the max.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 10 S toring the data to be transmitted to the remote MPU. CR#49 ~ 68: Data Receiving Buf fer Explanations: S toring the data received f rom the remote MPU.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 11 CR#70, 71: IP Address Explanations: 1. Setting up the IP address of our equipment in hex. When in DHCP mode, you can only read and cannot write. 2. Example: Assume you’d like to set the IP address as 192.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 12 CR#1 16: Modbus TCP S tatus Explanations: Displaying the current communication st atus of Modbus TCP mode .
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 13 registers (CR) in the extension module. Numbering of the module s: Every extension module conne cted to PLC MPU has a No. to allow you to kno w which module is which when compili ng the PLC program.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 14 2. Auto-search • Press “Auto-Search” (circl ed) to search for every DVPEN01-SL in the netwo rk and display them in the left column. • Move the cursor to the module you would like to set up.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 15 3. Searching by IP address • Set the transmission type as “Ethernet” first. Next c lick on the “Stat ic IP Search” icon (circled) to search for the designated IP. • Press the “search” icon and you will ope n the window for entering the IP address.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 16 4. Opening DVPE N01-SL setup page by RS-232` • Select “RS232" as the transmission type in co mmunication setting. You will have to designate a communication port. When DVPEN01-S L is s earched by RS-232, you do not need to set up the parameters (i.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 17 • Module Name: There can be many DVPEN 01-SL modules in the network. Thus , you can set up a module name for each module to identify the module when you need to use them .
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 18 sections), bordered by meri dians each 15° of longitude ap art. The local time in neighboring zones is then exactly one hour dif ferent.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 19 • Enter 192.168.0.1 into IP address. Click on “OK” to complete the IP address setting of the PC. 2. Setting up DVPEN01-SL Network • IP configuration: There are two types of IP, static IP and DHCP.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 20 IP Explanation Static The user e nters the IP ad dress, subnet mask and gateway . DHCP DHCP server offers the IP address, subnet mask and gateway. • IP address: IP address is the location of the equipment in the network.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 21 1. SMTP Server: The E-Mail will first be sent to SMTP server , and SMTP server will send it to the designated address. For example, assume there is an E-Mail to be sent to test@delt a.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 22 5. Select recipient s: After you have set up all the parameters for the E-Mail, you will need to select recipients. The E-Mail will be sent to the desig nated recipient s w hen the E-M ail is triggered.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 23 1. Enable Data Exchange: Check the box to enable or disable dat a exchange. S tart data ex change afte r enable it. 2. Communi cation Address & Data exchange host IP: Y ou have to enter the IP address of DVPEN01-SL at the other end.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 24 1. Enable IP Filter Function: Check the box to enable IP filter . 2. IP: IP addre sses that are allowed to esta blish connections. Maximum 8 IPs are allowed. 3. Netmask: The subnet of the IP is allowed to establish a connection.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 25 1. IP: Destination IP address in data transmission. 2. MAC: The MAC address corre sponding to the IP address. Note: Incorrect settings may result in connection failu re. Therefore, DO NOT set the M AC address of the equipment without the network into t he table.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 26 1. Modify: Check the box to modify the passwo rd. 2. New Password: Maximum 4 characters are allowed. Lea ve the column “blank” to disable the p assword protection function. 3. Confirm Password: Enter the new password a gain.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 27 Check “Default Setting” box and click o n “Y es”. Note: If you set up DVPEN01-SL by RS-2 32, you can return the setting to default setting whether the password is l ocked or not.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 28 1. Export: Save all the settings of DVPEN01-SL into *.eni files. The exported files do n ot include the pass word . 2. Import: Select a file and the file will be imported to all the settings.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 29 Input IP Address: Press “Add” to record the IP address of the module into the list. 6 Application Examples 6.1 Setting up IP and Communicating through WPLSoft Application Setting up network parame ters of DVPEN01-SL directly on the PC.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 30 4. Click on “Auto-Search” icon to search for all DVPEN01-SL modules in the network.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 31 6. Open “Basic” setup page. 7. Switch to “Network” setup page.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 32 8. Enter IP address: 192.168.0.4; Netmask: 255.255.255.0; Gateway: 192.16 8.0.1. Press “OK” to complete the setup, and WPLSoft will automatically search for DVPEN01-SL. 9. The IP of DVPEN01-SL ha s been modified into the new setting (DELTA DVPEN01-SL: 192.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 33 PC Hu b DH C P Ser v e r PC DV P-PLC DV PEN 0 1 2. Open “Communication Setting” in WPLSoft.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 34 4. Click on “Auto-Search” icon to search for a ll DVPEN01-SL modules in the network. Follow “View Æ Workspace Æ Communication” or “View Æ Workspace Æ Proje ct” to find the detected DVPEN01-SL module (default module name: DELT A DVPEN01-SL, IP: 192.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 35 6. Open the setup pag e. You can modify the module name for easier identificatio n. 7. Next, set up the new IP of DVPEN01-SL. First sw itch to “Network” setup page. If there is a DHCP server in the LAN, select DHCP in “IP Configuration”.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 36 6.3 Setting up IP and Communicating through WPLSoft Application Setting up network parame ters of DVPEN01-SL by ladder diag ram Network requirement (1) IP of DVPEN01-SL: 192.168.0.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 37 • Use T O instruction to write the network se tting parameters D0 ~ D7 into CR#69 ~ #75 in DVPEN01-SL. DVPEN01-SL is the first extension module numbered K100 attached at the left hand side of PLC.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 38 4. Open the setup page agai n, and DVPEN01-SL is now lo cked by the passwo rd. You cannot open any of the settings now. Click on “Unlock” to leave the entering password window.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 39 6. To clear the password, sim ply leave the passw ord columns blank. Click on “OK” to clear the password.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 40 2. Check the “Default Setting” box an d the “Warni ng” dialog box will a ppear. Click o n “Yes” to return to default setting (in approx. 5 ~ 10 seconds), and the password will be cleared as well.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 41 3. Check “Enable IP Filter Function” box. Enter “1 92.168.0.7” in No. 1 IP and “255.255.255.2 55” in all “Netmask” columns. 4. Enter “192.168.0.1” in No. 2 IP and “255.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 42 6.7 Setting up S tatic ARP T able Application Setting up st atic ARP table Network requirement (1) MAC address of equipment 192.168.1.6 is 00:18:23:10:00:35 (2) MAC address of equipment 192.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 43 Note: The MAC address of D VPEN01-SL can be obtained from WPLS oft or the MAC address sticker on the equipment. The MAC address of PC can b e found in the “Network Conn ection Details” (see below).
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 44 3. In “Subject and Mail” page, enter the ad dress of SMTP server, subject of E-Mail, a nd E-mail address of the recipient. 4. Switch to “Select Recipients” page. Ch eck all the boxes of “Recipient 1”.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 45 5. After all the settings in DVPEN01-SL are comp leted, compile the ladder diag ram in the MPU and download it to the MPU.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 46 3. Check “Enabl e Data Exchange” box. Enter IP address of PLC_A “192.168.0.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 47 • Write the dat a in RTC into CR#29 ~ CR#35. • Write “1” into CR#13 to st art the data exchange. • CR#14 = 2 refers to successful ex change. CR#14 = 3 refers to failed excha nge.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 48 Explanations: • The data exchang e will be executed every one secon d . • Write “0” into CR#28, and PLC_B will u se CR# 25 ~ CR#26 as the IP address of the destination PLC.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 49 END SET M2 M1 RS T K100 K1 M2 K14 D1 4 RS T M2 RS T M2 = D 1 4 K 2 = D 1 4 K 3 FRO M K100 K1 TOP K100 TO P K1 K 1 K0 K14 K13 K100 TO P K1 K86 H1 064 Explanations: • The data exchang e will be executed every one secon d .
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 50 M101 3 K100 K1 K100 K100 K1 M2 M1 M1 SET M1 TOP TOP TOP K100 TOP K1 K100 K1 TOP K100 TOP K1 K1 K0 H4 HC0A 8 K1 H0 K100 K100 K1 TO.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 51 • Write the length of the instrcutio n into CR#1 19. • Write “1” into CR#1 15 to start the ex ecution of Modbu s TCP instrcution. • CR#1 16 = 2 refers to successf ul execution.
Ethernet Communication Module DVPEN01-SL DVP-PLC Application Manual 52 MEMO.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Delta Electronics DVPEN01-SL è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Delta Electronics DVPEN01-SL - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Delta Electronics DVPEN01-SL imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Delta Electronics DVPEN01-SL ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Delta Electronics DVPEN01-SL, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Delta Electronics DVPEN01-SL.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Delta Electronics DVPEN01-SL. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Delta Electronics DVPEN01-SL insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.