1 OPERA TING INSTRUCTIONS UPS PROTECT B. PROTECT B. 750 PROTECT B. 1000 PROTECT B. 1500 PROTECT B. 2000 PROTECT B. 3000.
2 Thank you for purchasing a PROTECT B. UPS from A EG Pow er Solutions. The followin g security advices ar e an important component of the manual and w ill pr event any operation errors and protect y ou against possible dangers. Read the manual thoroug hly before y ou first use the appliance.
3 1 Notes on these O perating Instructions Duty to Provide Information These operating instructions will help y ou to install and operate the U ninterruptible Power Supply (UPS), PROTECT B. 750, PROTECT B. 1000, PROTECT B. 1500, PROTECT B. 2000 or PROTECT B.
4 Claims in connection with s upplied goods m ust be submitted within eight days of receipt, along with the packing s lip. Subsequent claims cannot be considered. The warranty does not apply for dam age caused by non- com pliance with these instructions (su ch da m ag e als o in clud es da m ag ing th e warranty seal).
5 Table of Contents 1 Notes on these Operating Instructions ............................. 3 2 Sy stem Description ..................... ..................................... 7 2.1 Overview .............. ...............................................
6 5.6 Interfaces and com m unication ................................ 39 5.6.1 Data line protection RJ 11 and RJ45 (modem / telephone / fax / network) ................. 39 5.6.2 Computer interfac es RS232 and USB ............. 40 5.6.3 Comm unication slot (PROTECT B.
7 2 Sy stem Description i P ROT EC T B. i s a n Un i nt er ru pt ib le Po we r S up pl y (U PS ) for e sse nt ia l l oa ds s uch a s PC s, w or kst at io ns , se rv er s, n et wo rk co mp on en ts , te l ec ommu ni ca ti on eq ui pme nt a n d si mil ar d ev i ce s.
8 ♦ Micro processor control for high ava ilability , suited for generator mode ♦ Easy extension of battery capacity using external batteries (starting with B.
9 stabiliz es the l oad voltage. As a result, voltage fluctuations in the public utility 's mains are reduced to a level which is acceptable f or the loads. T his is perf ormed without recourse to the internal energy storage, something which in turn has a positive effect on battery availabili ty.
10 3 Safety 3.1 General S afety Instructions Read these operating instructions car efully prior to com miss ioning of the PROTECT B. UPS and observe t he safety in s tructions! Only use the unit if it.
11 The output m ay be live, even if the UPS is not connected to the mains supply , as the UPS has its own inte rnal power supply (battery)! For health and saf ety reasons, the unit m ust be earthed correctly ! PROTECT B.
12 ♦ Never connect the mains input to the UPS output. ♦ Ensure that no fluids or foreign bodies c an pen etrate the UPS! ♦ Do not block the air vents of the unit! Keep children away from the uni.
13 Danger! Ex plo sive! Never throw batteries into open f ire. Never open or d am age batte ries. (Electroly te may le ak out and damage sk in and ey es.
14 3.3 Certification.
15 3.4 Technical Da ta Mod el power PROTECT B. 750 750 VA / 500 W PROTECT B. 1000 1000 VA / 700 W PROTECT B. 1500 1500 VA / 105 0 W PROTECT B. 2000 2000 VA / 134 0 W PROTECT B.
16 Output current power (at 230 Vac) PROTECT B. 750 3. 2 A PROTECT B. 1000 4. 3 A PROTECT B. 1500 6. 5 A PROTECT B. 2000 8. 7 A PROTECT B. 3000 13 A Transf er time at m ains outage 2- 4 m s (ty pical), 6 ms m ax. 13 ms m ax. in generator operatio n Voltage w aveform s inusoidal Outlets Non-heating appl iance con nect ors acc.
17 Recharge time 3 h (UPS in (to 90 % of rated capacity ) standard configuration) 7 h (UPS wi th 1 add. battery pack) 12 h (UPS wi th 2 add. battery pack s) 18 h (UPS wi th 3 add. ba ttery pack s) 24 h (UPS wi th 4 add. battery pack s) Type Sealed, maintenance free, hot swappabl e (f rom B.
18 Number of outlets PROTECT B. 750 4 x IEC 320 PROTECT B. 1000 6 x IEC 320 PROTECT B. 1500 6 x IEC 320 (sep. module) PROTECT B. 2000 6 x IEC 320 (sep. module) PROTECT B. 3000 8 x IEC 320-10 A 1 x IEC 320-16 A Equipment colour Black line Siz e W x H x D (m m ) Standard model (Size in horizontal / l ying v iew) PROTECT B.
19 Guidelines The PROT ECT B. com plies with the product norm EN 50091. The CE symbol on the unit c ertifies the compliance to the EG guideline s for 73/23 EEC low voltage and for 89/336 EEC electromagnetic com patibility (EMC), when follow ing the installation instruc tions in the manual.
20 4 Set-Up and Operatio n 4.1 Unpacking and Inspe ction The unit has been fully tested and inspected. Altho ugh the unit has been packed and s hipped with the us ual degree of c are, damage during transport cannot be ruled out completely .
21 Please k eep the plastic packaging bags away from babies and children in order to safeguard against suffocation accidents. Handle the c omponents with care. Please tak e into account their weights. It m ay be necessary to engage the help of a sec ond person, particularly in the case of the PROTECT B.
22 4.3 Connections, Operation / Display Elements 4.3.1 Front view : Model designation wit h type rating details PROTECT B. 750 and B. 1000 Model designation with type rating detail s PROTECT B. 1500 and B. 2000 (Battery module and UPS) Model designation with type rating details PROTECT B.
23 4.3.2 Operating panel Explanations (see also chapter 6) 1. Main switch of the UPS ( mains switch) 2. Pushbutton for sy stem test (m anually triggering) or switching off the buz zer 3. Pushbutton t o view the configuration 4. Enter butto n 5. LED for operating mode (details on page 42) 6.
24 4.3.3 Rear view (conn ections): Comments: 1. Mains connection (UPS inp ut) with electric fuse and integrated spare fuse 2. Load connections (UPS outputs) 3. Surge protection (RJ11/RJ45) for data interface for phone, fax, m odem or network (10/100MBit/s) 4.
25 Comments : 1. Mains connection (UPS inp ut) 2. Load connections (UPS outputs) PROTECT B. 3000 wi th additional load c onnection (IEC 320-16A) 3. Surge protection (R J11/RJ45) for data interface for phone, fax, m odem or network (10/100MBit/s) 4. Comm unication interface RS232 (9pin SUB-D socket) 5.
26 5 Commissioning 5.1 Deploy me nt The UPS was cons tructed for both horizonta l / flat (rack /19") operation and v ertical / standing (tower) operation. Operation the unit for longer time abov e an ambient tem perature of 25° C reduces the lifetim e of the batteries.
27 W hen operating the s y stem with more than one battery module, the UP S can be p os itioned between the m odules. The following graphic displa ys the possibiliti es: PROTECT B. 1500 / 2000 standing and lying (standard version) PROTECT B. 3000 can be operated in the standing and ly ing position as w ell.
28 5.1.2 19" Rack Mount Setup ROTECT B. 750, 1000, 1500, 2000 and 3000 can be installed in 19” rack s. The UPS and external battery enclosure need 2U of valuable rack s pace. Mount the UPS preferable in the lower third of the rack with respect to the m ass centre and suf ficient ventilati on.
29 4. Add up the fr ont panels f or both sides. The mec hanical install ation of the UPS is completed now. PROTECT B. 1500 und B. 2000 This model is designed such that the UPS and the battery module can be m ounted beside ea c h other into the r ack.
30 1. Place the UPS on a f lat and in a clean place that the front side of the UPS is facing to y ou. 2. Loosen the s crews in the middle of the cover and remove the covers f rom both units. 3. Fix the (wide) mounting brack et to the open front. Rack mounting holes stand out on each side of the units.
31 6 . A l ig n th e s eco n d ( sma ll er ) mo un ti n g br ack et a t the r ea r o f b ot h u ni ts a nd mo un t th e m w it h t he e nc lo se d scr ew s . 7. Ins tall Plug of the battery module with the socket at the rear panel of the USP. F ix the output m odule to the notch of the battery m odule.
32 PROTECT B. 3000 / B. 3000 BP For m ounting the 3000 VA UPS in a 19” rack fix the m ounting ears to the UPS and install the unit to the rails. Do the sam e for the optional battery module. 5.2 A dditional battery installation setup PROTECT B. 1500, 2000 und 3000 include external battery ports that allow connecting additional battery m odules.
33 PROTECT B. 3000 Connect the supplied battery module cable from extended battery m odule to the external battery port of the rear of UPS. If continuing to add up extended battery module, repeat above steps. 5.3 Emergency Power Off (EPO) set up PROTECT B.
34 7. A c t iv a te t h e e x te r n a l EP O s wi t c h t o t e s t t h e EP O f u n c ti o n 8. De-activate the external EPO s witch and restart the UPS. 5.4 Electric s tart-up First compare the s etting with the rated voltage valid in y our country .
35 o pe ra ti ng st ag h as be en re a che d (p os . 7 p. 3) . In case any thing different occurs, please follow the i ns tructions in Chapters 6. 2 / 6.3 . i Please s hut down the entire sy s tem if you cannot solve any problems which occ ur. Please contact our hotline (see page 4 ).
36 6. After selecting the mode, press the confirm ation button more than three seconds to com plete the configuation. 5.5 Operation Once y ou have connected the UPS to a suitable m ains connection, y ou c an start operation using the UPS m ain switch.
37 If the UPS does not automatically r eturn to norm al operation after a f ew m inutes, close all jobs as usual and switch off y our loads (e.g. PC) before the battery is fully discharged. This lengthens the service life of the battery ! Switch OFF the UPS by press ing the main switch .
38 Also avoid short-ter m unit overloads, which m ay, f or exam ple, occur when connecting a laser printer or laser fax m achine. Do not connect any household applian c es to the UPS. Never connect any additional loads to the UPS if there is a mains failure, i.
39 Executing the Test: ♦ To execute the m anual check press the button for about five seconds until the UPS acoustic signal f ades out. ♦ Additiona lly the button has the f unction to deactivate the acoustic alarm signal. Press the button when the acoustic alarm it audi ble for about 1 second.
40 5.6.2 Computer interfaces RS232 and USB The UPS off ers various interfaces to m anage the s y stem and to com fortable readout state inform ation and important parameters. T he pr otocol is optim ize d for operation with the shutdown and U PS m anagement software “ CompuW atch” from AEG.
41 In com bination with the intelligent UPS the software ensures high avai lability of all IT c omponents and full data integrity . The shutdown software “CompuW atch” supports m ost popular operating sy s tems like W indows 98/ME, W indow s NT/2000/ XP, Linux, Novell Netware, IBM AIX, HP-UX , SUN Solaris, Mac OS X, .
42 6 Signalling and failure solu tion 6.1 LED display 1. Main sw itch of the UPS (m ains switch) 2. Push button for m anually triggering the system tes t or switching off the buzz er 3. Push button to view the configuration 4. Acknowledgement button 5.
43 is providing battery power to y our equipment. On the other hand, the LED indicator gives you a w arning which will flash every two seconds wh en the battery is low. 9. LED: Bar c hart LEDs s howin g UPS utiliz ation. The LED indicator and the load level indi c ator wil l illuminate to show the load level; linearly subdivided in 25% steps.
44 6.2 A udible Alarm Trouble Shooting: Problem Cause Solution Sounding every 4 seconds The UPS is on battery Check the input voltage, the input fuse resp.
45 Output fuse it released Check the output fuse (B. 3000) UPS could not provide pow er to the load UPS output recognizes overlo ad or short circuit Check the connected cable Ensure the load does not exceed the maximum rating of UPS Battery is not charged Re -c harge the battery at least 24 hours Battery has reduced backup time .
46 7 Maintenance Th e PR OTE C T B . co ns is ts o f a dv an ce d a nd re si st an t co mpo n en ts . To g ua ra nt ee a co nt in uo us an d hi gh av ai la b il it y i t i s re co mmen d ed to che ck th e un it (e sp ec ia ll y th e ba tt er ie s an d th e fa ns ) in r eg ul ar i n te rv al s (a t le as t ev e ry 6 mon th s) .
47 Fan control The fan has to be c hecked on a r egular basis for dus t intrusion an d strange unty pical sounds. Cl ogged ventila tion has to be c leaned.
48 PROTECT B. 750 and B.1000 1. Unscrew the two screws on the side and rem ove the front panel carefully on both ends. Mak e sure that the panel does not ti lt too m uch. 2. Disconnect the battery cable f rom the UPS and r emove the battery retaini ng battery bracket to the right so that the battery can be pulled out to the f ront.
49 5. Close and reinstall the front panel . T ake care to push it in f irm ly and fix the front panel with the two sc rews f rom the beginni ng. PROTECT B. 1500 und B. 2000 1. Unscrew the two screws from the battery case and remove f ront panel by pullin g on both ends.
50 3. W ithdraw the new batteries fr om the transport container and put into the right position. Fix both blocks together and connect the electric connections of the extracted battery system. 4. Slide the new battery carefully into shaft of the UPS until th e end.
51 3. Pull first the right battery out and then the left one. 4. W ithdraw the new batteries fr om the transport container and put into the right position. Fix both blocks together and connect the electric c onnections with the j unction line of the extracted battery sy s tem.
52 8 Sto rage, Dismantling and Disposal Storage Long storage tim es without charging or discharging the battery at regular intervals m ay lead to permanent damage of the battery. If the battery is stored at room tem perature (20 0 C to 30 0 C) it will automatically di s charge at a rate of 3-6 % per month due to internal r eactions.
53 9 Glossary 9.1 Technical ter ms AVR Automatic Voltage Regulation against mains voltage variations DC/DC Booster Circuit technology to boost the direct voltage on a higher voltage leve l EPO E merge.
54 Guarantee ce rtificate Type: …….………………….... ................................................ .. Serial-no.: ……………………..……………............................... Date of purchase: …………….............…………………….
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il AEG Protect B. 3000 VA è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del AEG Protect B. 3000 VA - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso AEG Protect B. 3000 VA imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul AEG Protect B. 3000 VA ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il AEG Protect B. 3000 VA, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del AEG Protect B. 3000 VA.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il AEG Protect B. 3000 VA. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo AEG Protect B. 3000 VA insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.