66401100 e xcellence in hot water Installation, Operating and Servicing Instructions HeatMaster HM 71 HM 101.
1 INTENDED USERS OF THESE INSTR UCTIONS These instructions are intended for - specifying engineers - installing engineers - end-users - servicing engineers SYMBOLS The follo wing symbols are used in these instructions: Essential instruction for operating the system correctly .
OPERA TING PRINCIPLE The HeatMaster is a high performance, direct fired hot water stor age heater , which has indirect heat transfer due to its T ank-in-T ank construction. At the hear t of the HeatMaster is a stainless steel cylinder through which the flue tubes pass.
3 DESCRIPTION Flue reduction collar T op cover A utomatic air v ent Central heating flow pipe Flue pipes and turbulators Insulation Burner Detector NTC3 Heating return Combustion chamber Burner chambe.
4 DIMENSIONS The units are delivered fully assemb led, tested and packed on a timber base with shoc kproof edges and protected by heat-shrunk plastic film. On delivery and after unpacking, check the equipment f or damage. F or transpor t pur poses, refer to the weights and dimensions giv en below .
5 HEA TMASTER CONTROL SETTINGS Description The 71/101 series is fitted with an electronic controller (MCBA) which controls burner operation (ignition, safety and modulation), and provides f acilities to adapt the controller to the desired application.
6 BOILER ROOM Important •K eep vents free at all times . • Do not store inflammable products in the boiler room. • Do not store corrosive products near the boiler , such as paints, solvents , chlor ine, salt, soap and other cleaning products. • If you smell gas, do not s witch on the light or light a flame.
7 INST ALLA TION Balanced flue boiler connection type: C • C13: concentric hor izontal connection • C33: concentric vetical connection • C53: parallel chimney connection • C63: concentr ic vertical connection without ter minal (only in Germany and Luxembourg).
8 INST ALLA TION HO T W A TER CONNECTIONS Pressure reducing valve If the mains water pressure is greater than 6 bar , a pressure reducing v alve must be fitted. Expansion relief valve The tank expansion relief v alve must be A CV approved and calibrated to a maximum of 7 bar .
HEA TING CONNECTION The HeatMaster has two connections at the rear that can be used to connect a central heating circuit. Connecting a heating system may reduce the domestic hot water perf or mance. W ARNING The maximum pump motor load f or the MCBA is 250 W att.
10 ELECTRICAL CONNECTION Po wer supply The boiler operates with a 230 V - 50 Hz single phase supply . A double pole isolator with a 6 amp fuse or a 6 amp MCB must be fitted outside the boiler to allow pow er to be shut off during servicing and before an y repairs are carried out on the boiler.
7 8 9 10 11 12 L1 N T1 T2 S3 B4 L1 N T1 T2 S3 B4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 1 2 3 L1 N T1 T2 S3 B4 B5 T6 T7 T8 3 4 230V ~ 50 Hz.
12 COMMISSIONING FILLING THE HO T W A TER AND HEA TING CIRCUITS IMPORT ANT The hot water tank must be pressurised bef ore the heating circuit is filled. 1. Close the primar y circuit filling valves (11). 2. Open the stop valve (1) and the dr awoff tap (8).
13 BURNER FEA TURES 71/101 Gas burner features (*) propane Gas category T ype HM 71 HM 101 Input Kw 22.0 - 69.9 25.0 - 107 / 22.0 - 110 (*) Output Kw 18.4 - 63.0 23.0 - 96.3 / 20.2 - 99.0 (*) Combustion efficiency - natural gas % 92.0 92.1 Natural gas CO 2 % 9.
14 DRAINING THE BOILER Wa ter flowing out of the drain cock ma y be e xtremely hot and could cause severe scalding. K eep people awa y from discharges of hot water . Draining the heating circuit 1. T urn OFF the on/off switch on the boiler control panel, isolate e xter nal electrical supply , and tur n off the gas supply to the boiler.
15 USING THE BOILER Y our system should be serviced at least once a year by a qualified engineer. If the boiler is subject to heavy use, it may require servicing more than once a year - consult your service engineer for advice.
Changing the MCBA settings: Parameter mode Proceed as follo ws: • Press the “MODE” button once; the display will sho w “P ARA”. Press the “STEP” button once; the first digit is “1” and the last two show the setting f or the first parameter .
17 USER GUIDE codes 00 02 03-07 11 12 13-17 18 19 25 28 31 32 33 36 37 38 44 Error description No flame detected No ignition after 5 attempts Internal error Eprom error Low water pressure or 24V fuse .
18 SERVICE RECORD Date installed: % CO 2 (min. load) : % CO 2 (max. load) : Gas LPG Model : Serial number : Heating system pressure setting : ❏ ❏ Name and signature : Flue gas T° : Efficiency : Gas pressure : INST ALLA TION DET AILS Date serviced : % CO 2 (min.
INTERNA TIONAL A CV international n.v KERKPLEIN, 39 B-1601 RUISBR OEK - BELGIUM TEL.: +32 2 334 82 20 F AX: +32 2 378 16 49 E-MAIL: international.info@acv-world.com BELGIUM A CV BELGIUM n v/sa KERKPLEIN, 39 B-1601 RUISBR OEK-BELGIUM TEL.: +32 2 334 82 40 F AX: +32 2 334 82 59 E-MAIL: belgium.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Casablanca Fan Company HM 71 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Casablanca Fan Company HM 71 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Casablanca Fan Company HM 71 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Casablanca Fan Company HM 71 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Casablanca Fan Company HM 71, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Casablanca Fan Company HM 71.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Casablanca Fan Company HM 71. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Casablanca Fan Company HM 71 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.