Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS ...................1 INST ALLA TION ..............................1 - 8 Step 1 — Complete Pre-Installation Checks ....1 Step 2 — Rig and Mount the Unit ..........
LEGEND A— 1 1 ⁄ 4 -in. (32) diameter knockout for 5 ⁄ 8 -in. (16) ODM liquid line connection B— 1 3 ⁄ 4 -in. (44.5) diameter knockout for suction line connections of 1 1 ⁄ 8 in. (28.6) (38AE012), 1 3 ⁄ 8 in. (35) (38AE014,016), 1 5 ⁄ 8 in.
1 3 2 456 7 8 12 9 10 11 LEGEND 1— Low-V oltage Fuse 5— No. 2 Fan 9— Compressor 2— No. 1 Fan 6— T erminal Block 1 (Unit Power) 1 0— Low-Pressure Switch 3— High-Pressure Switch 7— T erminal Block 2 (Control Power) 11 — Hot Gas Bypass Piping Stub ( 3 ⁄ 8 -in.
T able 1A — Physical Data (English, 60 Hz) UNIT 38AE012 38AE014 38AE016 38AKS024 OPERA TING WEIGHT (lb) 732 779 789 900 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Speed (Rpm) 1750 No. Cylinders 666 4 Model No. 06DD824 06DD328 06DD537 06E4250 Oil (pt) 10 10 10 15.
T able 1C — Physical Data (English, 50 Hz) UNIT 38AE012 38AE014 38AE016 38AKS024 OPERA TING WEIGHT (lb) 732 779 789 900 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Speed (Rpm) 1460 No. Cylinders 666 4 Model No. 06DD824 06DD328 06DD537 06E4250 Oil (pt) 10 10 10 15.
T a b l e2—W eight Distribution UNIT WEIGHT — lb (kg) T otal Operating Support Point AB C D 38AE012 732 (333) 142 (65) 138 (63) 225 (102) 227(103) 38AE014 779 (354) 143 (65) 140 (64) 247 (1 12) 24.
INST ALL FIL TER DRIER(S) AND MOISTURE INDICA- TOR(S) — Every unit should have a filter drier and liquid- moisture indicator (sight glass). In some applications, depending on space and convenience requirements, it may be desirable to install 2 filter driers and sight glasses.
T able 5A — Electrical Data (3 Ph/60 Hz) UNIT UNIT COMPR F AN MOTORS (Single Phase) Model V olts MCA ICF MOCP (Fuse) RLA LRA T otal Fans FLA (ea) Fan No. kW Nameplate Supplied* Min Max 12 38AE012 501 208-230 187 253 62.5 178 100 43.6 170 2 4.3 3.7 1.
PRE-ST ART -UP Evacuate and Dehydrate the entire refrigerant sys- tem by either of the methods described in Carrier Standard Service T echniques Manual, Chapter 1. Leak T est the entire refrigerant system by the pres- sure method described in Carrier Standard Service T ech- niques Manual, Chapter 1.
Fig. 9 — 38AE012 and 38AKS024 Charging Chart 10.
Fig. 10 — 38AE014 Charging Chart 11.
Fig. 1 1 — 38AE016 Charging Chart 12.
Check Operation — V erify operation of all safety con- trols. Replace all service panels. Be sur e that contr ol panel cover is closed tightly . OPERA TING SEQUENCE Cooling — When the first stage (TC1) of the cooling ther- mostat closes, the timer starts.
Outdoor Fans — Each fan is supported by a formed- wire mount bolted to the fan deck and covered with a wire guard. The exposed end of the motor shaft is covered with a rubber boot.
TROUBLESHOOTING PROBLEM SOLUTION COMPRESSOR DOES NOT RUN Contactor Open 1. Power off. 1. Restore power . 2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct size fuse. 3. No control power . 3. Check secondary fuse(s); replace with correct type and size.
TROUBLESHOOTING (cont) PROBLEM SOLUTION COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH (cont) Airflow Restricted 1. Coil iced up. 1. Check refrigerant charge. 2. Coil dirty . 2. Clean coil fins. 3. Air filters dirty . 3. Clean or replace filters. 4. Dampers closed.
.
P ACKAGED SER VICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory , and skills programs is available.
ST ART -UP CHECKLIST A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y .
C. Start-Up CHECK EV APORA TOR F AN SPEED AND RECORD. CHECK CONDENSER F AN SPEED AND RECORD. AFTER A T LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE SUCTION PRESSURE S.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Carrier 38AE016 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Carrier 38AE016 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Carrier 38AE016 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Carrier 38AE016 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Carrier 38AE016, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Carrier 38AE016.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Carrier 38AE016. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Carrier 38AE016 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.