Manuale d’uso / di manutenzione del prodotto DELUXE 11 SEER R-410A del fabbricante Bryant
Vai alla pagina of 28
Form No. PDS 591B.18.1 DELUXE 11 SEER AIR CONDITIONER WITH PURON ® (R-410A) 591B (60 Hz) Sizes 018 thru 060 Br yant’ s Quantum Plus 591B with Puron® provides features which cannot be matched by any other family of equipment. The 591B is a Quantum Plus air conditioning system utilizing Br y- ant’ s unique Puron refr igerant.
—2— DIMENSIONS AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW.
— 3 — RECOMMENDED TUBE DIAMETERS * For tube sets g reater than 50 ft, consult Application Guideline and Ser vice Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant. CHECK-FLO-RA TER ® PISTON * Piston listed is f or any approv ed non-capillar y tube coil combination.
— 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE-SERIES 018-A 024-A 030-A 036-A Operating W eight (Lb) 168 178 188 198 ELECTRICAL Unit V olts — Hertz — Phase 208/230-60-1 Operating V oltage Range* 187-253 Compressor — Rated Load Amps 10.
— 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will oper ate satisf actorily . Oper ation outside these limits may result in unit f ailure. † If wire is applied at ambient g reater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70).
— 6 — A CCESSOR Y USA GE GUIDELINE * For tubing line sets g reater than 50 ft, refer to Application Guideline and Service Manual — Air Conditioning and Heat Pumps Using Puron ® Refrigerant. † Only when low-pressure s witch is used. ‡ Required for lo w-ambient controller (full modulation feature) and MotorMaster ® Control only .
— 7 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 10. Low-Ambient Pressure Switc h A long life pressure s witch which is mounted to outdoor unit service valve . It is designed to cycle the outdoor f an motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig).
— 8 — COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 018-A CC5A/CD5AA024* 17,400 NONE 10.
— 9 — COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 024-A CE3AA024 23,400 TDR 11.
— 10 — COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 036-A CC5A/CD5AA042* 35,400 NONE 10.
— 11 — COMBINA TION RA TINGS Continued UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 036-A COILS + 355MA V060080 V ARIABLE SPEED FURNA CE CC5A/CD5AA042 35,400 TDR 11.
— 12 — UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 042-A CE3AA042 40,000 TDR 11.5 — 11.5 10.30 CE3AA048 40,500 TDR 11.5 — 11.
— 13 — See notes on page 14. . UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 048-A CE3AA060 47,000 TDR 11.5 — 11.5 10.65 CK3BA060 47,000 TDR 11.
— 14 — * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system ma y cause degradation in perf or mance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR.
— 15 — DET AILED COOLING CAP A CITIES* See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † .
— 16 — DET AILED COOLING CAP A CITIES* See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † .
— 17 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity .
— 18 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity .
— 19 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity .
— 20 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity .
— 21 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity .
— 22 — DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur .
— 23 — CONDENSER ONL Y RA TINGS* See notes on page 25. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 591BN018-A 30 TCG SDT KW 15.90 73.70 0.77 15.00 83.10 0.92 14.20 92.60 1.10 13.30 102.00 1.28 12.30 111.40 1.49 11.
— 24 — CONDENSER ONL Y RA TINGS* Continued See notes on page 25. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 591BN036-A 30 TCG SDT KW 32.70 77.00 1.99 30.90 86.20 2.23 29.10 95.40 2.49 27.30 104.60 2.77 25.40 113.
— 25 — SYSTEM DESIGN SUMMAR Y 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor f an external static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor oper ating air temper ature without lo w-ambient oper ation accessory is 55 ° F (12.
— 26 — MA TCHED SYSTEM A98599.
— 27 —.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: New © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 — 28 — PRINTED IN U.S.A. Catalog No.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Bryant DELUXE 11 SEER R-410A è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Bryant DELUXE 11 SEER R-410A - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Bryant DELUXE 11 SEER R-410A imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Bryant DELUXE 11 SEER R-410A ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Bryant DELUXE 11 SEER R-410A, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Bryant DELUXE 11 SEER R-410A.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Bryant DELUXE 11 SEER R-410A. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Bryant DELUXE 11 SEER R-410A insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.