NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,.
INSTALLATION I. CHECK EQUIPMENT AND JOB SITE A. UNPACK UNIT Move to final location. Remove carton, taking care not to damage unit. B. INSPECT EQUIPMENT File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel.
INSTALLING TXV IN PLACE OF PISTON 1. Remove any existing refrigerant and ensure coil has not been exposed to atmospheric pressure for more than 15 minutes. 2. Remove indoor coil inlet tube at piston body inlet. Use back-up wrench to prevent damage. 3.
CAUTION: If ANY refrigerant tubing is buried, provide 6 – in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried without further special consideration. Buried refrigerant tubing lengths greater than 36 in. are NOT recommended.
G. FINAL TUBING CHECK IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
VIII. INSTALL ELECTRICAL ACCESSORIES A. GENERAL Refer to the individual instructions packaged with kits or acces- sories when installing. Available electrical accessories include latent capacity control. See Fig. 11 for typical accessory wiring diagrams.
O/ W2 W/W1 Y1 / W 2 G R THERMIDIST A T CONTROL MODEL RH V ARIABLE-SPEED CONDENSING FURNACE TW O-SPEED AIR CONDITIONER W/W1 G Y/ Y2 C Y2 R Y1 C DHUM HUM B S1 S2 W2 R C HEA T ST AGE 1 COOL ST AGE 1 COOL.
COOL ST AGE 1 FA N HEA T ST AGE 1 COOL ST AGE 2 N/A 24 V A C HOT R W/W1 Y/Y2 O/W2 Y1/W2 G 24 V A C COMM N/A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C PROGRAMMABLE THERMOST A T MODEL 2S SINGLE-ST AGE .
24 V A C HO T FA N COOL ST AGE 1 COOL ST AGE 2 HEA T ST AGE 1 HEA T ST AGE 2 R G R G 24 V A C COMM N/A OUTDOOR SENSOR CONNECTION C B S1 S2 C C R PROGRAMMABLE THERMOST A T MODEL 2S FK4C, FV4A OR 40FK F.
WIRING DIAGRAM NOTES: 1. WIRING MUST CONFORM TO NEC OR LOCAL CODES. 2. UNDERLINED LETTER ON THERMOSTAT TERMINAL INDICATES USAGE. FOR EXAMPLE: O/W2 MEANS O IS ENERGIZED IN COOLING MODE. 3. REFER TO INDOOR UNIT INSTALLATION INSTRUCTIONS FOR ANY ADDITIONAL FEATURES AND WIRING INFORMA- TION.
X. START-UP CAUTION: To prevent compressor damage or personal injury, observe the following: • Do not overcharge system with refrigerant. • Do not operate unit in a vacuum or at negative pressure.
NOTE: If subcooling charging conditions are not favorable, charge must be weighed in accordance with unit rating plate ± 0.6 oz/ft of 3/8-in. liquid line above or below 15 ft respectively. EXAMPLE: To calculate additional charge required for a 25 ft line set: 25 ft - 15 ft = 10 ft x 0.
I. PRESSURE SWITCH PROTECTION The outdoor unit is equipped with high- and low-pressure switches. If the control senses the opening of a high or low pressure switch, it will respond as follows: 1. De-energize the compressor low or high speed contactor, 2.
XIII. FINAL CHECKS IMPORTANT: Before leaving job, be sure to do the following: 1. Ensure that all wiring and tubing is secure in unit before adding panels and covers. Securely fasten all panels and covers. 2. Tighten service valve stem caps to 1/12 turn past finger tight.
Fig. 15 — Wiring Diagram — 024, 036, 048 A01513 CONNECTION DIAGRAM OCT -t ° LPS HPS OAT -t ° LO HI TO INDO O R UN IT RED CCH FA N C A P YEL RED BRN OFM BL K BL U/ PNK BLU/ PNK YEL / PN K YEL / P.
Fig. 16 — Wiring Diagram — 060 A02212 CONNECTION DIAGRA M OCT -t ∞ LPS HPS OAT -t ∞ LO HI T O IN DO O R U NIT RED CCH FA N CA P RED BRN OFM BL K BL U/ PNK BLU / PNK YEL / P NK YEL / PN K BRN B.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Bryant 598B è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Bryant 598B - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Bryant 598B imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Bryant 598B ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Bryant 598B, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Bryant 598B.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Bryant 598B. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Bryant 598B insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.