Form No. PDS 594D.18.7 ELECTRIC AIR CONDITIONER Model 594D (60 Hz) Sizes 018 thru 060 WIDE RANGE OF SIZES —A vailab le in 7 nominal sizes from 018 through 060 to meet the needs f or residential and light commercial applications.
—2— ACCESS PANEL 1 1 / 4 " 1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. Minimum outdoor operating ambient in cooling mode is 55 ° F (unless low-ambient control is used) max 125 ° F.
—3— RECOMMENDED TUBE DIAMETERS * For tube sets between 50 and 175 ft, consult Residential Split System Long-Line Application Guideline . CHECK-FLO-RA TER® * Piston listed is for any appro ved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil.
—4— SPECIFICA TIONS See notes on page 5. UNIT SIZE - SERIES 018-E 024-E 030-E 036-E OPERA TING WT (Lb) 138 143 146 200 ELECTRICAL Unit V olts—Hertz—Phase 208/230—60—1 208/230—60—1 208/230—60—1 208/230—60—1 Operating V oltage Range* 187—253 187—253 187—253 187—253 Compressor— Rated Load Amps 8.
—5— SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will operate satisf actor ily . Operation outside these limits ma y result in unit failure.
—6— ACCESSORY USAGE GUIDELINE * For tubing line sets betw een 50 and 175 ft, refer to Residential Split System Long-Line Application Guideline. † Only when low-pressure s witch is used. A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 1.
—7— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 11. Low-Ambient Contr oller Head pressure controller is a cycle control de vice activ ated by a temperature sensor mounted on a header tube of the outdoor coil.
—8— COMBINA TION RA TINGS See notes on page 11. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 018-E CK5A/CK5BA024* 17,600 NONE 10.
—9— COMBINA TION RA TINGS Continued See notes on page 11. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 030-E FC4BNF030 28,200 TDR & TXV 11.
—10— COMBINA TION RA TINGS Continued UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 042-E CD5AA048* 41,000 NONE 11.00 11.50 11.
—11— COMBINA TION RA TINGS Continued * T ested Combination † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg r adation in perf ormance. Use either the accessory Time-Dela y Rela y KAA TD0101TDR or a furnace equipped with TDR.
—12— DET AILED COOLING CAP A CITIES* See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† To.
—13— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity M.
—14— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity M.
—15— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity M.
—16— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity M.
—17— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity M.
—18— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI Standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur .
—19— CONDENSER ONLY RATINGS* See notes on page 20. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 594D018-E 30 TCG 16.9 16.2 15.4 14.6 13.8 12.9 12.0 SDT 77.1 86.9 96.8 107.0 116.00 126.0 136.0 KW 0.809 0.930 1.07 1.22 1.38 1.
—20— CONDENSER ONLY RATINGS* Continued * ARI listing applies only to systems shown in P erformance Data table . KW — T otal P ower (Kw) SDT — Saturated T emperature Lea ving Compressor (°F) S.
—21— SYSTEM DESIGN SUMMAR Y 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure av ailable is less than 0.01 in. wc. 2. Minimum outdoor operating air temperature without lo w-ambient operation accessor y is 55°F (12.
—22— MA TCHED SYSTEM A98599.
—23—.
—2 4— SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 594D.18.6 © 1999 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 PRINTED IN U.S.A. Catalog No.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Bryant 594D è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Bryant 594D - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Bryant 594D imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Bryant 594D ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Bryant 594D, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Bryant 594D.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Bryant 594D. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Bryant 594D insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.