Form No. PDS 593C.18.7 ELECTRIC AIR CONDITIONER Model 593C (60 Hz) Sizes 018 thru 060 WEA THER-PRO TECTIVE CABINET —Steel is galvaniz ed and coated with a la yer of zinc phosphate . A coat of modified poly- ester powder coating is then applied and bak ed-on, providing each unit with a hard, smooth finish that will last f or many y ears.
— 2 — AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW.
— 3 — RECOMMENDED TUBE DIAMETERS * For tube sets betw een 50 and 175 ft, consult Residential Split System Long-Line Application Guideline. CHECK-FLO-RA TER ® PIST ON * Piston listed is f or any appro ved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil.
— 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE 018-C, D 024-C, D 030-C, D 036-C, D Operating W eight (Lb) 137 143 161 169 ELECTRICAL Unit V olts — Her tz — Phase 208 – 230 — 60 — 1 Operating V oltage Range* 197 — 253 Compressor — Rated Load Amps 8.
— 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will operate satisf actorily . Operation outside these limits may result in unit f ailure. † If wire is applied at ambient greater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70).
— 6 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 1. Ball Bearing Fan Motor A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation f eature) or MotorMaster ® Control has been added.
— 7 — A CCESSOR Y DESCRIPTION AND USE (Listed Alphabetically) Continued 17. Time Delay Rela y An SPST dela y relay which brie fl y continues oper ation of the indoor blower motor to pro vide additional cooling after the compressor cycles off.
— 8 — COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 018-C, D CC5A/CD5AA018* 17,200 NONE 10.
— 9 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 030-C, D CC5A/CD5AA030* 28,600 NONE 10.
— 10 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 036-C, D CC5A/CD5AA036* 34,600 NONE 10.
— 11 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 036-C, D COILS + 355MA V042040 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 34,600 NONE 11.
— 12 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 042-C, D CK5A/CK5BA042 39,500 TDR 11 11 10.
— 13 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 048-C FB4(A,B)NB070 48,000 TDR 11.
— 14 — COMBINA TION RA TINGS Contin ued * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg radation in performance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a fur nace equipped with TDR.
— 15 — DET AILED COOLING CAP ACITIES* See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBt.
— 16 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 17 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 18 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 19 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 20 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 21 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 22 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 23 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 24 — DET AILED COOLING CAP ACITIES* Contin ued NO TE: When the required data fall betw een the published data, interpolation may be perf ormed. Extrapolation is not an acceptab le practice. * Detailed cooling capacities are based on indoor and outdoor unit at same ele vation per ARI standard 210/240-94.
— 25 — CONDENSER ONL Y RA TINGS* See notes on page 26. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 593C018-C, D TCG 17.9 16.6 15.3 14.0 12.7 11.3 10.0 30 SDT 75.7 84.2 93.0 102.0 111.0 120.0 129.0 KW 1.10 1.18 1.26 1.
— 26 — CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erformance table. KW — T otal P ower (kW) SDT — Saturated T emperature Lea ving Compress.
— 27 — SYSTEM DESIGN 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without lo w ambient operation accessor y is 55 ° F (12.
— 28 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 593C.18.6 © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Bryant 593C è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Bryant 593C - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Bryant 593C imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Bryant 593C ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Bryant 593C, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Bryant 593C.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Bryant 593C. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Bryant 593C insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.