Manuale d’uso / di manutenzione del prodotto 569C del fabbricante Bryant
Vai alla pagina of 20
IMPORT ANT —READ BEFORE INST ALLING 1. Read and become familiar with these installation instructions before installing this unit (Fig. 1). 2. Be sure the installation conforms to all applicable local and national codes. 3. These instructions contain important information for the proper maintenance and repair of this equipment.
NOTE: If vibration isolators are required for a particular in- stallation, use corner weight information in Fig. 2 to make proper selection. I. LOCA TE THE UNIT A. Clearance Maintain clearance around and above unit to provide mini- mum distance from combustible materials, proper airflow , and service access.
T able 1A — Specifications (English) UNIT 569C072 569C090 569C120 576B090 576B102 576B120 NOMINAL CAP ACITY (T ons) 67 1 ⁄ 2 10 7 1 ⁄ 2 8 1 ⁄ 2 10 OPERA TING WEIGHT (lb) Aluminum Coils (Stand.
T able 1B — Specifications (SI) UNIT 569C072 569C090 569C120 576B090 576B102 576B120 NOMINAL CAP ACITY (kW) 21 26 35 26 29.9 35 OPERA TING WEIGHT (kg) Aluminum Coils (Standard) 154 168 179 231 256 .
UNIT DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F 569C072 1 8 -6 1 ⁄ 2 9 1 8 -2 3 ⁄ 4 9 —1 8 -2 1 ⁄ 4 9 1 8 -4 5 ⁄ 16 9 2 8 -9 5 ⁄ 16 9 [470.0] [375.0] — [362] [415] [846.5] 569C090 1 8 -8 9 1 8 -6 1 ⁄ 2 9 —1 8 -3 9 2 8 - 5 ⁄ 16 9 3 8 -5 7 ⁄ 16 9 [508.
B. Filter Drier and Moisture Indicator The filter drier is factory installed. Moisture indicator is a field-installed accessory and should be installed just after liq- uid line shutof f valve. Do not use a receiver . A receiver is not supplied with the unit and should not be used.
All units except 208/230-v units are factory wired for the volt- age shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply , the transformer must be rewired by moving the black wire from the 230-v orange wire on the transformer and connecting it to the 200-v red wire from the transformer .
T able 4 — Electrical Data UNIT NOMINAL VOL T AGE (V -Ph-Hz) VOL T AGE RANGE COMPRESSOR OFM POWER SUPPL Y Min Max RLA LRA FLA MCA MOCP 569C072 208/230-3-60 187 254 21.8 142 1.9 25.6 35 460-3-60 414 508 9.6 72 1.0 12.9 15 575-3-60 518 632 7.6 58 1.9 1 1.
T able 5 — American/European Wire Conversions AMERICAN EUROPEAN Industry Standard Size American Conversion (mm 2 ) Industry Standard Size (mm 2 ) 18 A WG 0.82 1.0 16 A WG 1.30 1.5 14 A WG 2.08 2.5 12 A WG 3.30 4.0 10 A WG 5.25 6.0 8A W G 6.36 10.0 6A W G 13.
ST ART -UP I. ST ART -UP AND ADJUSTMENTS CAUTION: Complete the required procedures given in the Pre-Start-Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the compressor when the outdoor tem- perature is below 25 F ( 2 4 C) (unless accessory low am- bient kit is installed).
SERVICE W ARNING: When servicing unit, shut of f all electri- cal power to unit to avoid shock hazard or injury from rotating parts. I. CLEANING Inspect unit interior at the beginning of each cooling season and as operating conditions require. A. Condenser Coil Inspect coil monthly .
IV . CAP ACITY CONTROL (576B120 Only) A suction pressure-actuated unloader controls 2 cylinders and provides capacity control. Unloaders are factory set (see T able 1A or 1B), but may be field adjusted: A. Control Set Point The control set point (cylinder load point) is adjustable from 0 to 85 psig (586 kPa).
Fig. 14 — Cooling Charging Chart — 569C072 Fig. 15 — Cooling Charging Chart — 569C090,120 and 576B090,102,120 —13—.
TROUBLESHOOTING GUIDE SYMPTOM CAUSE REMEDY Compressor does not run — Contactor open Power off. Restore power . Fuses blown. Replace with correct fuses after finding cause and correcting. T ransformer open/shorted. Replace transformer if primary windings are receiving power and no output.
LEGEND FOR FIG. 16 AND 17 C— Contactor , Compressor CAP — Capacitor CB — Circuit Breaker CH — Crankcase Heater CLO — Compressor Lockout COMP — Compressor Motor COTP — Compressor T empera.
.
.
Copyright 1999 Bryant Heating & Cooling Systems CA TALOG NO. 5356-902.
ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES II. PRE-ST ART -UP OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y .
III. ST ART -UP CHECK EV APORA TOR-F AN SPEED AND RECORD. CHECK CONDENSER-F AN SPEED AND RECORD. AFTER A T LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE (576B only) SU.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Bryant 569C è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Bryant 569C - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Bryant 569C imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Bryant 569C ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Bryant 569C, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Bryant 569C.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Bryant 569C. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Bryant 569C insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.