Manuale d’uso / di manutenzione del prodotto 552A del fabbricante Bryant
Vai alla pagina of 36
Form No. PDS 552A.18.3 DELUXE 12 SEER AIR CONDITIONER WITH PURON ® REFRIGERANT 552A (60 Hz) Sizes 018 thru 060 Br yant’ s Quantum Plus 552A with Puron® refr igerant provides f eatures which cannot be matched by any other family of equip- ment. The 552A is a Quantum Plus air conditioning system uti- lizing Br yant’ s unique Puron refr igerant.
— 2 — DIMENSIONS AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW.
— 3 — RECOMMENDED TUBE DIAMETERS * For tube sets g reater than 50 ft and/or 20 ft vertical differential, consult Application Guideline and Service Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant. CHECK-FLO-RA TER ® PISTON * Piston listed is for any appro ved non-capillary tube coil combina- tion.
— 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE-SERIES 018-F 024-F/G 030-F 036-F/G Operating W eight (Lb) 168 209 209 212 ELECTRICAL Unit V olts — Her tz — Phase 208/230 — 60 — 1 Operating V oltage Range* 187 — 253 Compressor — Rated Load Amps 10.
— 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will oper ate satisf actor ily . Operation outside these limits ma y resu lt in unit f ailure. † If wire is applied at ambient g reater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70).
— 6 — A CCESSOR Y USA GE GUIDELINE * For tubing line sets g reater than 50 ft and/or 20 ft ver tical differential, ref er to Application Guideline and Ser vice Manual — Air Conditioning and Heat Pumps Using Puron ® Refrigerant. † Only when low-pressure s witch is used.
— 7 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Contin ued 10. Low-Ambient Pressure Switc h A long life pressure s witch which is mounted to outdoor unit service valve . It is designed to cycle the outdoor f an motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig).
— 8 — COMBINATION RATINGS UNIT SIZE-SERIES INDOOR UNIT TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV ‡ 018-F *CK5A/CK5BA024 17,500 NONE — 12.00 12.00 10.
— 9 — 024-F CK5A/CK5BW030 23,200 TDR 13.00 — 13.00 11.20 CK5P A024 23,000 TDR&TXV 12.50 —— 11.10 CK5P A030 23,200 TDR&TXV 13.00 —— 11.20 CK5PW024 23,000 TDR&TXV 12.50 —— 11.10 CK5PW030 23,200 TDR&TXV 13.00 —— 11.20 COILS + 355MA V042040 V ARIABLE-SPEED FURNACE CC5A/CD5A W030 23,200 TDR 13.
— 10 — 024-G CE3AA030 22,600 TDR 13.00 — 13.00 11.80 CK3BA024 22,200 TDR 13.00 — 13.00 11.85 CK3BA030 22,600 TDR 13.00 — 13.00 11.90 CK5A/CK5BA024 22,200 TDR 13.00 — 13.00 11.70 CK5A/CK5BA030 22,600 TDR 13.00 — 13.00 11.80 CK5A/CK5BW024 22,200 TDR 13.
— 11 — 024-G CK5A/CK5BW030 22,600 TDR 13.00 — 13.00 11.80 CK5PW024 22,200 TDR&TXV 13.00 —— 11.65 CK5PW030 22,600 TDR&TXV 13.00 —— 11.75 COILS + 315(A,J)A V060120 V ARIABLE-SPEED FURNA CE CE3AA024 22,200 TDR 13.00 — 13.00 11.45 CE3AA030 22,600 TDR 13.
— 12 — 030-F CK5PW036 29,000 TDR&TXV 13.00 —— 11.60 COILS + 355MA V042060 V ARIABLE-SPEED FURNACE CC5A/CD5AA036 29,000 TDR 13.00 — 13.00 11.25 CC5A/CD5A W030 28,000 TDR 12.50 — 12.50 10.80 CK3BA030 28,000 TDR 12.50 — 12.50 10.85 CK3BA036 29,000 TDR 13.
— 13 — 036-F , G CK5A/CK5BT036 34,600 TDR 12.50 — 12.50 11.15 CK5P A036 34,600 TDR&TXV 12.50 —— 11.15 CK5PE042 34,600 TDR&TXV 12.50 —— 11.25 CK5PT036 34,600 TDR&TXV 12.50 —— 11.15 COILS + 315(A,J)A V048090 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 34,600 TDR 12.
— 14 — 036-F , G CK3BA042 34,600 TDR 12.50 — 12.50 11.20 CK5A/CK5BA036 34,600 TDR 12.50 — 12.50 11.15 CK5P A036 34,600 TDR&TXV 12.50 —— 11.15 COILS + 355MA V042080 V ARIABLE-SPEED FURNACE CC5A/CD5AA042 34,600 TDR 12.50 — 12.50 11.25 CC5A/CD5A W036 34,600 TDR 12.
— 15 — 042-F CK5P A042 39,000 TDR&TXV 12.50 —— 10.85 CK5P A048 39,500 TDR&TXV 12.50 —— 10.95 CK5PE042 39,500 TDR&TXV 12.50 —— 10.90 CK5PT042 39,000 TDR&TXV 12.50 —— 10.85 CK5PT048 39,500 TDR&TXV 12.50 —— 10.
— 16 — 042-F CC5A/CD5A C048 39,000 TDR 12.50 — 12.50 10.65 CD5AA048 39,500 TDR 12.50 — 12.50 10.80 CK3BA042 39,000 TDR 12.50 — 12.50 10.75 CK3BA048 39,500 TDR 12.50 — 12.50 10.85 CK5A/CK5BA042 39,000 TDR 12.50 — 12.50 10.75 CK5A/CK5BA048 39,500 TDR 12.
— 17 — 048-F CK5P A048 44,500 TDR&TXV 12.00 —— 10.60 CK5PT048 44,500 TDR&TXV 12.00 —— 10.60 COILS + 315(A,J)A V066110 V ARIABLE-SPEED FURNA CE CC5A/CD5AA060 45,000 TDR 12.50 — 12.50 10.85 CC5A/CD5A C048 44,000 TDR 12.00 — 12.00 10.
— 18 — 048-F CK5PX060 46,000 TDR&TXV 12.00 —— 10.70 COILS + 355MA V060100 V ARIABLE-SPEED FURNACE CC5A/CD5AA060 44,500 TDR 12.00 — 12.00 10.55 CC5A/CD5A C048 44,000 TDR 12.00 — 12.00 10.40 CC5A/CD5A W060 45,500 TDR 12.50 — 12.50 10.85 CD5AA048 44,500 TDR 12.
— 19 — * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg radation in perf or mance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR.
— 20 — DET AILED COOLING CAP A CITIES* See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † .
— 21 — DET AILED COOLING CAP A CITIES* continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity .
— 22 — DET AILED COOLING CAP A CITIES* continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity .
— 23 — DET AILED COOLING CAP A CITIES* continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity .
— 24 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity .
— 25 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity .
— 26 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity .
— 27 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity .
— 28 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity .
— 29 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity .
— 30 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity .
— 31 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity .
— 32 — DET AILED COOLING CAP A CITIES* Continued NO TE: When the required data fall between the pub lished data, inter polation may be perf or med. Extrapolation is not an acceptable pr actice. * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94.
— 33 — CONDENSER ONL Y RA TINGS* See notes on page 35. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 552AN018-F 30 TCG 16.0 15.1 14.3 13.4 12.4 11.5 10.5 9.50 SDT 67.7 77.4 87.0 96.7 106.4 116.1 125.8 135.2 KW 0.80 0.
— 34 — CONDENSER ONL Y RA TINGS* Continued See notes on page 35. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 552AN030-F 30 TCG SDT KW 26.7 71.2 1.41 25.3 80.9 1.59 23.8 90.6 1.80 22.4 100. 2.04 21.0 110. 2.30 19.5 120.
— 35 — SYSTEM DESIGN SUMMAR Y 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure availab le is less than 0.01-in. wc. 2. Minimum outdoor oper ating air temperature without low-ambient oper ation accessor y is 55 ° F (12.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 552A.18.2 New: PDS 552A.18.3 © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 — 36 — PRINTED IN U.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Bryant 552A è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Bryant 552A - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Bryant 552A imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Bryant 552A ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Bryant 552A, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Bryant 552A.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Bryant 552A. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Bryant 552A insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.