Form No. PDS 550A.24.10 DELUXE 13 SEER AIR CONDITIONER WITH PURON ® REFRIGERANT 550A Sizes 024 thru 060 Br yant’ s Air Conditioners with Puron® refr igerant provide a col- lection of features unmatched by an y other family of equipment. The 550A family has been designed utilizing Br yant’ s Puron refrigerant.
—2— DIMENSIONS A99067 AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW.
—3— RECOMMENDED TUBE DIAMETERS *F or tube sets greater than 50 ft horizontal and/or 20 ft v er tical differential, consult Residential Split System Application Guideline and Service Manual. CHECK-FLO-RA TER® PIST ON *Piston listed is f or any appro ved non-capillary tube coil com- bination.
—4— SPECIFICA TIONS See notes on page 5. . UNIT SIZE-SERIES 024-G 030-F 036-F/G Operating Weight (Lb) 214 202 237 ELECTRICAL Unit V olts—Her tz—Phase 208/230—60—1 Operating V oltage Range* 187—253 Compressor— Rated Load Amps 12.8 14.7 15.
—5— SPECIFICA TIONS Continued *P ermissible limits of the voltage r ange at which the unit will operate satisf actorily . Operation outside these limits ma y result in unit f ailure. † If wire is applied at ambient greater than 30°C (86°F), consult T able 310-16 of the NEC (ANSI/NFP A 70).
—6— EV OLUTION™* CONTROLS * When applied with Bryant’ s Perf ect Humidity™ ser ies 355, 315 and FE Indoor Models. † Must be installed in Dual-Fuel Evolution system applications .
—7— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 5. Crankcase Heater An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging.
—8— COMBINA TION RA TINGS UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH FA C T OR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory Puron TXV‡ 024-G *CC5A/CD5AA030 23,000 NONE — 13.00 13.00 11.
—9— 024-G COILS + 315(A,J)A V066155 V ARIABLE-SPEED FURNA CE CE3AA024 22,400 TDR 14.00 — 14.00 12.30 CE3AA030 22,800 TDR 14.00 — 14.00 12.55 COILS + 355MA V042040 V ARIABLE-SPEED FURNACE CE3AA024 22,400 TDR 14.00 — 14.00 12.20 CE3AA030 22,800 TDR 14.
—10— 030-F FF1DNA030 28,600 TDR 12.50 — 12.50 11.05 FG3AAA036 28,400 NONE — 12.50 12.50 11.00 FK4(C,D)NF001 29,000 TDR&TXV 13.00 — — 11.95 FK4(C,D)NF002 29,000 TDR&TXV 13.50 — — 12.05 FK4(C,D)NF003 29,600 TDR&TXV 14.00 — — 12.
—11— 030-F COILS + 355MA V042060 V ARIABLE-SPEED FURNACE CC5A/CD5AA036 29,600 TDR 13.50 — 13.50 11.90 CC5A/CD5A W030 28,400 TDR 13.20 — 13.20 11.50 CE3AA030 29,000 TDR 13.20 — 13.20 11.65 CE3AA036 29,200 TDR 13.50 — 13.50 11.75 CK3BA030 28,400 TDR 13.
—12— 036-F CK5PE042 35,000 TDR&TXV 14.00 — — 12.20 CK5PT036 35,000 TDR&TXV 13.50 — — 12.05 CK5PT042 35,000 TDR&TXV 14.00 — — 12.15 CK5PW036 35,000 TDR&TXV 13.50 — — 12.05 COILS + 315(A,J)A V060110 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 35,000 TDR 14.
—13— 036-F CK3BA042 35,000 TDR 13.50 — 13.50 11.75 CK5A/CK5BA042 35,000 TDR 13.50 — 13.50 11.75 CK5A/CK5BT042 35,000 TDR 13.50 — 13.50 11.75 CK5A/CK5BW036 35,000 TDR 13.20 — 13.20 11.60 CK5P A042 35,000 TDR&TXV 13.50 — — 11.75 CK5PT042 35,000 TDR&TXV 13.
—14— 036-G FV4BNF003 35,000 TDR&TXV 14.00 — — 12.40 FV4BNF005 36,000 TDR&TXV 14.50 — — 12.85 FX4BNF036 35,000 TDR&TXV 12.50 — — 11.20 FX4BNF042 35,600 TDR&TXV 13.00 — — 11.40 COILS + 315(A,J)A V036070 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 34,400 TDR 13.
—15— 036-G COILS + 355MA V042040 V ARIABLE-SPEED FURNACE CC5A/CD5AA042 34,400 TDR 13.50 — 13.50 11.85 CC5A/CD5A W036 34,400 TDR 13.50 — 13.50 11.85 CC5A/CD5A W042 33,800 TDR 13.50 — 13.50 11.75 CE3AA036 34,000 TDR 13.50 — 13.50 11.65 CE3AA042 34,600 TDR 13.
—16— 036-G CK3BA036 34,600 TDR 13.50 — 13.50 12.00 CK3BA042 34,600 TDR 13.50 — 13.50 12.05 CK5A/CK5BA036 34,600 TDR 13.50 — 13.50 12.00 CK5A/CK5BA042 34,600 TDR 13.50 — 13.50 12.05 CK5A/CK5BE042 34,600 TDR 13.50 — 13.50 12.15 CK5A/CK5BT036 34,600 TDR 13.
—17— 042-F CC5A/CD5A W048 40,500 TDR 14.00 — 14.00 11.95 CD5AA048 40,500 TDR 14.00 — 14.00 11.90 CE3AA042 40,500 TDR 13.50 — 13.50 11.85 CE3AA048 41,000 TDR 13.50 — 13.50 11.90 CK3BA042 40,500 TDR 13.50 — 13.50 11.80 CK3BA048 40,500 TDR 14.
—18— 042-F CK5PT042 40,500 TDR&TXV 13.00 — — 11.30 CK5PT048 40,500 TDR&TXV 13.20 — — 11.55 COILS + 355MA V060080 V ARIABLE-SPEED FURNACE CC5A/CD5AA042 40,500 TDR 13.20 — 13.20 11.50 CC5A/CD5A C048 40,000 TDR 13.20 — 13.20 11.55 CD5AA048 40,500 TDR 13.
—19— 048-F COILS + 315(A,J)A V060110 V ARIABLE-SPEED FURNA CE CC5A/CD5AA060 46,000 TDR 13.00 — 13.00 12.00 CC5A/CD5A C048 45,000 TDR 13.00 — 13.00 11.70 CC5A/CD5A W048 45,500 TDR 13.50 — 13.50 11.95 CD5AA048 45,500 TDR 13.50 — 13.50 11.95 CE3AA048 46,000 TDR 13.
—20— 048-F CK5P A060 46,500 TDR&TXV 13.00 — — 11.70 CK5PT060 46,500 TDR&TXV 13.00 — — 11.70 CK5PX060 47,500 TDR&TXV 13.50 — — 12.05 COILS + 355MA V060120 V ARIABLE-SPEED FURNACE CC5A/CD5AA060 46,500 TDR 13.00 — 13.00 11.55 CC5A/CD5A W048 46,000 TDR 13.
—21— COMBINA TION RA TINGS Continued UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH FA C T OR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Bryant Gas Furnace or Accessory TDR + TXV‡ Accessory Puron TXV‡ 060-H *CD5PX060 59,000 TXV — 13.
—22— *T ested combination. † In most cases, only one method should be used to achie ve TDR function. Using more than one method in a system may cause deg radation in perf or mance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR.
—23— DET AILED COOLING CAP A CITIES* See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T ota.
—24— DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—25— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—26— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—27— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—28— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—29— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—30— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—31— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—32— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—33— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—34— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—35— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—36— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—37— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtu.
—38— DET AILED COOLING CAP A CITIES* Continued NO TE: When the required data f alls between the published data, interpolation may be perf or med. Extrapolation is not an acceptable pr actice. * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94.
—39— CONDENSER ONL Y RA TINGS* See notes on page 40. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 125 550A024-G 30 TCG 20.9 19.4 17.9 16.2 14.4 12.4 10.2 7.8 SDT 69.8 79.1 88.3 97.6 106.7 115.7 124.7 133.6 KW 0.92 1.07 1.
—40— CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Combination Ratings tab le. KW — Outdoor Unit Kilow atts Only SDT — Saturated T emperature Leaving Compressor (°F) SST — Saturated T emperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh).
—41— SYSTEM DESIGN SUMMAR Y 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor f an external static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temper ature without low-ambient operation accessor y is 55°F (12.
—42—.
—43—.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 550A.24.9 © 2004 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 —4 4— PRINTED IN U.S.A. Catalog No.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Bryant 550A è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Bryant 550A - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Bryant 550A imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Bryant 550A ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Bryant 550A, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Bryant 550A.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Bryant 550A. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Bryant 550A insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.