TECHNICAL GUIDE AFFINITY R-22 SPLIT -SYSTEM HEA T PUMPS 12 SEER MODELS: YMA024 THRU 060 (2 THRU 5 NOMINAL TONS) Due to continuous pr od uct improvement, sp eci fications are subject to change without n otice. Visit us on the web at www .yor k.com for the most up-to-date technical information.
036-21570-002 Rev. D (0605) 2 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request.
036-21570-002 Rev. D (0605) Unitary Products Group 3 PROCEDURES: 1. Unit factory charge listed on the unit nameplate inclu des refr igerant for the co ndenser , the smallest evaporator and 15 feet of inter- connecting line tubing. 2. V erify the TXV and additional charge requ ired for specific evaporator coil in th e system using the above table.
036-21570-002 Rev. D (0605) 4 Unitary Products Group ** Refer to Quick Selection Chart for specific furnace mat ch-up. COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL CO.
036-21570-002 Rev. D (0605) Unitary Products Group 5 COOLING CAP ACITY - Upflow , Downflow & Horizontal Furnaces and Coils UNIT MODEL FURNACE** COI L MODEL COOLING CFM RANGE (MIN.-MAX.) WR A T E D C F M TOT AL CAP ACITY SENSIBLE CAP ACITY SEER W/O TXV + T DR 1,2 SEER W/TXV + TDR EER YMA0241 1 600 1000 14 G1F A036S1 4 800 24.
036-21570-002 Rev. D (0605) 6 Unitary Products Group COOLING CAP ACITY - With V a riable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COI L MODEL 1 W COOLING RA TED CFM TOTAL CAP ACITY SENS.
036-21570-002 Rev. D (0605) Unitary Products Group 7 UNIT MODEL V ARIABLE SPEED FURNACE MODEL COI L MODEL 4 W COOLING RA TED CFM TOT AL CAP ACITY SENSIBLE CAP ACITY SEER W/O TXV +TDR SEER/ W/TXV +TDR 5 EER 1 PH 12 SEER HP / P1DU / P1XD / P1XU - V ARIABLE SPEED 6 YMA0481 1 P*DUC20V G1F A060S21(T) 21 1610 46.
036-21570-002 Rev. D (0605) 8 Unitary Products Group COP equals MBH output divided by (t ot al KW input x 3.412). HSPF (Heating Seasonal Performa nce Factor) is the tot al heatin g output during a norma l annua l usage period for heating divided by the to t al electric power input during the same period.
036-21570-002 Rev. D (0605) Unitary Products Group 9 COP equals MBH output divided by (tot al KW inp ut x 3.412). HSPF (Heating Seasonal Performa nce Factor) is the total heat i ng output during a norma l annual usage period for heating divide d by the total electric power input during the same period.
036-21570-002 Rev. D (0605) 10 Unitary Products Group ACCESSORIES* Hard St art Kit (024-31994-000, 024-31995-000) - Provides increased starting torque for areas with low voltage. TXV Kit s - 1 TV07 seri es thermal expansion valves precisely meter refrigerant for optimum pe rforman ce.
036-21570-002 Rev. D (0605) Unitary Products Group 11 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 7.
036-21570-002 Rev. D (0605) 12 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif f erent than those listed (bet ween .
036-21570-002 Rev. D (0605) Unitary Products Group 13 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 7.
036-21570-002 Rev. D (0605) 14 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif f erent than those listed (bet ween .
036-21570-002 Rev. D (0605) Unitary Products Group 15 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 7.
036-21570-002 Rev. D (0605) 16 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif f erent than those listed (bet ween .
036-21570-002 Rev. D (0605) Unitary Products Group 17 Multipliers for determini ng the performance with other indoor section. HEA TING P ERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA024 1 1 INDOOR COIL MODEL NO. G2FD030S17 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
036-21570-002 Rev. D (0605) 18 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA030 1 1 INDOOR COIL MODEL NO. G2FD030S17 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
036-21570-002 Rev. D (0605) Unitary Products Group 19 Multipliers for determining the performance with other indoor sections . HEA TING P ERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA036 1 1 INDOOR COIL MODEL NO. G2FD036S17 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
036-21570-002 Rev. D (0605) 20 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA042 1 1 INDOOR COIL MODEL NO. G2FD048S21 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
036-21570-002 Rev. D (0605) Unitary Products Group 21 Multipliers for determining the performance with other indoor sections . HEA TING P ERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA048 1 1 INDOOR COIL MODEL NO. G1F A06 0S24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
036-21570-002 Rev. D (0605) 22 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA060 1 1 INDOOR COIL MODEL NO. G1F A06 0S24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
036-21570-002 Rev. D (0605) Unitary Products Group 23 MA TCHING INDOOR COMPONENTS G1UA 1/2 CASED UPFLOW G1HD HORIZONT AL DUCT G2FD* MUL TI-POSITION (UPFLOW , HORIZONT AL AND DOWNFLOW) * A vailable with factor y installed horizontal drain p an.
Subject to change without notice. Printe d in U.S.A. 036-21570-002 Rev. D (0605) Copyright © by York International Corp. 2005. All right s reserved. Supersedes: 036-21570-002 Rev.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York YMA024 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York YMA024 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York YMA024 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York YMA024 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York YMA024, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York YMA024.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York YMA024. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York YMA024 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.