technic al guide W a t e r S o u r c e He at P umps.
2 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Johnson Controls 3 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) INTR ODUCTION Performance and dependability in a no-nonsense heat pump.
4 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps SPECIFICA TIONS GENERAL All R-series models ½ - 6 ton ship as factory-charged packages, complete with R-410A refrigerant. Horizontal (RSH) units are designed for suspended ceiling mount- ing.
Johnson Controls 5 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) NOMENCLA TURE WA TER SOUR CE HEA T PUMP Product Category RS = Water-Cooled HP R-410A Product Indentifier V = Vertical A.
6 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PHY SICAL D A T A Model Series 007 009 012 018 024 030 036 042 048 060 070 Nominal Cooling (T on) 1 0.5 0.75 1.0 1.5 2.0 2.5 3 3.5 4 5 6 Compressor-T ype Rotary Reciprocating Scroll Air Coil-T ype Enhanced Copper tubes, Enhanced Aluminum Fins Face Area(sq ft) 1.
Johnson Controls 7 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) ARI/ISO PERFORMANCE D A T A PERFORMANCE D A T A - ARI/ISO 13256-1 WA TER LOOP CONDITIONS* Unit Model Flow Rate (USGPM) Air Flow (SCFM) Cooling Capacity (Btuh) EER Heating Capacity (Btuh) COP 007 1.
8 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*007 — 320 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 1.8 4.8 1 1.0 4.1 0.44 2.6 80 2.7 30 1.0 2.1 4.9 8.
Johnson Controls 9 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) PERFORMANCE D A T A RS*009 — 320 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 2.4 7.0 16.1 5.6 0.57 3.7 84 2.9 30 1.2 2.6 6.0 12.
10 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*012 — 400 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 3.0 3.9 9.0 8.2 0.86 5.3 87 2.8 30 1.5 2.0 4.5 16.
Johnson Controls 11 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) PERFORMANCE D A T A RS*018 — 640 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 4.8 8.4 19.4 10.4 1.09 6.7 83 2.8 30 2.4 3.1 7.1 26.
12 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*024 — 800 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 6.0 9.7 22.4 13.3 1.50 8.2 83 2.6 30 3.0 3.4 7.9 35.
Johnson Controls 13 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) PERFORMANCE D A T A RS*030 — 1000 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 7.8 7.8 18.0 17.5 1.97 10.8 84 2.6 30 3.9 4.2 9.
14 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*036 — 1200 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 9.0 10.1 23.3 19.9 1.94 2.0 83 3.0 30 4.5 3.4 7.
Johnson Controls 15 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) PERFORMANCE D A T A RS*042 — 1400 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 10.4 12.3 28.4 26.7 3.32 15.4 86 2.5 30 5.2 4.1 9.
16 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*048 — 1600 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 12.0 15.1 34.9 30.5 3.32 19.1 86 2.8 30 6.0 4.4 10.
Johnson Controls 17 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) PERFORMANCE D A T A RS*060 — 2000 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 15.0 17.8 41.1 38.2 3.32 26.8 86 2.9 30 7.5 5.9 13.
18 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*070 — 2200 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 17.5 20.8 48.0 42.1 3.32 30.7 86 2.6 30 8.8 8.3 19.
Johnson Controls 19 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) CORRECTION F ACT ORS ANTIFREEZE CORRECTION T ABLE Antifreeze Concentration 5% 10% 15% 20% 25% 30% 40% Ethylene Glycol Cooling 0.998 0.995 0.993 0.991 0.989 0.987 0.984 Heating 0.
20 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps BL O WER PERFORMANCE BLO WER PERFORMANCE Unit Size Rated CFM Min. CFM Max.
Johnson Controls 21 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) ELECTRICAL D A T A RSH/RSV ELECTRICAL D A T A Unit Size SUPPL Y VOL T AGE COMPRESSOR BLOWER MIN. CCT . AMP ACITY MAX FUSE / CCT . BKR. AMP QTY RLA LRA HP FLA 007 208-230/1/60 1 @ 3.
22 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps D A B E C G 1.50" J 2.00" K L 1.63" M 3/4 FPT DRAIN W A TER IN W A TER OUT SUPPL Y AIR AIR RETURN 0.
Johnson Controls 23 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) A C K L 2 1" G D G F E G D G F E SERVICE DOORS 1 - ELECTRICAL BOX SERVICE DOOR 2 - COMPRESSOR AND C ONDENSER SERV.
24 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps WIRING DIA GRAM SINGLE PHASE RS* UNITS: 208-230V/1Ph/60Hz 265V/1PH/60Hz.
Johnson Controls 25 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) WIRING DIA GRAM 3 PHASE RS* UNITS: 208-230V/3Ph/60Hz 460V/3Ph/60Hz 575V/3Ph/60Hz.
26 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps NO TES.
Johnson Controls 27 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) NO TES.
Printed on recycled paper T echnical Guide: YK145.00-EG4 (309) Supersedes: Nothing © 2008 Johnson Controls, Inc. P .O. Box 423, Milwaukee, WI 53201 Printed in USA www .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York YK145.00-EG4 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York YK145.00-EG4 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York YK145.00-EG4 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York YK145.00-EG4 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York YK145.00-EG4, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York YK145.00-EG4.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York YK145.00-EG4. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York YK145.00-EG4 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.