246819-BTG-H-0208 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SPLIT - SYSTEM HEA T PUMPS 13 SEER – R-22 MODELS: E*BD-F018 THRU 060 (1.5 THRU 5 NOMINAL T ONS, 1 PHASE) E*BD-(T ,W)036 THRU 060 (2.5 THRU 5 NOMINAL T ONS, 3 PHASE) Due to continuo us product imp rovement, speci fications are subject to chan ge without notice.
246819-BTG-H-0208 2 Unitary Products Group All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request.
246819-BTG-H-0208 Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Matched Syste ms - 1 Phase Outdoor Unit EABD-F018S EABD-F024S EABD-F030S EAB D-F036S EABD-F042S EABD-F048S.
246819-BTG-H-0208 4 Unitary Products Group * This loose coil match does not achieve 13 SEER. PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the condenser , the smallest evaporator and 15 feet of inter- connecting line tubing.
246819-BTG-H-0208 Unitary Products Group 5 All dimensions are in inche s. Th ey are su bject to change with- out notice. Certified dimensions will be pro vided upon request.
246819-BTG-H-0208 6 Unitary Products Group PROCEDURES: 1. U nit factory charge listed on the unit nameplate includes refr igerant for the condenser , the smallest evaporator and 15 feet of inter-con- necting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using th e above table.
246819-BTG-H-0208 Unitary Products Group 7 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 1 & 3 PH 13 SEER HP WITH MA EABD-F018S MA08B 17 FC/MC18B 600 18 .0 12.
246819-BTG-H-0208 8 Unitary Products Group — = Not Applicable. Go to www.ari. org/aridirectory for the latest additiona l matches. 1 PH 13 SEER AC WITH A V / SV - V ARIABLE SPEED EABD-F018S A V24 17 – 600 18.0 12.6 14.00 12.00 EABD-F024S A V24 17 – 800 23.
246819-BTG-H-0208 Unitary Products Group 9 COOLING CAP ACITY - Upflow , Downflow , and Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. EABD-F018S 450 750 14,17 FC/MC/PC/UC18 600 18.
246819-BTG-H-0208 10 Unitary Products Group COOLING CAP ACITY - With V ariable S peed Furnac es UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 EABD-F018S (F ,L)L8V A12 FC/MC/PC18A 14 600 18.
246819-BTG-H-0208 Unitary Products Group 11 EABD-F048S FL9(C,V)D20 FC/MC/PC60D 24 1600 46.0 35 .5 13.25 1 1.00 (F ,L)L8VC16 FC/PC60C 21 1500 45.5 35.1 13 .25 1 1.00 (F ,L)L8VC20 FC/PC60C 21 1600 46.0 35.4 13 .25 1 1.00 FL9(C,V)C16 FC/PC60C 21 1600 46.
246819-BTG-H-0208 12 Unitary Products Group HEA TING PERFORMANCE - With Air Handler UNIT MODEL* AIR HANDLER COIL 1 MODEL ARI HEA T ING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD 1 & 3 PH 13 SEER HP WITH MA EABD-F018S MA08B FC/MC18B 18.0 3.
246819-BTG-H-0208 Unitary Products Group 13 CP equals MBH output divided by (t otal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating ou tput during a normal annual usage period for heating divided by the total electric power input during the same period.
246819-BTG-H-0208 14 Unitary Products Group CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period.
246819-BTG-H-0208 Unitary Products Group 15 HEA TING CAP ACITY - W ith V ariable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE COIL 1 MODEL ARI HEA T ING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD EABD-F018S (F ,L)L8V A12 FC/MC/PC18A 17.5 3.
246819-BTG-H-0208 16 Unitary Products Group CP equals MBH output divided by (to tal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period.
246819-BTG-H-0208 Unitary Products Group 17 ACCESSORIES Refer to Price Manual for specific model numbers. St art Assist Kit (2SA067*) Blower Time Delay - A vailable to increase efficiency when installed. Installs on indoor section and maintains blower for approximately one minute a fter cooling thermostat has been satisfied.
246819-BTG-H-0208 18 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 Unitary Products Group 19 Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 20 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 Unitary Products Group 21 Multipliers for determining th e performance with other indoor sections NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sen.
246819-BTG-H-0208 22 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 Unitary Products Group 23 Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 24 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 Unitary Products Group 25 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO EABD-F018S EV APORA T OR COIL MODEL NO FC /MC/PC/UC18 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
246819-BTG-H-0208 26 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO EABD-F024S EV APORA T OR COIL MODEL NO FC /MC/PC/UC24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
246819-BTG-H-0208 Unitary Products Group 27 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F030S, EABD-(T ,W)030S** EV APORA T OR COIL MODEL NO FC /MC/PC35 AIR TEMP .
246819-BTG-H-0208 28 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E ABD-F036S, EABD-(T ,W)036S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC48 AIR TEMP .
246819-BTG-H-0208 Unitary Products Group 29 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F042S, EABD-(T ,W)042S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC48 AIR TEMP .
246819-BTG-H-0208 30 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E ABD-F048S, EABD-(T ,W)048S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC60 AIR TEMP .
246819-BTG-H-0208 Unitary Products Group 31 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F060S, EABD-(T ,W)060S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC60 AIR TEMP .
Subject to change without notice. Printed in U.S.A. 246819-BTG-H-0208 Copyright © by Unitary Products Group. 2008. Al l rights reserved. Supersedes: 246819-BTG-G-0607 Unitary 5005 Norman Product Y or.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York W)036 THRU 060 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York W)036 THRU 060 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York W)036 THRU 060 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York W)036 THRU 060 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York W)036 THRU 060, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York W)036 THRU 060.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York W)036 THRU 060. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York W)036 THRU 060 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.