TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 13 SEER – R-410A MODELS: THGD18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice. V isit us on th e web at www .york.com A dditional rating informa tion can be fo und at w ww .
397763-YTG-B-0508 2 Johnson Controls Unitary Products All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request.
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 3 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the condenser, the smallest evaporator and 15 feet of interconnect- ing line tubing.
397763-YTG-B-0508 4 Johnson Controls Unitary Products COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 13 SEER HP WITH MA THGD18S41S1 MA08B 17 FC/MC/PC18B 600 17.0 12 .
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 5 — = Not applicable. 13 SEER HP WITH A V / SV / F*FV - V ARIABLE SPEED THGD18S41S1 A V24 17 – 550 17.0 13.0 14.00 12.00 THGD24S41S1 A V24 17 – 750 23.0 17.2 14.00 12.00 A V36 21 – 750 23.0 18.
397763-YTG-B-0508 6 Johnson Controls Unitary Products COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. THGD18S41S1 450 - 750 14,17 FC/MC/PC18 600 17.
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 7 COOLING CAP ACITY - W ith V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SENS. 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 THGD18S41S1 PV8*A12 F C/MC/PC18A 14 600 17.
397763-YTG-B-0508 8 Johnson Controls Unitary Products THGD30S41S1 PV8*C16 HC42C 21 1000 29.0 24.0 14 .00 12.00 PV8*C20 HC42C 21 1 100 29.0 25.6 14.00 12.00 P(C,V)9*C16 HC42C 21 1000 29.0 23.8 14.00 12.00 P(C,V)9*C20 HC42C 21 1050 29.0 23.8 14.00 12.00 PV8*C16 HD48C 21 1000 29.
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 9 THGD48S41S1 PV8*C16 FC/MC /PC48C 21 1500 46.5 34.2 13.00 1 1.00 PV8*C20 FC/MC /PC48C 21 1600 47.0 35.4 13.00 1 1.50 P(C,V)9*C16 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C20 FC/MC/PC48C 21 1600 47.
397763-YTG-B-0508 10 Johnson Controls Unitary Products HEA TING PERFORMANCE - With Air Handler UNIT MODEL* AIR HANDLER COIL 1 MODEL ARI HEA TING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD 13 SEER HP WITH MA THGD18S41S1 MA08B FC/MC18B 17.0 3.32 1.
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 11 CP equals MBH output divided by (t otal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating ou tput during a normal annual usage period for heating divided by the total electric power input during the same period.
397763-YTG-B-0508 12 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period.
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 13 HEA TING CAP ACITY - With V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE COIL 1 MODEL ARI HEA TING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD 13 SEER HP WITH V ARIABLE SPEED FURNACES 3 THGD18S41S1 PV8*A12 FC/MC/PC18A 16.
397763-YTG-B-0508 14 Johnson Controls Unitary Products THGD30S41S1 PV8*C20 HC42C 28.0 3.68 2.23 16.2 2. 50 1.90 8.00 P(C,V)9*C16 HC42C 27.8 3.58 2.28 16 .2 2.46 1.93 8.00 P(C,V)9*C20 HC42C 27.8 3.58 2.28 16 .2 2.46 1.93 8.00 PV8*C16 HD48C 28.0 3.68 2.
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 15 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating ou tput during a normal annual usage period for heating divided by the total electric power input during the same period.
397763-YTG-B-0508 16 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. St art Assist Kit (2SA067*) - May be required on 42, 48, 60 models. Models 18, 24 , 30, 36 ha ve been factory installed. Blower Time Delay - A vailable to increase efficiency whe n installed.
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between.
397763-YTG-B-0508 18 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween.
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 19 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between.
397763-YTG-B-0508 20 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween.
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 21 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between.
397763-YTG-B-0508 22 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween.
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 23 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between.
397763-YTG-B-0508 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD1 8S41S1 EV APORA TOR COIL MODEL NO AHP18 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 25 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD2 4S41S1 EV APORA TOR COIL MODEL NO AHP24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
397763-YTG-B-0508 26 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD3 0S41S1 EV APORA TOR COIL MODEL NO AHP36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 27 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD3 6S41S1 EV APORA TOR COIL MODEL NO AHP36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
397763-YTG-B-0508 28 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD4 2S41S1 EV APORA TOR COIL MODEL NO FC/MC/PC/UC48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
397763-YTG-B-0508 Johnson Controls Unitary Produ cts 29 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD4 8S41S1 EV APORA TOR COIL MODEL NO AHP/SHP48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
Subject to change without notice. Printe d in U.S.A. 397763-YTG-B-0508 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 397763-YTG-A-0408 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York THGD18 THRU 60 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York THGD18 THRU 60 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York THGD18 THRU 60 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York THGD18 THRU 60 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York THGD18 THRU 60, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York THGD18 THRU 60.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York THGD18 THRU 60. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York THGD18 THRU 60 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.