TECHNICAL GUIDE HORIZONT AL DISCHARGE AIR CONDITIONERS 13 SEER – R-410A MODELS: TCHD18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous pr oduct improvemen t, specifications are subject to change withou t notice. Visit us on the web at www .
556454-YTG-A-0210 2 Johnson Controls Unitary Products All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 3 System Charge for V arious Matched Systems Out door Unit TCHD18S41S3 TCHD24S41S3 T CHD30S41S3 TCHD36S41S3 TCHD4 8S41S3 TCHD60S41S3 Required Ori f.
556454-YTG-A-0210 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tubing. 2. V erify the TXV and additional charge re quir ed for specific evaporator coil in the system using the above table.
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT A L SEN S. 13 SEER AC WITH MV - V ARIABLE SPEED TCHD18S41S3 MV12B 17 FC/MC18B 600 18.
556454-YTG-A-0210 6 Johnson Controls Unitary Products — = Not applicable. 13 SEER AC WITH AHP / SHP / AHX / F*FP TCHD18S41S3 AHX18 17 – 630 18.2 13.1 14.25 1 1.75 AHX24 17 – 590 18.3 13.0 14.25 1 1.75 AHX30 17 – 610 18.6 13.3 14.50 12.00 F6FP018 17 – 600 17.
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 7 COOLING CAP ACITY - Upflow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT A L SEN S. TCHD18S41S3 450 - 750 14,17 FC/MC/PC24 600 18.
556454-YTG-A-0210 8 Johnson Controls Unitary Products COOLING CAP ACITY - With High Efficiency Motor Furnaces UNIT MODEL FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SENS. 13 SEER AC WITH V ARIABLE SPEED FURNACES 2 TCHD18S41S3 T*(8,L)X*A12 FC/MC/PC18A 14 540 17.
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 9 TCHD18S41S3 Y*9C*B12 HD36 17 635 18.5 12.9 14.75 12.35 Y*9C*C16 HD36 21 595 18.6 12.9 15.00 12.50 Y*(8,L)C*A12 UC18A 14 620 18.2 13.1 14.55 12.10 Y*(8,L)C*B12 UC18B 17 580 18.0 12.7 14.50 12.15 Y*9C*B12 UC18B 17 610 18.
556454-YTG-A-0210 10 Johnson Controls Unitary Products TCHD24S41S3 T*9X*B12 HD36 17 790 23.0 17.0 14.00 1 1.75 T*(8,L)X*A12 UC24A 14 785 23.6 17.3 14.50 12 .00 T*(8,L)X*B12 UC24B 17 835 23.6 17.6 14.75 12 .00 T*9X*B12 UC24B 17 775 23.6 17.3 14.50 12.00 T*(8,L)X*A12 UC30A 14 785 23.
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 11 TCHD24S41S3 Y*(8,L)C*A12 HC30 14 775 23.4 17.2 14.10 12.00 Y*(8,L)C*B12 HC36 17 760 23.6 17.1 14.50 12.20 Y*9C*B12 HC36 17 815 23.8 17.6 14.35 12.15 Y*(8,L)C*C16 HC42 21 895 24.4 18.9 14.90 12.60 Y*(8,L)C*C20 HC42 21 760 24.
556454-YTG-A-0210 12 Johnson Controls Unitary Products TCHD30S41S3 T*(8,L)X*B12 FC/MC/PC43B 17 1 1 15 28.8 21.6 14.25 12 .25 T*(8,L)X*C20 FC/MC/PC43C 21 870 26.4 21.3 14.50 12 .50 T*9X*B12 FC/MC/PC43B 17 1095 28.8 21.6 14.25 12.25 T*9X*C16 FC/MC/PC43C 21 1055 28.
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 13 TCHD30S41S3 Y*(8,L)C*C16 HC42 21 990 29.0 21.8 15.35 13.60 Y*(8,L)C*C20 HC42 21 1000 29.0 21.8 15.40 13.65 Y*9C*C16 HC42 21 1030 28.8 21.8 14.80 13.15 Y*9C*C20 HC42 21 995 29.0 21.8 15.20 13.45 Y*(8,L)C*A12 HD36 14 1000 28.
556454-YTG-A-0210 14 Johnson Controls Unitary Products TCHD36S41S3 T*9X*D20 FC/MC/PC48D 24 1240 34.8 25.7 14.75 12.50 T*(8,L)X*A12 HD36 14 1270 33.2 24.2 13.40 1 1.75 T*(8,L)X*B12 HD36 17 1270 33.2 24.2 13.70 1 1.75 T*9X*B12 HD36 17 1270 33.4 24.4 13.
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 15 TCHD36S41S3 Y*(8,L)C*B12 HC36 17 1220 33.4 24.4 13.55 1 1.80 Y*9C*B12 HC36 17 1 190 33.2 24.0 13.60 1 1.75 Y*(8,L)C*C16 HC42 21 1205 34.6 25.4 14.75 12.75 Y*(8,L)C*C20 HC42 21 1 1 90 34.6 25.6 15.
556454-YTG-A-0210 16 Johnson Controls Unitary Products TCHD48S41S3 T*9X*D20 HD48 24 1645 48.0 33.9 13.35 12 .00 T*(8,L)X*C16 UC48C 21 1640 45.5 32.8 13.00 1 1.00 T*(8,L)X*C20 UC48C 21 1515 45.0 31.6 13.05 1 1.50 T*9X*C16 UC48C 21 1565 45.0 32.8 13.00 1 1.
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 17 ACCESSORIES Refer to Price Manua l for specific model numbers. Hard St art Kit - Require d when using TXV indoor coil. Also, provides increased starting torque for areas with low voltage. Off Cycle Timer Delay - Provides a 5-minu te off cycle to pre- vent rapid recycling of the compressor .
556454-YTG-A-0210 18 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 19 Furnaces Co ils T .C. S.C. KW T*(8,L)X*A12 FC/MC/PC18A 0.98 0.98 0.94 T*(8,L)X*B12 FC/MC/PC18B 0.99 1.00 0.93 T*9X*B12 FC/MC/PC18B 0.99 1.02 0.93 T*(8,L)X*A12 FC/MC/PC24A 1.03 1.05 0.94 T*(8,L)X*B12 FC/MC/PC24B 1.
556454-YTG-A-0210 20 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 21 Furnaces Co ils T .C. S.C. KW T*(8,L)X*A12 FC/MC/PC24A 1.02 1.03 0.95 T*(8,L)X*B12 FC/MC/PC24B 1.03 1.05 0.94 T*9X*B12 FC/MC/PC24B 1.02 1.03 0.95 T*(8,L)X*A12 FC/MC/PC30A 1.02 1.02 0.95 T*(8,L)X*B12 FC/MC/PC30B 1.
556454-YTG-A-0210 22 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 23 Furnaces Co ils T .C. S.C. KW T*(8,L)X*A12 FC/MC/PC30A 1.01 1.02 0.97 T*(8,L)X*B12 FC/MC/PC30B 0.99 0.98 0.93 T*9X*B12 FC/MC/PC30B 1.01 1.02 0.97 T*(8,L)X*A12 FC/MC/PC32A 1.00 1.00 0.98 T*(8,L)X*B12 FC/MC/PC35B 1.
556454-YTG-A-0210 24 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 25 Furnaces Coils T .C. S.C. KW T*(8,L)X*A12 F C/MC/PC32A 0.96 0.95 0.98 T*(8,L)X*B12 F C/MC/PC35B 0.98 1.00 0.98 T*(8,L)X*C16 FC/MC/PC35 C 0.99 0.98 0.95 T*(8,L)X*C20 FC/MC/PC35 C 0.99 1.00 0.95 T*9X*B12 FC/MC/PC35B 0.
556454-YTG-A-0210 26 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 27 Furnaces Co ils T .C. S.C. KW T*(8,L)X*C16 FC/MC/PC48C 1.00 1.01 1.00 T*(8,L)X*C20 FC/MC/PC48C 1.01 1.02 0.99 T*9X*C16 FC /MC/PC48C 1.00 0.99 1. 00 T*9X*C20 FC /MC/PC48C 1.00 1.01 1. 00 T*9X*D20 FC /MC/PC48D 1.
Subject to change without notice. Published in U .S.A. 556454-YTG-A-0210 Copyright © 2010 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the p erfo rman ce with other indoor sections.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York TCHD18 THRU 60 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York TCHD18 THRU 60 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York TCHD18 THRU 60 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York TCHD18 THRU 60 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York TCHD18 THRU 60, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York TCHD18 THRU 60.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York TCHD18 THRU 60. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York TCHD18 THRU 60 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.