Manuale d’uso / di manutenzione del prodotto SUNLINE 2000 2000 del fabbricante York
Vai alla pagina of 24
DESCRIPTION YORK Sunline 2000 Heat Pumps are convertible single package units with a common cabinet and common roof curb for the 3, 4 and 5 ton sizes. The units were designed for residential and light commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.
SYSTEM PROTECTION -- Crankcase heaters and internal compressor protection are standard on all compressors. Every unit has a liquid line filter--drier , low pressure switch, high pressure switch and high temperature switch to protect all system components.
036-21564-003-A-1005 Unitary Products Group 3 MODELS BCH 036 048 060 SUPPL Y AIR BLOWER CENTRIFUGAL BLOWER (Dia. x Wd. in.) 12 x 10 12 x 10 12 x 10 F AN MOTOR HP (DIRECT -DRIVE) 1 2 3 4 1 F AN MOTOR HP (BEL T -DRIVE) 1.5 1.5 1.5 INDOOR COIL ROWS DEEP 4 3 3 FINS PER INCH 16 15 15 F ACE AREA (Sq.
036-21564-003-A-1005 4 Unitary Products Group COOLING CAP ACITIES - 3 TON (BCH036) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap.
036-21564-003-A-1005 Unitary Products Group 5 COOLING CAP ACITIES - 4 TON (BCH048) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap.
036-21564-003-A-1005 6 Unitary Products Group COOLING CAP ACITIES - 5 TON (BCH060) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap.
036-21564-003-A-1005 Unitary Products Group 7 HEA TING CAP ACITIES BCH036 CFM RET . AIR CAP OUTDOOR AIR TEMPERATURE, ° F (72% RH) ° F & K W - 1 0 0 1 02 03 04 05 06 0 1750 55 MBH 13.1 16.4 23.5 29.1 30.2 41.7 47.0 48.2 KW 2.9 3.0 3.2 3.3 3.5 3.7 3.
036-21564-003-A-1005 8 Unitary Products Group SUPPL Y AIR BLOWER PERFORMANCE - BCH036 & 048 with Belt-Drive MODEL BCH AIR FLOW CFM Available External S tatic Pressure - IWG* 0.
036-21564-003-A-1005 Unitary Products Group 9 SUPPL Y AIR BLOWER PERFORMANCE - BCH036, 048 & 060 with Direct-Drive SUPPL Y AIR BLOWER PERFORMANCE - BCH060 with Belt-Drive MODEL BCH AIR FLOW CFM Available External S tatic Pressure - IWG* 0.20 0.30 0.
036-21564-003-A-1005 10 Unitary Products Group HEA TER / CFM LIMIT ATIONS HEA TER SIZE NOM. KW VOL TAGE 1 UNIT MODEL SIZE, NOMINAL TONS 345 MINIMUM SUPPL Y AIR CFM 5 7 10 15 20 30 208 / 230-1-60 1,100.
036-21564-003-A-1005 Unitary Products Group 11 ELECTRICAL DA T A - Basic Unit (Direct-Drive) MODEL BCH POWER SUP - PL Y VOL TAGE LIMIT ATIONS (SEE NOTE 1) COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, (SEE NOTE 2) AMPS MAX.
036-21564-003-A-1005 12 Unitary Products Group MODEL BCH POWER SUPPL Y HEA TER ACCESSORY MODEL NUMBER SUPPL Y AIR BLOWER MOTOR FLA ELECTRIC HEA TERS MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE 1 AMPS MAX. SIZE HACR 2 BREAKER AMPS KW ST AGES TO T A L AMPS 048 208-1-60 2CE04510506 2CE04510706 2CE0451 1006 2CE0451 1506 2CE04512006 5.
036-21564-003-A-1005 Unitary Products Group 13 ELECTRICAL DA T A - Basic Unit (Belt-Drive) MODEL BCH POWER SUP - PL Y VOL TAGE LIMIT ATIONS (SEE NOTE 1) COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, (SEE NOTE 2) AMPS MAX.
036-21564-003-A-1005 14 Unitary Products Group MODEL BCH POWER SUPPL Y HEA TER ACCESSORY MODEL NUMBER SUPPL Y AIR BLOWER MOTOR FLA ELECTRIC HEA TERS MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE 1 AMPS MAX. SIZE HACR 2 BREAKER AMPS KW ST AGES TO T A L AMPS 048 208-1-60 2CE04510506 2CE04510706 2CE0451 1006 2CE0451 1506 2CE04512006 8.
036-21564-003-A-1005 Unitary Products Group 15 CLEARANCES Front 24" Back 12" (Less Economizer) 36" (With Economizer or Fixed Air/Motorized Air Damper) Left Side (Filter Access) 24".
036-21564-003-A-1005 16 Unitary Products Group UNIT DIMENSIONS - CONT'D. ( B C H-3 ,4&5T O N ) REAR VIEW SIDE SUPPL Y AND RETURN AIR DUCT OPENINGS 17 1 2 3 11 1 2 4 5 8 17 1 2 11 1 2 7 7 8 6 1 2 DUCT COVERS - Units are shipped with all air duct openings covered.
036-21564-003-A-1005 Unitary Products Group 17 ROOF CURB DIMENSIONS B C H-3 ,4&5T O N COMPRESSOR AND OUTDOOR COIL END OF UNIT DUCT SIZES: Supply Air = 19" x 19" Return Air = 19" x 1.
FIELD--INST ALLED ACCESSORIES SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER -- Includes a slide--in/plug--in damper assembly with fully modulating spring return motor actuator capable of introducing up to 100% outdoor air , one outdoor air electronic enthalpy sensor and a rainhood with filters.
036-21564-003-A-1005 Unitary Products Group 19 TYPICAL APPLICATIONS TYPICAL ROOF-TOP INST ALLA TION ROOF JACK INST ALLA TION ROOF CURB INST ALLA TION SLAB ON GROUND INST ALLA TION FIELD-SUPPLIED DISCO.
GENERAL DESCRIPTION Units shall be factory--assembled, single packaged Heat Pumps, designed for outdoor mounted inst allation. Units shall have minimum SEER ratings of 10.
(1) -- Loss--of--charge/Low--pressure switch. (2) -- High--pressure switch. If any of the above safety devices trip, an LED (light emitting diode) indicator shall illuminate. C. Unit shall incorporate “AUTO RESET” compressor over--temperature, over--current protection.
6. THERMOST A TS -- Multiple models available from A.C.O., M.C.O., Electronic or Electrical Mechanical ver - sions. 7. ANTI--RECYCLE TIMER -- Assures 5--minute off--time between compressor cycles. 8. ELECTRIC HEA T -- Slide--in design, provides single point power and ranges from 5 to 30 KW .
036-21564-003-A-1005 Unitary Products Group 23.
8QLWDU3URGXFWV*URXS < RUN'ULYH1RUPDQ2. 6XEMHFWWRFKDQJHZLWKRXWQRWLFH3ULQWHGLQ86$ &RSULJKW.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York SUNLINE 2000 2000 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York SUNLINE 2000 2000 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York SUNLINE 2000 2000 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York SUNLINE 2000 2000 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York SUNLINE 2000 2000, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York SUNLINE 2000 2000.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York SUNLINE 2000 2000. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York SUNLINE 2000 2000 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.