TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 14.5 SEER – R-410A MODELS: YHJF18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous prod uct improvemen t, specifications are subject to chan ge without notice. Vi si t us on the web at ww w .york.
510667-YTG-B-0509 2 Johnson Controls Unitary Products All dimensions are in inche s. They are su bject to change with- out notice. Certified dimensions will be provi ded upon request.
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the u nit nameplate includes re friger ant for the condenser, the smallest evaporator and 15 feet of interconnecting line tub ing. 2. V erify the TXV and additional charge required for specific evaporator coil in the system u sing the above table.
510667-YTG-B-0509 4 Johnson Controls Unitary Products — = Not applicable. COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 ST AGE COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 14.5 SEER HP WITH MV - V ARIABLE SPEED YHJF18S41S1 MV12B 17 FC/MC35B – 600 18.
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With High Efficiency Motor Furnaces UNIT MODEL FURNACE MODEL COIL MODEL 1 WS T A G E COOLING RA TED CFM Net MBH SEER EER TOT AL SENS. 14.5 SEER HP WITH V ARIABLE SPEED FURNACES 2 YHJF18S41S1 T*(8,L)X*A12 FC/MC/PC32A 14 – 590 18.
510667-YTG-B-0509 6 Johnson Controls Unitary Products YHJF36S41S1 T*(8,L)X*A12 FC/MC/PC37A 14 – 1290 35.8 27.4 14.50 12.00 T*(8,L)X*B12 FC/MC/PC43B 17 – 1300 35.8 27.4 14.50 12.00 T*(8,L)X*C16 FC/MC/PC43C 21 – 1 175 35.4 26.4 15.00 12.50 T*(8,L)X*C20 FC/MC/PC43C 21 – 1250 36.
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 7 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period.
510667-YTG-B-0509 8 Johnson Controls Unitary Products HEA TING CAP ACIT Y - With High Efficiency Motor Fu rnaces MODEL FURNACE MODEL COIL 1 MODEL ARI HEA TING 2 47 F1 7 FH S P F MBH COP KW MBH COP KW STD 14.5 SEER HP WITH V ARIABLE SPEED FUR NACES 3 YHJF18S41S1 T*(8,L)X*A12 FC/MC/PC32A 17.
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 9 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period.
510667-YTG-B-0509 10 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period.
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 11 SOUND LEVEL - TYPICAL OCT A VE BAND SPE CTRUM (without tone adjustment) * Rated in accordance with ARI 270-200 8 S tandards. TYPICAL INST ALLA TION TYPICAL FIELD WIRING Size T est Condition 63 125 250 500 1000 2000 4000 8000 dBA SQI RSS Sound Power Calibration 1091 402 82.
510667-YTG-B-0509 12 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 13 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
510667-YTG-B-0509 14 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 15 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
510667-YTG-B-0509 16 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
510667-YTG-B-0509 18 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 19 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
510667-YTG-B-0509 20 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF18S41S1 EV APORA TOR COIL MODEL NO AHX30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 21 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF24S41S1 EV APORA TOR COIL MODEL NO AHX30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
510667-YTG-B-0509 22 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF30S41S1 EV APORA TOR COIL MODEL NO AHX36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 23 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF36S41S1 EV APORA TOR COIL MODEL NO AHX36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
510667-YTG-B-0509 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF42S41S1 EV APORA TOR COIL MODEL NO AHX60 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 25 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF48S41S1 EV APORA TOR COIL MODEL NO F6FP060 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
Subject to change without notice. Publishe d in U.S.A. 510667-YTG-B-0509 Copyright © 2009 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 510667-YTG-A-0409 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York SPLIT-SYSTEM YHJF18 THRU 60 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York SPLIT-SYSTEM YHJF18 THRU 60 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York SPLIT-SYSTEM YHJF18 THRU 60 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York SPLIT-SYSTEM YHJF18 THRU 60 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York SPLIT-SYSTEM YHJF18 THRU 60, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York SPLIT-SYSTEM YHJF18 THRU 60.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York SPLIT-SYSTEM YHJF18 THRU 60. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York SPLIT-SYSTEM YHJF18 THRU 60 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.