® FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 528150-YTG-G-12 10 TECHNICAL GUIDE Description ASHRAE 90.1 COMPLIANT YORK ® Predator ® units are convertible single packages with a common footprint cabinet and common roof curb for all 3 through 12-1/2 ton mode ls.
528150-YTG-G-1210 2 Johnson Controls Unitary Products Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
528150-YTG-G-1210 Johnson Controls Unitary Products 3 Cooling With Gas Heat (6 1/2 Throug h 10 Tons) Roof curbs in eight- and fourteen-inch heights. Roof curbs for transitioning from Y ork Sunline™ .
528150-YTG-G-1210 4 Johnson Controls Unitary Products Nomenclature Z H 090 N10 A 2 A AA 5 0 1 2 4 A Product Category Z = A/C, Single Pkg., R-410A A = Std. Motor Airflow B = Std. Motor/Econo./Barometric Relief (Downflow Only) C = Std. Motor/Econo./Power Exhaust (D ownflow Only) D = Std.
528150-YTG-G-1210 Johnson Controls Unitary Products 5 Features and Benefits Standard Features • High Efficiency – High efficiency un its reach as high as 12.2 EER. Gas/electric units ha ve electroni c spark ignition and power vented combustion with steady state efficiencies of 80%.
528150-YTG-G-1210 6 Johnson Controls Unitary Products board will alarm on igniti on failures, compressor lock - outs and repeated limit switch trip s. • Nuisance T rip Protection and Strikes - T o prevent nuisance trouble calls, the co ntrol board uses a “three times, you’re out” philosophy .
528150-YTG-G-1210 Johnson Controls Unitary Products 7 actuators have an adjustable auxiliary end -switch for optional power exhaust con trol. • VAV or Simplicity® Intelli-Comfo rt™ control, a factory-installed dry bulb se nsor determines if o utdoor air temperature is lo w enough to provide free-cooling operation.
528150-YTG-G-1210 8 Johnson Controls Unitary Products • Phase Monitors - Designed to pre vent un it damage. The phase monitor will shut the unit down in an out-o f phase condition. (Standard on units with Scroll Compressors.) • Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil fro m damage.
528150-YTG-G-1210 Johnson Controls Unitary Products 9 • Slab Economizer for Energy Rec overy Ventilator - (Without barometric relief or Fresh Air Hood) - The economize r is provided with a single enthalpy inp ut. The economizer is 2% low leakage type.
528150-YTG-G-1210 10 Johnson Controls Unitary Products Accessories Field Installed Acessories - Non-Electric al MODEL VOLTAGE DESCRIPTION WHERE USED 1BD0408 All Burglar Bars, Downflow All Cabinets 1CG.
528150-YTG-G-1210 Johnson Controls Unitary Products 11 Field Installed Acessories - Electric Heat MODEL VOLTAGE DESCRIPTION WHERE USED 2TP04520925 230 9kW Electric Heat All 50" C abinet 6.5 and 8.5 Ton Models 2TP04520946 460 2TP04520958 575 2TP04531825 230 18kW Electric Heat All 50" Cabinet 6.
528150-YTG-G-1210 12 Johnson Controls Unitary Products Guide Specifications GENERAL Units shall be manufactured by Unitary Products in an ISO 9001 certified facility. YORK® Predator ® units are convertible single packages with a common footprint cabinet and common roof curb for all 3 through 12- 1/2 ton models.
528150-YTG-G-1210 Johnson Controls Unitary Products 13 factory wired, piped and charge d with R-410A refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. Th e cooling performance shall be rated in accordance with DOE and ARI test procedu res.
528150-YTG-G-1210 14 Johnson Controls Unitary Products g. Control board shall monitor eac h refrigerant safety switch independently. h. Control board shall retain l ast 5 fault codes i n non- volatile memory, which will no t be lost in the event of a power loss.
528150-YTG-G-1210 Johnson Controls Unitary Products 15 • CONVENIENCE OUTLET (P OWERED/NON-POWERED) – Unit can be provided with an op ti onal 120VAC GFCI o utlet with cover on the corner of t he u nit housing the compressors.
528150-YTG-G-1210 16 Johnson Controls Unitary Products Physical Data ZH037-061 Single Stage Gas Physical Data Component Models ZH037 ZH049 ZH061 Nominal Tonnage 3.0 4.0 5.0 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (MBh) 37000 50000 62000 ARI net capacity (MBh) 36000 48000 60000 EER 11.
528150-YTG-G-1210 Johnson Controls Unitary Products 17 CONDENSER FAN DATA Quantity of fans 1 1 1 Fan diameter (Inch) 24 24 24 Type Prop Prop Prop Drive type Direct Direct Direct Quantity of motors 1 1 1 Motor HP each 1/3 1/3 1/3 No.
528150-YTG-G-1210 18 Johnson Controls Unitary Products ZH037-061 Two Stage Gas Physical Data Component Models ZH037 ZH049 ZH061 Nominal Tonnage 3.0 4.0 5.0 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (MBh) 37000 50000 62000 ARI net capacity (MBh) 36000 48000 60000 EER 11.
528150-YTG-G-1210 Johnson Controls Unitary Products 19 1. 1 st Stage Capacity is 75% of Full Capacity . 2. 1 st Stage Capacity is 70% of Full Capacity . 3. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3. 4. 2 In. Pleated, Optional, MERV 7.
528150-YTG-G-1210 20 Johnson Controls Unitary Products ZH078-150 Physical Data Component Models ZH078 ZH090 ZH102 Z H120 ZH150 Nominal Tonnage 6.5 7.5 8.5 10 12.5 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 81000 93000 104000 125000 155000 ARI net capacity (Btu) 78000 90000 102000 120000 150000 EER 11.
528150-YTG-G-1210 Johnson Controls Unitary Products 21 CONDENSER FAN DATA Quantity of fans 2 2 2 2 4 Fan diameter (Inch) 24 24 24 24 24 Type Prop Prop Prop Prop Prop Drive typ e Direct Direct Direct Direct Direct Quantity of motors 2 2 2 2 4 Motor HP each 1/3 3/4 3/4 3/4 1/3 No.
528150-YTG-G-1210 22 Johnson Controls Unitary Products ZJ037-061 Single Stage Gas Heat Ph ysical Data Component Models ZJ037 ZJ049 ZJ061 Nominal Tonnage 3.0 4.0 5.0 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (MBh) 37000 50000 62000 ARI net capacity (MBh) 36000 48000 60000 EER 12.
528150-YTG-G-1210 Johnson Controls Unitary Products 23 CONDENSER FAN DATA Quantity of fans 1 2 2 Fan diameter (Inch) 24 24 24 Type Prop Prop Prop Drive type Direct Direct Direct Quantity of motors 1 2 2 Motor HP each 1/3 1/3 1/3 No.
528150-YTG-G-1210 24 Johnson Controls Unitary Products ZJ037-061 Two Stage Gas Heat Phys ical Data Component Models ZJ037 ZJ049 ZJ061 Nominal Tonnage 3.0 4.0 5.0 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (MBh) 37000 50000 62000 ARI net capacity (MBh) 36000 48000 60000 EER 12.
528150-YTG-G-1210 Johnson Controls Unitary Products 25 1. 1 st Stage Capacity is 75% of Full Capacity . 2. 1 st Stage Capacity is 70% of Full Capacity . 3. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3. 4. 2 In. Pleated, Optional, MERV 7.
528150-YTG-G-1210 26 Johnson Controls Unitary Products ZJ078-150 Physical Data Component Models ZJ078 ZJ090 ZJ102 Z J120 ZJ150 Nominal Tonnage 6.5 7.5 8.5 10 12.5 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 80000 93000 106000 124000 155000 ARI net capacity (Btu) 78000 90000 102000 120000 150000 EER 12.
528150-YTG-G-1210 Johnson Controls Unitary Products 27 CONDENSER FAN DATA Quantity of fans 2 2 2 2 4 Fan diameter (Inch) 24 24 24 24 24 Type Prop Prop Prop Prop Prop Drive typ e Direct Direct Direct Direct Direct Quantity of motors 2 2 2 2 4 Motor HP each 1/3 3/4 3/4 3/4 1/3 No.
528150-YTG-G-1210 28 Johnson Controls Unitary Products ZR037-061 Single Stage Gas Heat Physical Data Component Models ZR037 ZR049 ZR061 Nominal Tonnage 3 4 5 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 36500 49000 62000 ARI net capacity (Btu) 35500 47500 60000 EER 12.
528150-YTG-G-1210 Johnson Controls Unitary Products 29 Component Models ZR037 ZR049 ZR061 Nominal Tonnage 3 4 5 CONDENSER FAN DATA Quantity of fans 1 2 2 Fan diameter (Inch) 24 24 24 Type Prop Prop Prop Drive type Direct Direct Direct Quantity of motors 1 2 2 Motor HP each 1/3 1/3 1/3 No.
528150-YTG-G-1210 30 Johnson Controls Unitary Products ZR037-061 Two Stag e Gas Heat Physical Data Component Models ZR037 ZR049 ZR061 Nominal Tonnag e 3 4 5 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 36500 49000 62000 ARI net capacity (Btu) 35500 47500 60000 EER 12.
528150-YTG-G-1210 Johnson Controls Unitary Products 31 Component Models ZR037 ZR049 ZR061 Nominal Tonnag e 3 4 5 CONDENSER FAN DATA Quantity of fans 1 2 2 Fan diameter (Inch) 24 24 24 Type Prop Prop Prop Drive type Direct Direct Direct Quantity of motors 1 2 2 Motor HP each 1/3 1/3 1/3 No.
528150-YTG-G-1210 32 Johnson Controls Unitary Products ZR078-150 Physical Data Component Models ZR078 ZR090 ZR102 ZR120 ZR150 Nominal Tonnage 6.5 7.5 8.5 10 12.5 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Mbh) 80000 91000 106000 125000 156000 ARI net capacity (Mbh) 78000 88000 102000 120000 150000 EER 11.
528150-YTG-G-1210 Johnson Controls Unitary Products 33 REHEAT COIL DATA Face area (Sq. Ft.) 6.66 6.66 10 10 10 R o w s 22222 Fins per inch 13 13 13 13 13 Tube diameter (in.
528150-YTG-G-1210 34 Johnson Controls Unitary Products ZH/ZJ/ZR078-150 Unit Limitatio ns Size (Tons) Model Unit Voltage Unit Limitations Applied Voltage Outdoor DB Temp Min Max Max (°F) 037 (3) ZH/ZJ.
528150-YTG-G-1210 Johnson Controls Unitary Products 35 Capacity Performance ZH037-150 Cooling Capacities ZH037 (3.0 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (.
528150-YTG-G-1210 36 Johnson Controls Unitary Products 115°F 125°F 750 77 36.4 3.3 13.7 12.3 9.1 - - - 32.6 3.5 12.4 10.7 8.1 - - - 72 31.9 3.2 19.7 16.6 13.4 10.3 - - 28.4 3.4 18.2 15. 2 12.2 9.1 - - 67 27.4 3.1 25.8 20.9 17.7 14.6 11.4 - 24.1 3.4 24.
528150-YTG-G-1210 Johnson Controls Unitary Products 37 ZH049 (4.0 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) T.
528150-YTG-G-1210 38 Johnson Controls Unitary Products 115°F 125°F 1000 77 46.0 4.3 16.4 14.3 10.4 - - - 41.4 4.7 13.7 12.1 8.7 - - - 72 40.8 4.2 24.6 20.6 16.7 12.7 - - 36.3 4.5 22.4 18. 6 14.8 11.0 - - 67 35.6 4.1 32.8 26.9 23.0 19.0 15.1 - 31.2 4.
528150-YTG-G-1210 Johnson Controls Unitary Products 39 ZH061 (5.0 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) T.
528150-YTG-G-1210 40 Johnson Controls Unitary Products 115°F 125°F 1250 77 57.6 5.5 21.5 19.6 14.2 - - - 52.1 6.0 20.7 17.0 12. 6 - - - 72 52.0 5.3 33.3 27.9 22.5 17.1 - - 46.8 5.7 31.1 25. 8 20.6 15.3 - - 67 46.5 5.2 45.0 36.1 30.8 25.4 20.0 - 41.5 5.
528150-YTG-G-1210 Johnson Controls Unitary Products 41 ZH078 (6.5 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) T.
528150-YTG-G-1210 42 Johnson Controls Unitary Products 115°F 125°F 1625 77 78.3 7.0 31.2 26.7 19.5 - - - 69.4 7.5 24.9 23.7 17. 5 - - - 72 70.7 6.8 44.7 37.4 30.1 22.9 - - 63.1 7.3 40.9 34. 3 27.8 21.3 - - 67 63.2 6.7 58.1 48.0 40.8 33.5 26.2 - 56.8 7.
528150-YTG-G-1210 Johnson Controls Unitary Products 43 ZH090 (7.5 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) T.
528150-YTG-G-1210 44 Johnson Controls Unitary Products 115°F 125°F 1875 77 96.7 8.4 32.9 30.3 22.4 - - - 89.9 9.0 27.0 24.2 19. 6 - - - 72 86.3 8.2 51.1 43.3 35.4 27.5 - - 79.5 8.8 48.1 40. 3 32.5 24.8 - - 67 75.9 8.0 69.4 56.2 48.4 40.5 32.6 - 69.1 8.
528150-YTG-G-1210 Johnson Controls Unitary Products 45 ZH102 (8.5 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) T.
528150-YTG-G-1210 46 Johnson Controls Unitary Products 115°F 125°F 2125 77 101.7 9.7 38.8 35.0 25.9 - - - 91.0 10.3 34.9 30.1 22.7 - - - 72 92.3 9.4 58.1 49.0 39.9 30.8 - - 82.4 10.0 54.4 45.4 36.5 27 .5 - - 67 82.9 9.1 77.4 63.0 53.9 44.8 35.7 - 73.
528150-YTG-G-1210 Johnson Controls Unitary Products 47 ZH120 (10 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) To.
528150-YTG-G-1210 48 Johnson Controls Unitary Products 115°F 125°F 2500 77 118.1 11.1 48.5 41.2 30.6 - - - 106.7 12.3 43.2 38.1 27.7 - - - 72 110.4 11.1 69.4 58.8 48.3 37.8 - - 100.8 12.2 65.9 55.6 45.2 34.8 - - 67 102.7 11.1 90.2 76.5 66.0 55.5 44.
528150-YTG-G-1210 Johnson Controls Unitary Products 49 ZH150 (12.5 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) .
528150-YTG-G-1210 50 Johnson Controls Unitary Products 115°F 125°F 3125 77 158.4 14.6 65.6 53.5 40.6 - - - 147.6 16.1 60.0 50.8 38.1 - - - 72 144.6 14.5 88.2 75.4 62.5 49.6 - - 134.2 16.0 84.9 72.2 59.5 46.8 - - 67 130.9 14.3 110.9 97.3 84.4 71.5 58 .
528150-YTG-G-1210 Johnson Controls Unitary Products 51 ZJ037-150 Cooling Capa cities ZJ037 (3.0 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW.
528150-YTG-G-1210 52 Johnson Controls Unitary Products 115°F 125°F 750 77 32.6 3.1 11.2 9.9 7.0 - - - 28.3 3.3 9.2 7.9 5.4 - - - 72 29.2 3.0 17.7 14.8 11.8 8.9 - - 25.6 3.2 16.0 13.2 10.3 7.5 - - 67 25.9 2.9 24.2 19.6 16.6 13.7 10.8 - 22.9 3.1 22.9 18.
528150-YTG-G-1210 Johnson Controls Unitary Products 53 ZJ049 (4.0 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) T.
528150-YTG-G-1210 54 Johnson Controls Unitary Products 115°F 125°F 1000 77 45.6 4.3 17.0 15.2 10.8 - - - 40.4 4.7 17.9 11.7 9.0 - - - 72 40.1 4.2 25.9 21.5 17.1 12.8 - - 35.0 4.6 23.8 19. 5 15.2 10.9 - - 67 34.7 4.1 34.7 27.8 23.4 19.1 14.7 - 29.7 4.
528150-YTG-G-1210 Johnson Controls Unitary Products 55 ZJ061 (5.0 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) T.
528150-YTG-G-1210 56 Johnson Controls Unitary Products 115°F 125°F 1250 77 58.5 4.9 22.3 20.4 14.9 - - - 53.4 5.3 21.9 17.7 13. 3 - - - 72 52.4 4.8 33.7 28.3 22.8 17.4 - - 47.6 5.2 31.8 26. 4 21.0 15.6 - - 67 46.3 4.7 45.1 36.1 30.7 25.2 19.8 - 41.7 5.
528150-YTG-G-1210 Johnson Controls Unitary Products 57 ZJ078 (6.5 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) T.
528150-YTG-G-1210 58 Johnson Controls Unitary Products 115°F 125°F 1625 77 72.1 6.8 27.6 25.3 18.8 - - - 63.3 7.3 26.5 21.1 16. 1 - - - 72 64.6 6.6 41.6 35.1 28.6 22.1 - - 56.2 7.1 37.8 31. 6 25.4 19.2 - - 67 57.2 6.4 55.6 44.9 38.4 31.9 25.4 - 49.1 6.
528150-YTG-G-1210 Johnson Controls Unitary Products 59 ZJ090 (7.5 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) T.
528150-YTG-G-1210 60 Johnson Controls Unitary Products 115°F 125°F 1875 77 90.4 8.3 33.6 30.2 21.8 - - - 81.7 8.9 32.0 25.5 18. 7 - - - 72 81.1 8.0 51.6 43.1 34.6 26.2 - - 72.9 8.6 48.1 39. 7 31.4 23.0 - - 67 71.9 7.8 69.5 56.0 47.5 39.0 30.6 - 64.1 8.
528150-YTG-G-1210 Johnson Controls Unitary Products 61 ZJ102 (8.5 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) T.
528150-YTG-G-1210 62 Johnson Controls Unitary Products 115°F 125°F 2125 77 97.3 9.0 38.3 35.1 25.1 - - - 86.3 9.7 39.4 29.5 21. 9 - - - 72 87.5 8.7 58.0 48.0 38.1 28.1 - - 77.4 9.4 53.9 44. 1 34.4 24.6 - - 67 77.8 8.5 77.8 61.0 51.1 41.1 31.1 - 68.4 9.
528150-YTG-G-1210 Johnson Controls Unitary Products 63 ZJ120 (10 Ton ) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) T.
528150-YTG-G-1210 64 Johnson Controls Unitary Products 115°F 125°F 2500 77 113.0 11.0 47.0 40.7 30.0 - - - 101.1 12.1 44.1 37.0 26.4 - - - 72 104.5 11.0 69.2 58.5 47.8 37.1 - - 93.6 12.1 65.1 54.5 43.9 33.3 - - 67 96.0 11.0 91.4 76.3 65.6 55.0 44.3 - 86.
528150-YTG-G-1210 Johnson Controls Unitary Products 65 ZJ150 (12.5 Ton) Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) .
528150-YTG-G-1210 66 Johnson Controls Unitary Products 115°F 125°F 3125 77 158.4 14.0 63.3 51.9 38.9 - - - 148.8 15.3 56.6 48.7 35.8 - - - 72 144.4 14.0 86.9 73.8 60.8 47.8 - - 134.6 15.3 82.9 70.0 57.1 44.2 - - 67 130.4 14.0 110.4 95.8 82.7 69.7 56 .
528150-YTG-G-1210 Johnson Controls Unitary Products 67 ZR037-150 Cooling and Reheat Capacities ZR037 (3.0 Ton) Cool in g Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (.
528150-YTG-G-1210 68 Johnson Controls Unitary Products 115°F 125°F 750 77 34.0 2.4 11.6 10.9 8.1 - - - 31.5 2.1 11.5 9.9 7.9 - - - 72 30.0 2.5 18.1 15.3 12.4 9.6 - - 27.2 2.3 17.2 14.5 11.7 9.0 - - 67 26.0 2.6 24.6 19.6 16.8 13.9 11.1 - 22.8 2.6 22.
528150-YTG-G-1210 Johnson Controls Unitary Products 69 ZR037 (3.0 Ton) Reheat Air on Evaporator Coil Temperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (M.
528150-YTG-G-1210 70 Johnson Controls Unitary Products ZR049 (4.0 Ton) Cool in g Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacit.
528150-YTG-G-1210 Johnson Controls Unitary Products 71 115°F 125°F 1000 77 50.4 4.0 17.7 16.3 12.1 - - - 49.5 3.7 16.5 12.8 10. 1 - - - 72 43.0 3.9 26.2 22.0 17.8 13.6 - - 40.5 3.9 24.0 19. 9 15.8 11.7 - - 67 35.6 3.8 34.6 27.7 23.5 19.3 15.2 - 31.5 4.
528150-YTG-G-1210 72 Johnson Controls Unitary Products ZR049 (4.0 Ton) Reheat Air on Evaporator Coil Temperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (M.
528150-YTG-G-1210 Johnson Controls Unitary Products 73 ZR061 (5.0 Ton) Cool in g Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacit.
528150-YTG-G-1210 74 Johnson Controls Unitary Products 115°F 125°F 1250 77 60.8 6.1 19.8 18.1 13.3 - - - 55.9 7.3 18.9 12.5 10. 1 - - - 72 52.8 5.6 32.2 26.9 21.6 16.2 - - 47.8 6.5 29.2 24. 0 18.8 13.6 - - 67 44.7 5.0 44.7 35.7 29.8 24.5 19.1 - 39.6 5.
528150-YTG-G-1210 Johnson Controls Unitary Products 75 ZR061 (5.0 Ton) Reheat Air on Evaporator Coil Temperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (M.
528150-YTG-G-1210 76 Johnson Controls Unitary Products ZR078 (6.5 Ton) Cool in g Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacit.
528150-YTG-G-1210 Johnson Controls Unitary Products 77 115°F 125°F 1625 77 72.6 8.1 27.5 24.0 18.0 - - - 68.3 9.0 24.0 21.5 15. 8 - - - 72 65.6 8.1 40.7 34.7 28.6 22.5 - - 60.4 8.9 38.3 32. 2 26.2 20.2 - - 67 58.6 8.1 54.0 45.3 39.2 33.1 27.1 - 52.6 8.
528150-YTG-G-1210 78 Johnson Controls Unitary Products ZR078 (6.5 Ton) Reheat Air on Evaporator Coil Temperatur e of Air on Con denser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity .
528150-YTG-G-1210 Johnson Controls Unitary Products 79 75°F 85°F 1625 7 2 3 4 . 3 5 . 7 ----- 3 2 . 4 5 . 6 ----- 67 34.2 5.4 1.3 1.2 1.1 1.0 - 32 .2 5.6 0.3 0.4 0.5 0.6 - 62 30.6 5.0 4.3 4.2 4.1 4.0 3.9 28.2 4.8 2.1 2.2 2 .2 2.3 2.4 1950 7 2 3 5 . 1 5 .
528150-YTG-G-1210 80 Johnson Controls Unitary Products ZR090 (7.5 Ton) Cool in g Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacit.
528150-YTG-G-1210 Johnson Controls Unitary Products 81 115°F 125°F 1875 77 87.0 8.8 31.8 27.6 20.5 - - - 80.5 9.7 27.4 25.2 18. 3 - - - 72 79.6 8.7 47.8 40.7 33.6 26.5 - - 73.1 9.6 45.1 38. 1 31.2 24.2 - - 67 72.2 8.7 63.8 53.7 46.6 39.5 32.4 - 65.8 9.
528150-YTG-G-1210 82 Johnson Controls Unitary Products ZR090 (7.5 Ton) Reheat Air on Evaporator Coil Temperature o f Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (.
528150-YTG-G-1210 Johnson Controls Unitary Products 83 75°F 85°F 1875 7 2 4 1 . 4 6 . 3 ----- 3 9 . 2 6 . 7 ----- 6 7 4 0 . 3 6 . 0 1 . 8 1 . 7 1 . 5 1 . 3 - 3 8 . 0 6 . 3 ----- 6 2 3 7 . 7 5 . 8 5 . 8 5 . 6 5 . 4 5 . 2 5 . 0 3 4 . 9 6 . 0 ----- 2250 7 2 4 1 .
528150-YTG-G-1210 84 Johnson Controls Unitary Products ZR102 (8.5 Ton) Cool in g Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacit.
528150-YTG-G-1210 Johnson Controls Unitary Products 85 115°F 125°F 2125 77 102.2 10.3 39.0 35.2 25.4 - - - 95.6 11.4 36.2 31.0 22.6 - - - 72 93.5 10.1 60.2 50.4 40.6 30.8 - - 86.5 11.1 56.8 47.1 37.5 27.8 - - 67 84.8 10.0 81.3 65.5 55.8 46.0 36.2 - 77.
528150-YTG-G-1210 86 Johnson Controls Unitary Products ZR102 (8.5 Ton) Reheat Air on Evaporator Coil Temperature o f Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (.
528150-YTG-G-1210 Johnson Controls Unitary Products 87 75°F 85°F 2125 7 2 4 2 . 8 6 . 3 ----- 3 7 . 6 6 . 4 ----- 6 7 3 5 . 4 6 . 5 1 . 6 1 . 5 1 . 4 1 . 2 - 2 8 . 6 6 . 8 ----- 6 2 3 1 . 9 6 . 2 4 . 4 4 . 3 4 . 2 4 . 1 4 . 0 2 4 . 7 6 . 5 ----- 2550 7 2 5 0 .
528150-YTG-G-1210 88 Johnson Controls Unitary Products ZR120 (10 Ton) Cooling Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (.
528150-YTG-G-1210 Johnson Controls Unitary Products 89 115°F 125°F 2500 77 114.7 11.7 43.6 38.1 27.5 - - - 104.7 12.9 36.1 33.8 23.4 - - - 72 105.4 11.5 66.6 55.9 45.3 34.6 - - 96.1 12.7 61.8 51.4 41.1 30.7 - - 67 96.1 11.4 89.6 73.7 63.1 52.4 41.8 - 87.
528150-YTG-G-1210 90 Johnson Controls Unitary Products ZR120 (10 Ton) Reheat Air on Evaporator Coil Temperature o f Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (M.
528150-YTG-G-1210 Johnson Controls Unitary Products 91 75°F 85°F 2500 72 59.1 8.4 0.6 0.7 0.9 - - 5 2.8 8.9 3.0 3.8 4.5 - - 6 7 5 3 . 8 8 . 0 ----- 4 9 . 1 8 . 4 ----- 6 2 4 9 . 1 7 . 6 ----- 4 2 . 8 8 . 0 ----- 3000 7 2 6 2 . 5 8 . 1 ----- 5 6 . 8 8 .
528150-YTG-G-1210 92 Johnson Controls Unitary Products ZR150 (12.5 Ton) Cooling Air on Evaporator Coil T emperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity.
528150-YTG-G-1210 Johnson Controls Unitary Products 93 115°F 125°F 3125 77 156.3 14.6 67.9 54.8 40.9 - - - 144.5 16.0 60.9 51.5 37.9 - - - 72 142.6 14.5 90.8 77.0 63.1 49.3 - - 131.3 15.9 86.6 73.0 59.4 45.8 - - 67 128.8 14.4 113.7 99.1 85.3 71.5 57 .
528150-YTG-G-1210 94 Johnson Controls Unitary Products ZR150 (12.5 Ton) Reheat Air on Evaporator Coil Temperature o f Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity .
528150-YTG-G-1210 Johnson Controls Unitary Products 95 75°F 85°F 3125 7 2 8 3 . 6 9 . 7 ----- 8 3 . 0 1 0 . 2 ----- 67 76.2 9.2 11.5 10.1 8.7 7.3 - 73. 4 9.4 12.6 11.4 10.1 8.8 - 62 70.5 8.7 34.8 33.4 32.0 30.6 29.2 66.4 8.9 44.7 43.4 42.1 40 .9 39.
528150-YTG-G-1210 96 Johnson Controls Unitary Products Drive Selection 1. Determine side or bottom supply duct Application. 2. Determine desired airflo w. 3. Calculate or measur e the amount of exte r nal static pressure. • Add or deduct any additional static resistanc e from “Additional Static Resi stan ce Table”.
528150-YTG-G-1210 Johnson Controls Unitary Products 97 Altitude and Tempe rature Correctio n for CFM, Static Pressure and Power. The information below should be use d to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level.
528150-YTG-G-1210 98 Johnson Controls Unitary Products Indoor Blower S pe ci fic a t io ns Size (Tons) Model Airflow Option Motor Motor Sheave Blower Sheave Belt HP RPM Eff. SF Frame Datu m Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) M odel 037 (3) ZH Std.
528150-YTG-G-1210 Johnson Controls Unitary Products 99 RPM Selection Size (Tons) Model Airflow Option HP Max BHP Motor Sheave Blower Sheave 6 Turns Open 5 Turns Open 4 Turns Open 3 Turns Open 2 Turns Open 1 Turn Open Fully Closed 037 (3) ZH Std. 1.5 1.
528150-YTG-G-1210 100 Johnson Controls Unitary Products Additional Static Resistance - ZH037 th ru 061 Size (Tons) Model CFM Cooling Only 1 1. Add these values to the available static resist ance in the respective Blower Performance T ables. Economizer 2 3 2.
528150-YTG-G-1210 Johnson Controls Unitary Products 101 Additional Static Resistance - ZH/ZR078 thr u 150 Size (Tons) Model CFM Coolin g Only 1 1. Add these values to the available static resist ance in the respective Blower Performance T ables. Economizer 2 3 2.
528150-YTG-G-1210 102 Johnson Controls Unitary Products Additional Static Resistance - ZJ078-150 Size (Tons) Model CFM Cooling Only 1 1. Add these values to the available static resist ance in the respective Blower Performance T ables. Economizer 2 , 3 2.
528150-YTG-G-1210 Johnson Controls Unitary Products 103 Gas Heat Minimum Supply Air Size (Tons) Model Heat Size Supply Air (CFM) Heating Min Max 037 (3) ZH/ZJ/ZR A05 / N05 890 2220 A07 / N07 915 2370 .
528150-YTG-G-1210 104 Johnson Controls Unitary Products Airflow Performanc e ZH037-150 Side Duct Applicat ion ZH037 (3.0 Ton) Side Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s.
528150-YTG-G-1210 Johnson Controls Unitary Products 105 ZH078 (6.5 Ton) Side Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 106 Johnson Controls Unitary Products ZH120 (10 Ton) Side Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 Johnson Controls Unitary Products 107 ZH037-150 Bott om Duct Applicat ion ZH037 (3.0 Ton) Bottom Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 108 Johnson Controls Unitary Products ZH078 (6.5 Ton) Bottom Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 Johnson Controls Unitary Products 109 ZH120 (10 Ton) Bottom Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 110 Johnson Controls Unitary Products ZJ037-150 Side Duct A pplicatio n ZJ037 (3.0 Ton) Side Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 Johnson Controls Unitary Products 111 ZJ078 (6.5 Ton) Side Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 112 Johnson Controls Unitary Products ZJ120 (10 Ton ) Side Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 Johnson Controls Unitary Products 113 ZJ037-150 Botto m Duct Ap plication ZJ037 (3.0 Ton) Bottom Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 114 Johnson Controls Unitary Products ZJ078 (6.5 Ton) Bottom Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 Johnson Controls Unitary Products 115 ZJ120 (10 Ton) Bottom Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 116 Johnson Controls Unitary Products ZR037-150 Side Duct Applicat ion ZR037 (3.0 Ton) Side Duct ZR049 (4.0 Ton) Side Duct ZR061 (5.0 Ton) Side Duct Air Flow (CFM) Available External Static Pressure - IWG 1 0.2 0.4 0.6 0.8 1.0 1.2 1.
528150-YTG-G-1210 Johnson Controls Unitary Products 117 ZR078-150 Side Duct Applicat ion ZR078 (6.5 Ton) Side Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 118 Johnson Controls Unitary Products ZR120 (10 Ton) Side Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 Johnson Controls Unitary Products 119 ZR037-150 Bott om Duct Applicat ion ZR037 (3.0 Ton) Bottom Duct ZR049 (4.0 Ton) Bottom Duct ZR061 (5.0 Ton) Bottom Duct Air Flow (CFM) Available External Static Pressure - IWG 1 0.2 0.4 0.6 0.8 1.
528150-YTG-G-1210 120 Johnson Controls Unitary Products ZR078-150 Bott om Duct Applicat ion ZR078 (6.5 Ton) Bottom Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 Johnson Controls Unitary Products 121 ZR120 (10 Ton) Bottom Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat e xchangers and 2” filter s. See STATIC RESI STANCE table for additional applications.
528150-YTG-G-1210 122 Johnson Controls Unitary Products Sound Performance Indoor Sound Power Levels (3 thru 5 Ton) Indoor Sound Power Levels (Horizontal Duct ed Inlet, Standard Static Be lt Drive) UNI.
528150-YTG-G-1210 Johnson Controls Unitary Products 123 Indoor Sound Power Levels (Horizontal Duct ed Discharge, Standard Stat ic Be lt Drive) UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / Standard S.
528150-YTG-G-1210 124 Johnson Controls Unitary Products UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / Standard Static Belt Drive TEST CONFIGURATION Horizontal ( Side Supply) Ducted Disch arge Indoor Blower Speed (RPM) 610 - 3 Turns Open Equivalent 710 - 1 Turn Open Equivalent External Static Pressure (IWG) 0.
528150-YTG-G-1210 Johnson Controls Unitary Products 125 Indoor Sound Power Levels (Vertical Ducted Inlet, Standard Static Belt Drive) UNIT DESCRIPTION / MODEL ZH/ZJ/ZR037 / 3 Ton / Standard Static Bel.
528150-YTG-G-1210 126 Johnson Controls Unitary Products Indoor Sound Power Levels (Vertical Ducted Dischar ge, Standard Static Belt Drive) UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / Standard Stati.
528150-YTG-G-1210 Johnson Controls Unitary Products 127 UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / Standard Static Belt Drive TEST CONFIGURATION Vertical (Bottom Supply) Ducted Discharge Indoor Blower Speed (RPM) 609 - 3 Turns Open Equivalent 712 - 1 Turn Open Equivalent External Static Pressure (IWG) 0.
528150-YTG-G-1210 128 Johnson Controls Unitary Products Indoor Sound Power Levels (Horizontal Ducted Inlet, High Static Belt Drive) UNIT DESCRIPTION / MODEL ZH/ZJ/ZR037 / 3 Ton / High Static Belt Driv.
528150-YTG-G-1210 Johnson Controls Unitary Products 129 Indoor Sound Power Levels (Horizontal Duct ed Discharge, High Static Belt Drive) UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / High Static Belt Drive TEST CONFIGURATION Horizontal (Side Return) Ducted Inlet Indoor Blower Speed (RPM) 1,012- 5.
528150-YTG-G-1210 130 Johnson Controls Unitary Products UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / High Static Belt Drive TEST CONFIGURATION Horizontal (Side Supp ly) Ducted Discharge Indoor Blower Speed (RPM) 922 - 6 Turns Open Equivalent 1,069 - 4 Turns Open Equivalent 1,165 - 2.
528150-YTG-G-1210 Johnson Controls Unitary Products 131 Indoor Sound Power Levels (Vertical Ducted Inlet, High Static Belt Drive) UNIT DESCRIPTION / MODEL ZH/ZJ/ZR037 / 3 Ton / High Static Belt Drive .
528150-YTG-G-1210 132 Johnson Controls Unitary Products Indoor Sound Power Levels (Vertical Ducted Discharge, High Static Belt Drive) UNIT DESCRIPTION / MODEL ZH/ZJ/ZR061 / 5 Ton / High Static Belt Dr.
528150-YTG-G-1210 Johnson Controls Unitary Products 133 UNIT DESCRIPTION / MODEL ZH/ZJ/ZR049 / 4 Ton / High Static Belt Drive TEST CONFIGURATION Vertical (Bottom Supply) Ducted Discharge Indoor Blower Speed (RPM) 962 - 5.5 Turns Open Equivalent 1,092 - 3.
528150-YTG-G-1210 134 Johnson Controls Unitary Products Indoor Sound Power Levels (6.5 thru 12.5 T on) Size (Tons) Model CFM ESP (IWG) Blower Sound Pow er, dB (10 -12 ) Watts Sound Rating 1 dB (A) Octave Band Centerline Frequency (Hz) RPM BHP 63 125 2 50 500 1000 2000 4000 8000 078 (6.
528150-YTG-G-1210 Johnson Controls Unitary Products 135 Outdoor Sound Power Levels ZH/ZJ/ZR037-150 Size (Tons) Model Sound Rating 1 dB (A) Octave Band Centerline Frequency (H z) 63 125 250 500 1000 2000 4000 8000 037 (3) ZH 81 82.5 8 6.5 78.0 75.5 76.
528150-YTG-G-1210 136 Johnson Controls Unitary Products Electrical Data ZH037-061 Standard Indo or Blower - Without Powered Convenience Ou tlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Exh Motor Pwr Conv Outlet Electric He at Op t i o n MCA 1 (Amps) 1.
528150-YTG-G-1210 Johnson Controls Unitary Products 137 ZH078-150 Standard Motor - Without Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr .
528150-YTG-G-1210 138 Johnson Controls Unitary Products 120 (10) 208 17.9 120 28 .0 3.5 6.8 5.5 0.0 N o n e -- -5 4 . 1 5 9 . 6 7 0 7 0 E18 13.5 2 37.5 55.3 62.2 70 70 E24 18 2 50.0 71 77.8 80 80 E36 25.5 2 70.8 97 103.9 100 110 E54 40.6 2 112.7 149.4 156.
528150-YTG-G-1210 Johnson Controls Unitary Products 139 ZH037-061 Hi Static In door Blower - Without Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Exh Motor Pwr Conv Outlet Electric He at Op t i o n MCA 1 (Amps) 1.
528150-YTG-G-1210 140 Johnson Controls Unitary Products ZH078-150 Hi Static Motor - Without Powered Convenien ce Ou tlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor P.
528150-YTG-G-1210 Johnson Controls Unitary Products 141 120 (10) 208 17.9 120 28 .0 3.5 9.6 5.5 0.0 None - - - 56.9 62.4 70 80 E18 13.5 2 37.5 58.8 65.7 70 80 E24 18 2 50.0 74.5 81.3 80 90 E36 25.5 2 70.8 100.5 107.4 110 110 E54 40.6 2 112.7 152.9 159.
528150-YTG-G-1210 142 Johnson Controls Unitary Products ZH037-061 Standard Indo or Blower - With Powered Convenience Ou tle t Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Exh Motor Pwr Conv Outlet Electric He at Op t i o n MCA 1 (Amps) 1.
528150-YTG-G-1210 Johnson Controls Unitary Products 143 ZH078-150 Standard Motor - With Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Exh.
528150-YTG-G-1210 144 Johnson Controls Unitary Products 120 (10) 208 17.9 120 28.0 3.5 6.8 5.5 10.0 None - - - 64.1 69.6 80 80 E18 13.5 2 37.5 67.8 74.7 80 80 E24 18 2 50.0 83.5 90.3 90 100 E36 25.5 2 70.8 109.5 116.4 11 0 125 E54 40.6 2 112.7 161.9 168.
528150-YTG-G-1210 Johnson Controls Unitary Products 145 ZH037-061 Hi Static Indoor Blower - With Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Exh Motor Pwr Conv Outlet Electric He at Op t i o n MCA 1 (Amps) 1.
528150-YTG-G-1210 146 Johnson Controls Unitary Products ZH078-150 Hi Static Motor - With Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Ex.
528150-YTG-G-1210 Johnson Controls Unitary Products 147 120 (10) 208 17.9 120 28.0 3.5 9.6 5.5 10.0 None - - - 66.9 72.4 80 90 E18 13.5 2 37.5 71.3 78.2 80 90 E24 18 2 50.0 87 93.8 90 100 E36 25.5 2 70.8 113 119.9 125 125 E54 40.6 2 112.7 165.4 172.2 175 175 230 17.
528150-YTG-G-1210 148 Johnson Controls Unitary Products ZJ037-061 Standard Indo or Blower - Without Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Exh Motor Pwr Conv Outlet Electric He at Op t i o n MCA 1 (Amps) 1.
528150-YTG-G-1210 Johnson Controls Unitary Products 149 ZJ078-150 Standard Motor - Without Powered Convenience Outle t Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr.
528150-YTG-G-1210 150 Johnson Controls Unitary Products 120 (10) 208 16 110 24.9 3.5 6.8 5.5 0.0 None - - - 49.8 55.3 60 70 E18 13.5 2 37.5 55.3 62.2 60 70 E24 18 2 50.0 71 77.8 80 80 E36 25.5 2 70.8 97 103.9 100 110 E54 40.6 2 112.7 149.4 156.2 15 0 175 230 16 110 24.
528150-YTG-G-1210 Johnson Controls Unitary Products 151 ZJ037-061 Hi Static Indoor Blower - With ou t Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Exh Motor Pwr Conv Outlet Electric He at Op t i o n MCA 1 (Amps) 1.
528150-YTG-G-1210 152 Johnson Controls Unitary Products ZJ078-150 Hi Static Motor - Without Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr.
528150-YTG-G-1210 Johnson Controls Unitary Products 153 120 (10) 208 16 110 24.9 3.5 9.6 5.5 0.0 None - - - 52.6 58.1 60 70 E18 13.5 2 37.5 58.8 65.7 60 70 E24 18 2 50.0 74.5 81.3 80 90 E36 25.5 2 70.8 100.5 107.4 11 0 110 E54 40.6 2 112.7 152.9 159.7 175 175 230 16 110 24.
528150-YTG-G-1210 154 Johnson Controls Unitary Products ZJ037-061 Standard Indo or Blower - With Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Exh Motor Pwr Conv Outlet Electric He at Op t i o n MCA 1 (Amps) 1.
528150-YTG-G-1210 Johnson Controls Unitary Products 155 ZJ078-150 Standard Motor - With Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Exh.
528150-YTG-G-1210 156 Johnson Controls Unitary Products 120 (10) 208 16 110 24.9 3.5 6.8 5.5 10.0 None - - - 59.8 65.3 70 80 E18 13.5 2 37.5 67.8 74.7 70 80 E24 18 2 50.0 83.5 90.3 90 100 E36 25.5 2 70.8 109.5 116.4 110 125 E54 40.6 2 112.7 161.9 168.
528150-YTG-G-1210 Johnson Controls Unitary Products 157 ZJ037-061 Hi Static Blower - With Powered Convenie nce Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Exh Motor Pwr Conv Outlet Electric He at Op t i o n MCA 1 (Amps) 1.
528150-YTG-G-1210 158 Johnson Controls Unitary Products ZJ078-150 Hi Static Motor - With Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Ex.
528150-YTG-G-1210 Johnson Controls Unitary Products 159 120 (10) 208 16 110 24.9 3.5 9.6 5.5 10.0 None - - - 62.6 68.1 70 80 E18 13.5 2 37.5 71.3 78.2 80 80 E24 18 2 50.0 87 93.8 90 100 E36 25.5 2 70.8 113 119.9 125 125 E54 40.6 2 112.7 165.4 172.2 175 175 230 16 110 24.
528150-YTG-G-1210 160 Johnson Controls Unitary Products ZR037-061 Standard Indo or Blower - Without Powered Convenience Ou tlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower .
528150-YTG-G-1210 Johnson Controls Unitary Products 161 ZR078-150 Standard Motor - Without Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr .
528150-YTG-G-1210 162 Johnson Controls Unitary Products 120 (10) 208 17.9 120 28 .0 1.5 8.2 5.5 0.0 N o n e -- -5 1 . 5 5 7 . 0 6 0 7 0 E18 13.5 2 37.5 57.1 64.0 60 70 E24 18 2 50.0 72.7 79.6 80 80 E36 25.5 2 70.8 98.7 105.6 100 110 E54 40.6 2 112.7 151.
528150-YTG-G-1210 Johnson Controls Unitary Products 163 ZR037-061 Hi Static In door Blower - Without Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower .
528150-YTG-G-1210 164 Johnson Controls Unitary Products ZR078-150 Hi Static Motor - Without Powered Convenien ce Ou tlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor P.
528150-YTG-G-1210 Johnson Controls Unitary Products 165 120 (10) 208 17.9 120 28.0 1.5 10.9 5.5 0.0 None - - - 54.2 59.7 70 70 E18 13.5 2 37.5 60.5 67.3 70 70 E24 18 2 50.0 76.1 83.0 80 90 E36 25.5 2 70.8 102.1 109.0 110 110 E54 40.6 2 112.7 154.5 161.
528150-YTG-G-1210 166 Johnson Controls Unitary Products ZR037-061 Standard Indo or Blower - With Powered Convenience Ou tle t Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Mo.
528150-YTG-G-1210 Johnson Controls Unitary Products 167 ZR078-150 Standard Motor - With Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Exh.
528150-YTG-G-1210 168 Johnson Controls Unitary Products 120 (10) 208 17.9 120 28.0 1.5 8.2 5.5 10.0 None - - - 61.5 67.0 70 80 E18 13.5 2 37.5 69.6 76.5 70 80 E24 18 2 50.0 85.2 92.1 90 100 E36 25.5 2 70.8 111.2 118.1 12 5 125 E54 40.6 2 112.7 163.6 170.
528150-YTG-G-1210 Johnson Controls Unitary Products 169 ZR037-061 Hi Static Indoor Blower - With Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Moto.
528150-YTG-G-1210 170 Johnson Controls Unitary Products ZR078-150 Hi Static Motor - With Powered Convenience Outlet Size (Tons) Volt Compres sors (each) OD Fan Motors (each) Supply Blower Motor Pwr Ex.
528150-YTG-G-1210 Johnson Controls Unitary Products 171 120 (10) 208 17.9 120 28.0 1.5 10.9 5.5 10.0 None - - - 64.2 69.7 80 80 E18 13.5 2 37.5 73.0 79.8 80 80 E24 18 2 50.0 88.6 95.5 90 100 E36 25.5 2 70.8 114.6 121.5 125 125 E54 40.6 2 112.7 167.0 173.
528150-YTG-G-1210 172 Johnson Controls Unitary Products Typical Wiring Diagrams ZH/ZJ037-150 Typical Wiring Dia grams Typical ZH/ZJ037-061 Cooling Unit with Gas Heat 230 Volt Wir ing Diagram.
528150-YTG-G-1210 Johnson Controls Unitary Products 173 Typical ZR037-061 Reheat Unit with Gas H eat 230 Volt Wiring Diagram.
528150-YTG-G-1210 174 Johnson Controls Unitary Products Typical ZH/ZJ037-061 Cooling Unit with Gas Heat 460/575 Volt Wiring Dia gram.
528150-YTG-G-1210 Johnson Controls Unitary Products 175 Typical ZR037-061 Reheat Unit with Ga s Heat 460 /5 75 Volt Wiring Diagram.
528150-YTG-G-1210 176 Johnson Controls Unitary Products Typical ZH/ZJ037-061 Cooling Unit with/w ithout Electr ic He at Wiring Diagram.
528150-YTG-G-1210 Johnson Controls Unitary Products 177 Typical ZR037-061 Reheat Unit with/wi thout Electric Heat Wiri ng Diagram.
528150-YTG-G-1210 178 Johnson Controls Unitary Products Typical ZH/ZJ/ZR078-120 Cooling Unit with Gas Heat 230 Volt Wiring Diagram.
528150-YTG-G-1210 Johnson Controls Unitary Products 179 Typical ZH/ZJ/ZR078-120 Cooling Unit wit h Gas Heat 460/57 5 Volt Wirin g Diagr am.
528150-YTG-G-1210 180 Johnson Controls Unitary Products Typical ZH/ZJ/ZR078-120 Cooling Unit wit h/without Electric Heat Wiring Di agram.
528150-YTG-G-1210 Johnson Controls Unitary Products 181 Typical ZH/ZJ /Z R150 Cooling Uni t with Gas Heat 230 Volt Wiring Diagram.
528150-YTG-G-1210 182 Johnson Controls Unitary Products Typical ZH/ZJ /Z R150 Cooling Uni t with Gas Heat 460/575 Volt Wiring Diagram.
528150-YTG-G-1210 Johnson Controls Unitary Products 183 Typical ZH/ZJ/ZR150 Cool ing Unit with/withou t Electric Heat Wiring Diagram.
528150-YTG-G-1210 184 Johnson Controls Unitary Products Typical ZR037-061 Reh eat Wiring Diagram.
528150-YTG-G-1210 Johnson Controls Unitary Products 185 Typical ZR078-120 Reh eat Wiring Diagram.
528150-YTG-G-1210 186 Johnson Controls Unitary Products Typical ZR150 Reheat Wiring Diagra m.
528150-YTG-G-1210 Johnson Controls Unitary Products 187 Typical ZH/ZJ078-150 Factor y In stalled VF D (Option).
528150-YTG-G-1210 188 Johnson Controls Unitary Products Typical ZH/ZJ078-150 Factory In stalle d VF D with Manual Bypass (Optio n).
528150-YTG-G-1210 Johnson Controls Unitary Products 189 Typical ZH/ZJ078-150 BAS Ready Unit with Factory In stalled VFD (Option).
528150-YTG-G-1210 190 Johnson Controls Unitary Products Typical ZH/ZJ078-150 BAS Ready Unit with F act ory Installed VFD and Manual Bypass (Option).
528150-YTG-G-1210 Johnson Controls Unitary Products 191 Typical ZH/ZJ078-150 VFD Ready Unit (Option).
528150-YTG-G-1210 192 Johnson Controls Unitary Products Weights and Dimensions ZH/ZJ037-150 Unit Weights Unit 4 Point Load Weig ht Unit 6 Point Load Weight D A C B LEFT FRONT D A C B E F LEFT FRONT Size (Tons) Model Weight (lbs.) Cente r of Gravity 4 Point Lo ad Location (lbs.
528150-YTG-G-1210 Johnson Controls Unitary Products 193 Weights and Dimensions ZR037-150 Un it Weights Unit 4 Point Load Weig ht Unit 6 Point Load Weight D A C B LEFT FRONT D A C B E F LEFT FRONT Size (Tons) Model Weight (lbs.) Cente r of Gravity 4 Point Lo ad Location (lbs.
528150-YTG-G-1210 194 Johnson Controls Unitary Products ZH/ZJ/ZR037-150 Unit Dimensions ZH037-061 and ZJ/Z R037 ZH/ZJ/ZR037-150 Unit Acces sory Weights Unit Accessory Weight (lb s.) Shipping Operating Economizer 90 85 Power Exhaust 40 35 Electric Heat 1 1.
528150-YTG-G-1210 Johnson Controls Unitary Products 195 ZJ/ZR049 thru 061 and ZH/Z J/ZR07 8 thru 120 Ø 24.47 TYP . 2 PL. 15.38 15.38 59.00 15.25 29.69 59 LEFT 1 1 3/8 21 3/16 89 27 5/16 4 3/16 FRONT .
528150-YTG-G-1210 196 Johnson Controls Unitary Products ZH150 FRONT See detail B for drain location See detail A for gas inlet C D E F B 4 3/16 27 5/16 89 21 3/16 1 1 3/8 A LEFT 59 14.
528150-YTG-G-1210 Johnson Controls Unitary Products 197 ZJ/ZR150 15.23 29.03 14.85 29.03 14.85 15.23 28.86 29.66 44.09 Ø 24.58 TYP . 4 PL. FRONT See detail B for drain location See detail A for gas inlet C D E F B 4 3/16 27 5/16 89 21 3/16 1 1 3/8 A LEFT 59 ZH/ZJ/ZR037-150 Unit Physica l Dimensions Unit Model Number Dimensio n (in.
528150-YTG-G-1210 198 Johnson Controls Unitary Products Detail A Detail B 42” CABINET Ø 3.126 Ø 2.000 3.184 4.727 7.705 14.594 Gas Pipe Inlet Gas Exhaust V ent 50 3/4” CABINET Ø 3.126 Ø 2.000 3.184 4.737 7.715 17.541 Gas Pipe Inlet Gas Exhaust V ent 5-3/8 3/4” FPT ZH/ZJ/ZR037-150 Unit Cle aran ces Direction Distance ( in.
528150-YTG-G-1210 Johnson Controls Unitary Products 199 ZH/ZJ/ZR037-150 Unit Bottom Duct Openings TOP VIEW Bottom condensate drain Bottom gas supply entry FRONT RETURN AIR SUPPL Y AIR RIGHT LEFT 20 1/8 19 1/8 17 1/8 6 13/16 6 13/16 32 1 1/16 14 1/2 16 3/8 18 1/16 25 9/16 12 5/16 27 1/2 24 21 18 89 Ø 2.
528150-YTG-G-1210 200 Johnson Controls Unitary Products ZH/ZJ/ZR037-150 Unit Electric al Entry ZH/ZJ/ZR037-120 Unit Side Du ct Openings Disconnect Swith Cover Power Entry Ø 2-1/2 Control Entry Ø 7/8.
528150-YTG-G-1210 Johnson Controls Unitary Products 201 ZH150 Unit Side Duct Op enings ZJ/ZR150 U nit Side Duct Openings ZH/ZJ/ZR037-150 Side Duct Dimensions Unit Model Number Dimension (in.
528150-YTG-G-1210 202 Johnson Controls Unitary Products ZH/ZJ/ZR037-150 Unit Left Duc t Opening ZH/ZJ/ZR037-150 Unit Acces sory Dimensions ZH/ZJ/ZR037-150 Roof Cu rb 4-5/16 30-3/8 8 or 14 50-1/2 30 20 20 80-5/8 6 2 T YP.
528150-YTG-G-1210 Johnson Controls Unitary Products 203 ZH/ZJ/ZR037-150 Transition Ro of Curb ZH/ZJ/ZR037-150 Economizer Assembly 76-5/8 94 50-1/2 30-1/2 64-1/4 59-1/4 10 23 4 26 80-5/8 2T Y P FRONT R.
528150-YTG-G-1210 204 Johnson Controls Unitary Products Economizer Options Factory Installed Downflo w Economizer Field Insta lled Downflow Ec onomizer W/ Power Exhaust Economizer Usage Application Ca.
528150-YTG-G-1210 Johnson Controls Unitary Products 205 Field Insta lled Horizontal Economizer W/Power Exhaust Slab Economizer Downflow W/Po wer Exhaus t 1EH0408 Barometric Relief Hood 1EH0408 Baromet.
Subject to change without notice. Pr inted in U.S.A. 528150-YTG-G-1210 Copyright © 2011 b y Johnson Controls, Inc. All rights reserved. Supersedes: 528150-YTG-F-0810 Johnson Contro ls Unitary Product.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York R-410A ZH/ZJ/ZR Series è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York R-410A ZH/ZJ/ZR Series - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York R-410A ZH/ZJ/ZR Series imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York R-410A ZH/ZJ/ZR Series ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York R-410A ZH/ZJ/ZR Series, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York R-410A ZH/ZJ/ZR Series.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York R-410A ZH/ZJ/ZR Series. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York R-410A ZH/ZJ/ZR Series insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.