TECHNICAL GUIDE SPLIT -SYSTEM A IR CONDITIONERS 13 SEER – R-22 MODELS: H*RD018 THRU 060 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) H*RD036 THRU 060 (2.5 THRU 5 NOMINAL TONS, 3 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice.
254892-YTG-C-0606 2 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request.
254892-YTG-C-0606 Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Ma tched Systems - 1 Phase Outdoor Unit H2RD018S06 H2RD024S06 H2RD030S06 H2RD036S06 H2RD042S06 H2RD048S06 .
254892-YTG-C-0606 4 Unitary Products Group H C 1 8 A 3 X 0 2 B + 1 ––––– H C 3 0 A 3 X – 2 A + 0 0 –––– HC36B3X – – 0 0 – – – H C 4 2 C 3 X ––––0 0 – H C 6 0 C .
254892-YTG-C-0606 Unitary Products Group 5 PROCEDURES: 1. U nit factory charge listed on the unit nameplate includes refr igerant for the condenser , the smallest evaporator and for 15 feet of inter- connecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
254892-YTG-C-0606 6 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request.
254892-YTG-C-0606 Unitary Products Group 7 Additional R-22 Charge / Orifice Size for V arious Ma tched Systems - 3 Phase Outdoor Unit H1RD030S(25,46) H1RD036S(25,46) H1RD042S(25,46) H1RD048S(25, 46) H.
254892-YTG-C-0606 8 Unitary Products Group PROCEDURES: 1. U nit factory charge listed on the unit nameplate include s refr iger ant for the condenser , the smallest evaporator and for 15 feet of inter- connecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
254892-YTG-C-0606 Unitary Products Group 9 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL ELECTRIC HEA T KW 2 W RA TED CFM NET MBH SEER EER TOT AL SENS. 1 & 3 PH 13 SEER AC WITH MA H2RD018S06 MA08B 2,5,8 17 FC/MC18B 600 17.
254892-YTG-C-0606 10 Unitary Products Group — = Not applicable. 1 PH 13 SEER AC WITH A V / SV - V ARIABLE SPEED H2RD018S06 A V24 2,5,8,10,15 17 – 600 18.0 1 1.7 14.00 1 1.50 H2RD024S06 A V24 2,5,8,10,15 17 – 800 23.2 16.5 14.00 1 1.50 H2RD030S06 A V36 5,8,10,15,18 21 – 1000 30.
254892-YTG-C-0606 Unitary Products Group 11 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL F URNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. H2RD018S06 450 750 14,17 FC/MC/PC/UC18 600 17.
254892-YTG-C-0606 12 Unitary Products Group H2RD042S06 1200 1600 17,21 FC/MC/PC/UC42 1400 40.5 29.6 13.00 1 1.00 21,24 FC/MC/PC/UC48 1400 41.0 30.2 13.00 1 1.00 17 G*F A042S17 1400 40.5 29.6 13.00 1 1.00 21 G*F A048S21 1400 41.0 29.6 13.00 1 1.00 21 G*FD042H21 1400 40.
254892-YTG-C-0606 Unitary Products Group 13 COOLING CAP ACITY - With V ariable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER AC WITH V ARIABLE SPEED FURNACES 2 H2RD018S06 PV8*A12 FC/MC/PC18A 14 600 17.
254892-YTG-C-0606 14 Unitary Products Group H2RD036S06 PV8*A12 FC/MC/PC36A 14 1200 35.0 25.4 13.00 1 1.00 PV8*B16 FC/MC/PC36B 17 1200 35.2 25.6 13.75 1 1.00 PV8*C16 FC/MC/PC36C 21 1200 35.2 25.6 14.00 1 1.50 PV8*C20 FC/MC/PC36C 21 1200 35.2 25.6 14.00 1 1.
254892-YTG-C-0606 Unitary Products Group 15 H2RD048S06 PV8*C16 FC/MC/PC48C 21 1500 46.5 34.2 13.00 1 1.00 PV8*C20 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C16 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C20 FC/MC/PC48C 21 1600 47.0 35.
254892-YTG-C-0606 16 Unitary Products Group ACCESSORIES Refer to Price Manual for specific model numbers. HARD ST ART KIT - Provides increased starting torque for areas with low voltage. COMPRESSOR BLANKET - Designed to furth er reduce the normal compressor operating sound.
254892-YTG-C-0606 Unitary Products Group 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), s.
254892-YTG-C-0606 18 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F),.
254892-YTG-C-0606 Unitary Products Group 19 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), s.
254892-YTG-C-0606 20 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F),.
254892-YTG-C-0606 Unitary Products Group 21 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), s.
254892-YTG-C-0606 22 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F),.
254892-YTG-C-0606 Unitary Products Group 23 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), s.
Subject to change without notice. Printe d in U .S.A. 254892-YTG-C-0606 Copyright © by York International Corp. 2006. All right s reserved. Supersedes: 254892 / 036-21339-002 Rev.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York H*RD036 THRU 060 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York H*RD036 THRU 060 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York H*RD036 THRU 060 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York H*RD036 THRU 060 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York H*RD036 THRU 060, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York H*RD036 THRU 060.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York H*RD036 THRU 060. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York H*RD036 THRU 060 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.