246819-BTG-H-0208 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SPLIT - SYSTEM HEA T PUMPS 13 SEER – R-22 MODELS: E*BD-F018 THRU 060 (1.5 THRU 5 NOMINAL T ONS, 1 PHASE) E*BD-(T ,W)036 THRU 060 (2.5 THRU 5 NOMINAL T ONS, 3 PHASE) Due to continuo us product imp rovement, speci fications are subject to chan ge without notice.
246819-BTG-H-0208 2 Unitary Products Group All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request.
246819-BTG-H-0208 Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Matched Syste ms - 1 Phase Outdoor Unit EABD-F018S EABD-F024S EABD-F030S EAB D-F036S EABD-F042S EABD-F048S.
246819-BTG-H-0208 4 Unitary Products Group * This loose coil match does not achieve 13 SEER. PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the condenser , the smallest evaporator and 15 feet of inter- connecting line tubing.
246819-BTG-H-0208 Unitary Products Group 5 All dimensions are in inche s. Th ey are su bject to change with- out notice. Certified dimensions will be pro vided upon request.
246819-BTG-H-0208 6 Unitary Products Group PROCEDURES: 1. U nit factory charge listed on the unit nameplate includes refr igerant for the condenser , the smallest evaporator and 15 feet of inter-con- necting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using th e above table.
246819-BTG-H-0208 Unitary Products Group 7 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 1 & 3 PH 13 SEER HP WITH MA EABD-F018S MA08B 17 FC/MC18B 600 18 .0 12.
246819-BTG-H-0208 8 Unitary Products Group — = Not Applicable. Go to www.ari. org/aridirectory for the latest additiona l matches. 1 PH 13 SEER AC WITH A V / SV - V ARIABLE SPEED EABD-F018S A V24 17 – 600 18.0 12.6 14.00 12.00 EABD-F024S A V24 17 – 800 23.
246819-BTG-H-0208 Unitary Products Group 9 COOLING CAP ACITY - Upflow , Downflow , and Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. EABD-F018S 450 750 14,17 FC/MC/PC/UC18 600 18.
246819-BTG-H-0208 10 Unitary Products Group COOLING CAP ACITY - With V ariable S peed Furnac es UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 EABD-F018S (F ,L)L8V A12 FC/MC/PC18A 14 600 18.
246819-BTG-H-0208 Unitary Products Group 11 EABD-F048S FL9(C,V)D20 FC/MC/PC60D 24 1600 46.0 35 .5 13.25 1 1.00 (F ,L)L8VC16 FC/PC60C 21 1500 45.5 35.1 13 .25 1 1.00 (F ,L)L8VC20 FC/PC60C 21 1600 46.0 35.4 13 .25 1 1.00 FL9(C,V)C16 FC/PC60C 21 1600 46.
246819-BTG-H-0208 12 Unitary Products Group HEA TING PERFORMANCE - With Air Handler UNIT MODEL* AIR HANDLER COIL 1 MODEL ARI HEA T ING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD 1 & 3 PH 13 SEER HP WITH MA EABD-F018S MA08B FC/MC18B 18.0 3.
246819-BTG-H-0208 Unitary Products Group 13 CP equals MBH output divided by (t otal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating ou tput during a normal annual usage period for heating divided by the total electric power input during the same period.
246819-BTG-H-0208 14 Unitary Products Group CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period.
246819-BTG-H-0208 Unitary Products Group 15 HEA TING CAP ACITY - W ith V ariable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE COIL 1 MODEL ARI HEA T ING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD EABD-F018S (F ,L)L8V A12 FC/MC/PC18A 17.5 3.
246819-BTG-H-0208 16 Unitary Products Group CP equals MBH output divided by (to tal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period.
246819-BTG-H-0208 Unitary Products Group 17 ACCESSORIES Refer to Price Manual for specific model numbers. St art Assist Kit (2SA067*) Blower Time Delay - A vailable to increase efficiency when installed. Installs on indoor section and maintains blower for approximately one minute a fter cooling thermostat has been satisfied.
246819-BTG-H-0208 18 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 Unitary Products Group 19 Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 20 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 Unitary Products Group 21 Multipliers for determining th e performance with other indoor sections NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sen.
246819-BTG-H-0208 22 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 Unitary Products Group 23 Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 24 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), s.
246819-BTG-H-0208 Unitary Products Group 25 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO EABD-F018S EV APORA T OR COIL MODEL NO FC /MC/PC/UC18 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
246819-BTG-H-0208 26 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO EABD-F024S EV APORA T OR COIL MODEL NO FC /MC/PC/UC24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
246819-BTG-H-0208 Unitary Products Group 27 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F030S, EABD-(T ,W)030S** EV APORA T OR COIL MODEL NO FC /MC/PC35 AIR TEMP .
246819-BTG-H-0208 28 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E ABD-F036S, EABD-(T ,W)036S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC48 AIR TEMP .
246819-BTG-H-0208 Unitary Products Group 29 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F042S, EABD-(T ,W)042S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC48 AIR TEMP .
246819-BTG-H-0208 30 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E ABD-F048S, EABD-(T ,W)048S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC60 AIR TEMP .
246819-BTG-H-0208 Unitary Products Group 31 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F060S, EABD-(T ,W)060S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC60 AIR TEMP .
Subject to change without notice. Printed in U.S.A. 246819-BTG-H-0208 Copyright © by Unitary Products Group. 2008. Al l rights reserved. Supersedes: 246819-BTG-G-0607 Unitary 5005 Norman Product Y or.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York E*BD-(T è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York E*BD-(T - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York E*BD-(T imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York E*BD-(T ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York E*BD-(T, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York E*BD-(T.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York E*BD-(T. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York E*BD-(T insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.