343615-YTG-B-0308 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SINGLE P ACKAGE GA S/ELECTRIC UNITS AND SINGLE P ACKAGE AIR CONDITIONERS DY 036, 048 & 060 3, 4 & 5 NOMINAL TONS 14.
343615-YTG-B-0308 2 Johnson Controls Unitary Products T ABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMEN CLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . .
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 3 PRODUCT NOMENCLA TURE D Y 048 N04 A 2 A AA 2 0 1 2 4 A D = A/C, Single Pkg., R-22 Product Category Airflow D = Direct Drive/Motorized Damper B = Direct Drive/Single Input Economizer A = Direct Drive Product Generation 2 = Second Generation C00 = Cooling Only.
343615-YTG-B-0308 4 Johnson Controls Unitary Products FEA TURES All models are available with a wide variety of factory- mounted options such as stainless steel heat exchangers, electric heaters, phas.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 5 Gas/Electric Electric/Electric and Heat Pump FIGURE 1 - UNIT CUT A W A Y 3/4 " PVC female condensate drain Knockout for side control entry G.
343615-YTG-B-0308 6 Johnson Controls Unitary Products F ACTOR Y -INST ALLED OPTIONS • SINGLE INPUT ELECTR ONIC ENTHALPY ECONO- MIZERS - Includes a slide-in / plug-in damper assemb ly with fully modulating spring-return motor actuator capa- ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 7 • ST AINLESS STEEL HEA T EXCHANGER - F or applica- tions in corrosive environments, this option provides a full stainless steel heat exch anger assembly .
343615-YTG-B-0308 8 Johnson Controls Unitary Products • ENTHALPY ACCESSOR Y CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy . • BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 9 T AB LE 4: DY036 INDOOR SOUND POWER LEVELS (HORIZONT AL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Sta.
343615-YTG-B-0308 10 Johnson Controls Unitary Products T AB LE 6: DY03 6 IN DOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Stat.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 11 T AB LE 8: DY048 INDOOR SOUND POWER LEVELS (HORIZONT AL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower St.
343615-YTG-B-0308 12 Johnson Controls Unitary Products T AB LE 10: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Stati.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 13 T AB LE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONT AL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower S.
343615-YTG-B-0308 14 Johnson Controls Unitary Products T AB LE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Stati.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 15 T AB LE 16: DY036 COOLING CAP ACITIES (3 TON) Air on Evap- orator Co il T emperatur e of Air on Condenser Coil 75°F 85°F CFM WB (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Cap acity (MBH) 1 Return Dry Bulb (°F) To t a l Cap.
343615-YTG-B-0308 16 Johnson Controls Unitary Products T AB LE 17: DY048 COOLING CAP ACITIES (4 TON) Air on Evap- orator Co il T emperatur e of Air on Condenser Coil 75°F 85°F CFM WB (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Capacity (MBH) 1 Return Dry Bulb (°F) To t a l Cap.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 17 T AB LE 18: DY060 COOLING CAP ACITIES (5 TON) Air on Evap- orator Co il T emperatur e of Air on Condenser Coil 75°F 85°F CFM WB (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Cap acity (MBH) 1 Return Dry Bulb (°F) To t a l Cap.
343615-YTG-B-0308 18 Johnson Controls Unitary Products T AB LE 19: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) SIDE DUCT APPLICATION UNIT TONNAGE MOT OR 1 SPEED A V AILABLE EXTERNAL ST A TIC PRESSURE - IWG 2 0.2 0.3 0.4 0. 5 0.6 0.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 19 1. Deduct these resistance values from the available external st atic pressure shown i n SUPPL Y AIR BLOWER PERFORMANCE T ables. 2. Add these resistance va lues to the av ailable static resi stance values on SUPP L Y AIR BLOWER PERFORMANCE T ables.
343615-YTG-B-0308 20 Johnson Controls Unitary Products T AB LE 23: ELECTRICAL DA T A - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET Size (Tons) Volt Compressors (each) OD Fan Motor.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 21 060 (5.0) 208-1-60 28.8 145.0 45.0 2.3 7.6 0.0 None - - - 45.9 50 E05 4.0 1 19.2 45.9 50 E07 5.6 1 26.9 45.9 50 E10 8.0 1 38.5 57.6 60 E15 11.9 2 57.2 81.0 90 E20 15.9 2 76.4 105. 1 110 E30 22.2 2 106.
343615-YTG-B-0308 22 Johnson Controls Unitary Products T AB LE 24: ELECTRICAL DA T A - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET Size (Tons) Volt Compressors (each) OD Fan Motors.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 23 060 (5.0) 208-1-60 28.8 145.0 45.0 2.3 7.6 10.0 None - - - 55.9 60 E05 4.0 1 19.2 55.9 60 E07 5.6 1 26.9 55.9 60 E10 8.0 1 38.5 70.1 80 E15 11.9 2 57.2 93.5 100 E20 15.9 2 76.4 117. 6 125 E30 22.
343615-YTG-B-0308 24 Johnson Controls Unitary Products T ABLE 25: DY PHYSICAL DATA MODELS DY 036 048 060 EV APORA TOR BLOWER Centrifuga l Blower (Di a. x Wd. in.) 12 X 10 12 X 10 12 X 10 Fan Motor H P (Direct Drive) 3/4 1 1 EV APORA TOR COIL Rows Deep 3 4 4 Fins Per Inch 13 13 13 Face Area (Ft.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 25 FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING REFER TO THE ELECTRICAL DA T A T ABLES TO SIZE THE DISCONNECT SWITCH, O VERCURRENT PROTEC- TION AND WIRING.
343615-YTG-B-0308 26 Johnson Controls Unitary Products FIGURE 3 - UNIT DIMENSIONS (3 - 5 TO N COOLING ONL Y/ELECTRIC HEA T ) FRONT VIEW FIGURE 4 - UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEA T) FRONT V.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 27 FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD DETAIL “A” FIGURE 6 - UNIT WITH FIXED OUTD OOR AIR/MOTORIZED DAMPER RAINHOOD DETAIL “B”.
343615-YTG-B-0308 28 Johnson Controls Unitary Products FIGURE 7 - UNIT DIMENSIONS (REAR VIEW) FIGURE 8 - DISCONNECT/B LOWER ACCESS LOCA TION T ABLE 28: UTILITIES ENTR Y HOLE OPENIN G SIZE (DIA.) USED FOR A 7/8” KO 1 1. Opening in the bottom to the unit can be located by the side in the insulation.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 29 FIGURE 9 - TYPICAL APPLICA TIONS.
343615-YTG-B-0308 30 Johnson Controls Unitary Products FIGURE 10 -FOUR A ND SIX POINT LOADING 44 7 / 8 82 1 / 4 Y X A B C D CONDENSER COIL END OF UNIT FRONT OF UNIT APPROXIMATE CENTER OF GRAVITY BACK .
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 31 T ABLE 32: OPERA TING WEIGHTS (LBS.) MO DE L S IZ E 3 TON 4 TO N 5 TO N BASIC UNIT DY (Cooling Onl y) 575 58 5 590 DY (Gas/Electric) N04 615 - -.
343615-YTG-B-0308 32 Johnson Controls Unitary Products GUIDE SPECIFICA TIONS GENERAL Units shall be manufactured by Y ork International Unitary Products Group in an ISO 9001 certified facility . Y ork's Sunline Magnum ™ units are convertible single pack- age units.
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 33 Coils: a. Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. S pecial Phenolic coating shall be availab le as a factory option.
343615-YTG-B-0308 34 Johnson Controls Unitary Products OPTIONAL OUTDOOR AIR (Shall be made availa ble by either/or): • ELECTRONIC ENTHALPY AUT OMA TIC ECONO- MIZER - Outdoor and return air dampers that are inter- locked and positioned by a fully-modulating, spring return damper actuator .
343615-YTG-B-0308 Johnson Controls Unitary Produ cts 35.
Subject to change without notice. Pr inted in U.S.A. 343615-YTG-B-0308 Copyright © 2008 b y Johnson Controls, Inc. All righ ts reserved. Supersedes: 343615-YT G-A-0807 Johnson Controls Un itary Produ.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York DY 048 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York DY 048 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York DY 048 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York DY 048 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York DY 048, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York DY 048.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York DY 048. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York DY 048 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.