GENERAL YORK M odel DCG uni ts ar e sin gle pack age ai r co ndit ione rs with ga s heat desig ned fo r outd oor in stal lati on on a roof top or a slab . The units are completely assembled on rigid, permanently attached base rails. All piping, refrigerant charge, and electrical wiring is factory-installed and tested.
Gene ral ... .... .... ...... .......... .......... .......... .......... .......... .......... ... 1 Inspe ction.......... .......... .......... .......... .......... .......... .......... ....... 1 Refere nce ..... .......... .......... .......... .
LIMIT A TIONS These unit s must be instal led in a ccor dance w ith th e curren t editi ons of the follo wing na ti onal and loc al safet y codes: In the U. S.A.: 1. Natio na l Elec tr ical Code ANSI /N F P A No. 70. 2. Nationa l Fu el Ga s Cod e Z223 .
The supply and return air duct systems should be designed for the CFM and static requirements of the job. They should NOT be sized to match the dimensions of the duct connections on the unit. CAUTION: When fastening ductwork to the side duct flanges on the unit, insert the screws through the duct flanges only .
DISCONNECT SWITCH BRACKET FOR UNITS WITH OPTIONAL BEL T -DRIVE BLOWER A specia l brac ket for m ount ing a fiel d-su pplied disconnect swit ch is provid ed in ea ch unit ordered w ith an optional belt -drive supply air bl ower . The brac ket is ship ped ins ide t he blowe r com par tment taped to t he top o f the blowe r ho usin g.
The he ating v alue of the gas may differ with localit y . Th e value shou ld be ch ec ke d with the loca l gas utilit y . NOTE : T here may be a lo cal gas ut ility re quireme nt spe cify ing a mini mum diam ete r fo r gas pipi ng. All uni ts requi re a 1/2 inch p ipe connec tion at the en trance f itti ng.
VENT AND COMBUSTION AIR HOODS The ve nt and co mbust ion air ho ods are sh ipped at tach ed to the blowe r housing in the blo wer compar tment. These ho ods must be inst alled on the o utside of the gas heat a c ces s pane l to ens ure proper unit functi on.
NOTE : I nsta ll f ilters so that “ Air F low” a rrows poin t towa rd the unit . 8. Inst all filt er cover ove r the en d of the hood with o ne scre w (cen t er of ho od ), sec urin g filter s into po s itio n.
FIG 8 - CENTER OF GRA VITY APPROXIMATE CENTER OF GRAVITY FRONT 48-11/32 21 32-1/8 15-1/4 82 1 ⁄ 4 “ X 44 7 ⁄ 8 “ CONDENSER COIL END BACK CORNER C CORNER D CORNER B CORNER A Y DIM. 3-5 TO N 6 T ON Y 19-3/4" 22 " X 40-3/4" 44 " MODELS UNIT SIZ E 036 048 060 072 EV AP .
- SUPPL Y AI R PERFORMANCE - 3 & 4 T on w/ Bel t- Dri ve Bl ower T ABLE 8 UNIT SIZE AIR FLOW CFM Available External Static P ressure - IWG* 0.20 0.
UNIT SIZE AIR FLOW CFM Available External Static P ressure - IWG* 0.20 0.30 0.40 0.50 0.60 0.70 0.80 RPM Watts RPM W at ts RPM Watts RPM W at ts RPM Watts RPM W atts RPM Watts 072 3200 1 150 2325 1 18.
OUTD OOR TEMPERA TURE, ° F SUPERHEA T A T SCROLL COMPRESSOR SUCTION, ° F , AIRFLOW = 400 CFM /T ON INDOOR WB TEMPERA TURE, ° F 55 57 59 61 63 65 67 69 71 73 75 65 25.6 26.8 28 29.2 30.4 31. 6 32.8 33.3 33.9 34.4 34.9 70 20.1 21.7 23.3 24. 9 26.5 28.
OUTD OOR TEMPERA TURE, ° F SUPERHEA T A T SCROLL COMPRESSOR SUCTION, ° F , AIRFLOW = 400 CFM /T ON INDOOR WB TEMPERA TURE, ° F 55 57 59 61 63 65 67 69 71 73 75 65 15.2 18.0 20.9 23. 7 26.5 29.3 32.1 33. 4 34.7 36.0 37.3 70 1 1.9 14.9 17.8 20. 8 23.
DUCT COVERS - Units are shipped with all air duct openings covered. For side duct applications; 1. Remove and discard the supply and ret urn air duct covers. 2. Connect duct work to duct flanges on the rear of the uni t. For bottom duct applicat ions; 1.
COOL ING SYSTEM The c ooli ng sec tion is a c omple te fact ory pac kage utiliz ing a n air-cooled condenser . The system is factory-charged wi th Refr igeran t-22. The scrol l com pres sor is her metically seale d and inte rnally sprun g. Th e scrol l compressors have inherent (internal) prot ection.
The limit switch operates when a high temperatur e con dition , caus ed b y inad equate sup ply air flow , occ urs shut ting down the igni tion co ntro l and cl osing t he mai n gas valve.
PILOT CHECKOUT The pil ot flame sh ould enve lope 3/8 inches of the end of t he flam e sens or . R efe r to Fi gure 12. T o adju st pilo t fla me, (1) rem ove pi lot ad just ment cove r scre w , (2) adjus t the s crew for the pr oper pi lot f lame, (3) be su re to re plac e cov er scre w afte r adjus tment to pr event poss ible g as l eakage .
evapor ator coil ma y vary gre atly , meas urin g th e pr essure drop across a w et coil un der field cond itions woul d be inac curat e. T o ass ure a dry co il, th e scroll compre ssors should be de-ene rgized wh ile th e test i s bein g ru n.
NORMAL MAINT ENANCE CAUT ION: Prior to any of th e follo wing ma intena nce p roce- dures , sh ut off all pow er to t he unit to prev ent person al i njur y . Periodic maintenance normally consists of changing or cleaning filters and (under some conditions) cleaning the main burners.
2. The supp ly ai r blower operates but the draft moto r doe s not when the roo m ther mosta t is se t to ca ll for h eat an d the fan swit ch in the “ON” pos itio n. a . The draft motor has inherent protection. If the motor shell is hot to the touch, wait for the internal overload to reset.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York D7CG 048 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York D7CG 048 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York D7CG 048 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York D7CG 048 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York D7CG 048, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York D7CG 048.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York D7CG 048. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York D7CG 048 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.