279104-YTG-B-0307 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 10 SEER – R-22 MODELS: E*RA036 THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) MODELS: 036-048 (3 PH) MODELS: 060, 090 (3 PH) Due to continu ous product improv e ment, specific ations are subjec t to ch an ge without notice.
279104-YTG-B-0307 2 Unitary Products Group All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provid ed upon request.
279104-YTG-B-0307 Unitary Products Group 3 PROCEDURES: 1. Unit factory charge listed on the unit na meplate includes refri gerant for the condenser , the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V er ify the o rifice size and additional charge required for specific evaportor coil in the system using t he above table.
279104-YTG-B-0307 4 Unitary Products Group - = Not applicable COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL ELECTRI C 2 HEA T KW W RA TED CFM NET MBH SEER W/O TXV SEER WITH TXV 3 EER TOT AL SENS. 3 PH 10 SEER HP WITH MA / MC / N-AH / G2FD E1RA036S(25,46) MA12BN2,4 10 17 FC/MC35B3X 1250 34.
279104-YTG-B-0307 Unitary Products Group 5 * Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up. COOLING CAP ACITY - Up flow , Downflow , & Horizontal Furnac es and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (MIN.
279104-YTG-B-0307 6 Unitary Products Group COP equals MBH output divided by (t ot al KW input x 3.412). HSPF (Heating Seasonal Performa nce Factor) is the total heatin g output during a normal annual usage perio d for heating divided by the total electric power input during the same period.
279104-YTG-B-0307 Unitary Products Group 7 ACCESSORIES Refer to Price Manual for specific model numbers. S tart A ssist Kit (2SA067*) Blower Time Delay - A vailable to increase efficiency when installed. Installs on indoor section and maintains blower for approximately one minute a fter cooling thermostat has been satisfied.
279104-YTG-B-0307 8 Unitary Products Group TYPICAL FIELD WIRING - 3 PH (036 - 060) TYPICAL FIELD WIRING - 3 PH (090) THERMOST A T INDOOR UNIT OUTDOOR UNIT LOW VOLT AGE TERMINAL BLOCK IN AIR HANDLER WITH ELECTRIC HEA T 3,4 DEFROST CONTROL 1 FIELD INST ALLED JUMPER GND.
279104-YTG-B-0307 Unitary Products Group 9 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif f erent than those listed (between 73- 87 F), se.
279104-YTG-B-0307 10 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif f erent than those listed (between 73 -87 F),.
279104-YTG-B-0307 Unitary Products Group 11 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif f erent than those listed (between 73- 87 F), s.
279104-YTG-B-0307 12 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MODEL NO E1RA036S(25 ,46) EV APORA TOR COIL MODEL NO F2RP/F2FP036 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
279104-YTG-B-0307 Unitary Products Group 13 Multipliers for determining the performance with other indoor sections . HEA TING P ERFORMANCE DA T A CONDENSING UNIT MODEL NO E2RA048S(25 ,46) EV APORA TOR COIL MODEL NO F2RP/F2FP048 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
279104-YTG-B-0307 14 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MODEL NO E1RA060S(25 ,46) EV APORA TOR COIL MODEL NO G2FD060(S,H)24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
279104-YTG-B-0307 Unitary Products Group 15 NOTES.
Subject to change without notice. Printed in U.S.A. 279104-YTG-B-0307 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 279104-YTG- A-1 106 Unitary 5005 Norman Product Y .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York 060 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York 060 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York 060 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York 060 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York 060, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York 060.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York 060. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York 060 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.