RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 1 FM 4/08 Configuring the EZ-ZONE ® RUI/Gateway 1.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 2 FM 4/08 3. Some notables regarding the graphic above. In the steps that follow we are going to focus on four of the prompt s shown: a.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 3 FM 4/08 9. Provide a name for the channel. 10. In this example the device driv er selected will be “Modbus Ethernet”.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 4 FM 4/08 11. Select the appropriate hardware (network adapter) used on the network.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 5 FM 4/08 13. The next selection allows for multiple master s on the network.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 6 FM 4/08 15. Once the channel configuration is complete it is now time to configure a device (RUI/Gateway).
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 7 FM 4/08 17. Recall that in steps 1-3 it was said that there ar e other configuration st eps that need to be addressed that are not covered in this paper.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 8 FM 4/08 19. If communications fail between KEPServer EX and RUI/Gateway stop polling device.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 9 FM 4/08 21. Use the defaults for port number and IP protocol.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 10 FM 4/08 23. The graphic below sh ows the default Modbus ® word order which also represents the default Modbus ® word order for the RUI/Gateway (Low/High).
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 11 FM 4/08 25. KEPServerEX allows for impor ted tags via a text file.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 12 FM 4/08 27. This concludes the device (RUI/Gateway) configuration.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 13 FM 4/08.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 14 FM 4/08 30. To create similar tags for PV2 - PV4 simply click on the duplicate ic on (circle) and change the fields accordingly (squares).
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 15 FM 4/08 said, look closely at the addresses given in defining the CLSP for each of the four PM controls.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 16 FM 4/08 34.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 17 FM 4/08 36.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 18 FM 4/08 38. Changing an element in the assembly is EZ. A new tag was created as shown below.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 19 FM 4/08 39.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 20 FM 4/08 42.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Watlow Electric RUI/Gateway è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Watlow Electric RUI/Gateway - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Watlow Electric RUI/Gateway imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Watlow Electric RUI/Gateway ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Watlow Electric RUI/Gateway, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Watlow Electric RUI/Gateway.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Watlow Electric RUI/Gateway. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Watlow Electric RUI/Gateway insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.