Installation Instructions and User Guide for the Frostex Pipe Freeze Protection System Using the 9800 FlexFit Plug Kit Directives d’installation et Guide de l’Utilisateur du Système Frostex de Pr.
Contents Five Important Safety Warnings 1 General Instructions 2 Installation Instructions 2 Periodic Inspections 8 T roubleshooting 8 Limited Warranty 9 Before Y ou Begin Make sure your 9800 FlexFit Plug Kit is complete.
Five Important Safety Warnings Follow all five of these instructions to prevent fire or shock: 1. Use the correct heating cable. • Use only braided versions of Frostex heating cable. • Earlier versions of Frostex heating cable with no braid are not compatible.
General Instructions • Observe the safety warnings on page 1. Follow the installation steps (pages 2–7) in the exact order given. • T o ensure the plug is properly connected, do not assemble at temperatures below 0°F (–18°C).
T able 2. Plastic Pipe Number of heating cable runs required 1C. Calculate the total length of heating cable required. Multiply the number of heating cable runs by your pipe length. Add one extra foot (30 cm) for each valve in your line. Add one extra foot (30 cm) for the distance to the power connection.
4 Step 2. Install the end seal. Note: The end seal can only be used once, so do not install it until step 2D. Heating Cable Construction Clear plastic wrap Black core (bus wires inside) Braid Blue jack et 2A. Prepare the heating cable. Cleanly cut off one end of the heating cable.
5 Step 3. Install the 9800 FlexFit plug. Cable guide Ground contact Indicator post Back wall Cov er T E ST Indicator light Ground-fault unit Reset button T est button K eep d ry Ga rder a u s ec 3A. Prepare the cable. Cleanly cut off the end of the cable.
Step 4. Attach the heating cable to the pipe. 4A. Prepare to install the heating cable. Begin the installation at the electrical outlet. Leave at least 1 foot (30 cm) of extra heating cable so the ground-fault unit can be secured to the outside of the thermal insulation, as shown in Figures 1 and 2.
Step 5. Install the insulation. Thermal insulation must be used. It protects the Frostex heat- ing cable from damage and helps keep the pipes from freezing. Before you insulate, be sure the Frostex heating cable is undamaged—no nicks or cuts—and the braid is intact.
Periodic Inspections Each month • T est the 9800 FlexFit plug as described in Step 6B. Periodically Each time you plug in the system, and at least once a year , do the following: • Check the entire Frostex system for signs of damage.
Limited Warranty T yco Thermal Controls warrants all Frostex self-regulating heating cables and compo- nents against faulty workmanship and use of defective materials for two (2) years from the date of purchase. This warranty can be amended only by a written instru- ment signed by a duly authorized officer of T yco Thermal Controls.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Tyco 9800 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Tyco 9800 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Tyco 9800 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Tyco 9800 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Tyco 9800, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Tyco 9800.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Tyco 9800. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Tyco 9800 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.