WSHP-DS-6 March 2000 Water Source Heat Pump Water-to-Water Model WPWD WSHP-DS-6.
2 Introduction The WPWD product is a heating and cooling hydronic fluid water-to- water heat pump capable of pro- ducing water temperature up to 130 F or temperatures down to 25 F. This extended operating range offers great opportunities in commercial, residential and indus- trial applications.
3 Introduction 2 Features and Benefits 4 Model Number Description 7 General Data 8 Application Considerations 9 Electrical Data 18 Performance Data 19 Dimensional Data 25 Wiring Diagram 28 Accessory O.
4 General The water source heat pump model WPWD (water-to-water) offers a range of capacities from 2 tons to 6 tons. All units are housed in one standard compact cabinet. Cabinet The cabinet, which allows easy ac- cess for installation and service, is constructed of heavy gauge metal.
5 Controls Features and Benefits Lockout Relay 50 VA Transformer 24 VAC Contactor Compressor Run Capacitor 2 Amp Fuse (for use with desuperheater option) Ground 10 Pole Terminal Strip Low Voltage Ther.
6 Cold water (Supply) Hot water (Supply) Water heater hook-up kit with drain valve from Desuperheater to Desuperheater Desuper-out Isolation Valves (by others) Desuper-in Desuperheater Option The desuperheater option is a heat recovery system packaged within the water-to-water unit.
7 Model Number Description Digits 1 & 2: Product Type WP = Trane Commercial Water Source Heat Pump Digit 3: Product Configuration W = Water-to-Water Digit 4: Development Sequence D Digits 5-7: Unit Nominal Capacity 024 = 24.0 MBh 036 = 36.0 MBh 042 = 42.
8 General Data Table G-1: Physical Data (English) Model: WPWD 024 036 042 048 060 072 Unit Size Width of cabinet (in) 23 23 23 23 23 23 Width of cabinet and connections (in) 24.8 24.8 24.8 24.8 24.8 24.8 Height (in) 24.3 24.3 24.3 24.3 24.3 24.3 Depth (in) 23.
9 Application Considerations Closed Loop System Closed loop systems (both ground source and surface water) provide heat rejection and heat addition to maintain proper water source temperatures. Operating and maintenace cost are low because an auxillary fossil fuel boiler and cooling tower are not required to maintain the loop temperature.
10 Application Considerations Open Loop System Where an existing or proposed well can provide an ample supply of suitable quality water, ground water systems may be very efficient. (See Figure 7) Operation and benefits are similar to those for closed loop systems.
11 Source Side vs. Load Side Application Considerations Source vs. Load The model WPWD water-to-water system contains two water to refrig- erant heat exchangers. The two heat exchangers enable the system to be divided into a source and load separation.
12 Closed Loop Geothermal Application Considerations (Closed) Ground Loop Heat Exchanger Geothermal Space Heating / Cooling T emperature Refrigeration Equipment Hydronic Ice Melting Via Unit a W ater-to-W ater Geothermal Integrated System The Trane ground source heat pump is highly efficient in service station applications.
13 Fresh Air Ventilation Application Considerations Water-Out (source) Water-In (source) Water-Out (load) Water-In (load) Exhaust Air Fresh Air (Closed) Ground Loop Heat Exchanger Geothermal Space Hea.
14 Fresh Air Ventilation Mechanical Application Considerations HOT W A TER COIL EXHAUST AIR OUTSIDE AIR AIR HANDLER AIR HANDLER EXHAUST AIR TO HE A T PU MPS EXHAUST AIR FROM TOILET RMS WPWD AUTOMA TIC.
1 2 3 5 4 6 7 Central Pump Application Ball valves should be installed in the supply and return lines for unit isolation and unit water flow rate balancing (if an auto- matic flow device is not selected).
16 Well Water Systems Application Considerations 7 6 2 3 4 5 Figure 11: Well water installation 1 9 8 S u p p l y O v e r f l o w R e t u r n General A well water application involves an open loop water supply . The water is drawn from an open well or pond into the unit.
17 Earth Coupled Application Ball valves should be installed in the supply and return lines for unit isolation. Flexible hoses may be used to connect the water supply and return lines to the water inlets and outlet s. These hoses reduce possible vibration between the unit and the rigid system.
18 Electrical Data Table E-1: Electrical Data Model: WPWD 024 036 042 048 060 072 Voltage 208-230/60hz/1phase Compressor RLA 11.4 15 18.4 20.4 28 32.1 Compressor LRA 56 73 95 109 169 169 Minimum Circuit Ampacity 16 21 25.8 28.6 39 45 Max Fuse Size 25 30 40 45 60 70 Aux Pump Amps 2.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Trane WSHP-DS-6 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Trane WSHP-DS-6 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Trane WSHP-DS-6 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Trane WSHP-DS-6 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Trane WSHP-DS-6, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Trane WSHP-DS-6.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Trane WSHP-DS-6. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Trane WSHP-DS-6 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.