Manuale d’uso / di manutenzione del prodotto 4YCY4024A del fabbricante Trane
Vai alla pagina of 29
© 2008 Trane Pub. No. 22-1797-03 Product Data 4YCY4024A through 4YCY4060A Single Packaged Convertible Gas/Electric 14 SEER 2 - 5 Ton, 40 - 120 KBTU R-410A 22-1797-03.
2 It's Hard to Stop a Trane. Single Packaged Convertible Gas/Electric System Trane offers a complete family of packaged gas/electric heating and cooling sys- tems, designed to give you the unbeatable combination of energy efficiency and lower operating costs.
3 Contents Optional Equipment Listing 4 General Data 5 Performance Data Cooling 9 Indoor Fan 11 Typical Wiring 15 Optional Equipment 18 Dimensional Data 23 Mechanical Specifications 29.
4 Optional Equipment Listing OPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [ ✓ ✓ ✓ ✓ ✓ ] indicates accessories included) Hinged Filter Access Door (4YCY4024-036) 8 ................................................................ BA Y ACCDOR1A[ ] Hinged Filter Access Door (4YCY4042-060) 8 .
5 MODEL RA TED Volts/PH/Hz Performance Cooling BTUH j Indoor Airflow (CFM) Power Input (KW) EER/SEER(BTU/Watt-Hr .) n Sound Power Rating [dB(A)] 8 Performance Heating k Input BTUH - 1st Stage (Natural Gas) p Input BTUH - 2nd Stage (Natural Gas) p AFUE T emp.
6 General Data MODEL RA TED Volts/PH/Hz Performance Cooling BTUH j Indoor Airflow (CFM) Power Input (KW) EER/SEER(BTU/Watt-Hr .) n Sound Power Rating [dB(A)] 8 Performance Heating k Input BTUH - 1st Stage (Natural Gas) p Input BTUH - 2nd Stage (Natural Gas) p AFUE T emp.
7 General Data 1 1 1 1 1 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I. Standard 270. 2 2 2 2 2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft.
8 General Data MODEL RA TED Volts/PH/Hz Performance Cooling BTUH j Indoor Airflow (CFM) Power Input (KW) EER/SEER(BTU/Watt-Hr .) n Sound Power Rating [dB(A)] 8 Performance Heating k Input BTUH - 1st Stage (Natural Gas) p Input BTUH - 2nd Stage (Natural Gas) p AFUE T emp.
9 Performance Data Cooling 4YCY4036A1/3 A T 1200 NOM CFM (COOLING PERFORMANCE A T INDOOR DRY BULB TEMPERA TURES) OD ID TO T SENS CA P A T ENTERING DB TEMP TO T AL AMB WB CAP 72 75 78 80 KW 85 59 34.5 28.8 32.4 34.5 34.5 2.7 63 36.0 23.4 27.0 30.5 32.9 2.
10 Performance Data Cooling 4YCY4048A1/3 A T 1600 NOM CFM (COOLING PERFORMANCE A T INDOOR DRY BULB TEMPERA TURES) OD ID TO T SENS CA P A T ENTERING DB TEMP TO T AL AMB WB CA P 72 75 78 80 KW 85 59 45.3 38.2 42.9 45.3 45.3 3.6 63 47.2 31.0 35.7 40.5 43.
11 Indoor Blower Performance Indoor Fan Performance 4YCY4024A Down Airflow Horizontal Airflow 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Watts 52 66 89 115 140 164 186 206 229 259 300 CFM 706 716 727 733.
12 Indoor Blower Performance Indoor Fan Performance 4YCY4042A Down Airflow Horizontal Airflow 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Watts 162 173 197 226 256 285 313 343 383 440 525 CFM 1058 1062 10.
13 Indoor Fan Performance 4YCY4060A Down Airflow Horizontal Airflow 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Watts 200 220 250 285 320 354 386 417 449 487 538 CFM 1407 1394 1396 1403 1408 1408 1402 139.
14 Heating Airflow, horizontal or downflow from .2 to .6” wg. Selection Low Stage High Stage 7-OFF 8-OFF A 600 850 7-ON 8-OFF B 625 900 7-OFF 8-ON C 650 925 7-ON 8-ON D 700 975 4YCY4024A1064 Switch .
15 Typical Field Wiring C 757192i2 B G Y W1 W2 R COMMON FA N COMPRESSOR HEA T FIRST ST AGE HEA T SECOND ST AGE 24V UNIT CONTROL BO X GROUND WIRE 3 PH POWER UNIT NO TE 1 1 PH POWER B G Y W1 W2 R COMMON.
16 Typical Wiring.
17 From Dwg. 21D757165 P02 Typical Wiring.
18 Optional Equipment BA YCURB050A Full Perimeter Roof Mounting Curb for *****018-036A 46 3/8 17 7/8 3 3 5/8 19 1/2 2 3/16 19 1/2 14 1 1/2 38 7/8 15 35 7/8 43 3/8 The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only.
19 Optional Equipment BA YCURB051A Full Perimeter Roof Mounting Curb for *****042-060A 56 1/8 15 7/8 3 10 7/8 19 1/2 4 3/4 19 1/2 14 41 7/8 20 1 1/2 38 7/8 53 1/8 The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only.
20 Optional Equipment The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings.
21 BA YECON101,102A Down Discharge Economizer and Rain Hood (Mounts Over Horizontal Return Air Opening) BA YECON200,201A Horizontal Economizer and Rain Hood Return Duct Roofcurb Relief damper Mist eli.
22 A B C D FULL Y OPEN 2/3 1/3 FULL Y CLOSED BA YDMPR101,102A, 25% Motorized Outside Air Damper (Mounts Over Horizontal Return AIr Opening) BA YOSAH001,002A, 25% Outside Air Damper (Replaces Filter/Coil Access Panel) Optional Equipment The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only.
23 Dimensional Data 4YCY4024A through 4YCY4036A (1 of 3).
24 Dimensional Data 4YCY4024A through 4YCY4036A (2 of 3).
25 4YCY4024A through 4YCY4036A (3 of 3) Dimensional Data.
26 Dimensional Data 4YCY4042A through 4YCY4060A (1 of 3).
27 Dimensional Data 4YCY4042A through 4YCY4060A (2 of 3).
28 4YCY4042A through 4YCY4060A (3 of 3) Dimensional Data.
29 Mechanical Specifications General All units shall be factory assembled, piped, internally wired and fully charged with refrigerant. All units shall be designed to operate at outdoor ambient temperatures as high as 1 15°F. Cooling capacities shall be rated in accordance with A.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Trane 4YCY4024A è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Trane 4YCY4024A - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Trane 4YCY4024A imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Trane 4YCY4024A ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Trane 4YCY4024A, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Trane 4YCY4024A.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Trane 4YCY4024A. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Trane 4YCY4024A insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.