INSTRUCTION MANUAL FOR 500A/102A/152A/202A POWER SUPPLY Document: 83-493-001 Rev. K TDK-Lambda Americas 405 Essex Road, Neptune, NJ 07753 Tel: (732) 922-9300 Fax: (732) 922-9334 Web: www.
THIS PAGE INTENTIONALLY BLANK.
ONE YEAR WARRANTY TDK-Lambda Ameri cas, Inc. (405 Essex Road, Nept une, N.J. 07753), warrants that the uni t is free from defect s in material or workmanship for a period of ONE YEAR from the date of initial sh ipment. TDK-Lambda Am ericas Inc. will service and, at its option, repair or replace pa rts which prov e to be defe ctive.
TDK-Lambda MANUFACTURER'S PRODUCT DECLARATION INTENDED PURPOSE (USE) The Power Supplies described by this manual are defined by TDK-Lambda Americas Inc. as a component for use in the composition of an apparatus as defined in Article 1 (1) of the EMC Directive (89/336/EEC).
TDK-Lambda Description of symbols used in product labeling SYMBOL PUBLICATION DESCRIPTION EC Council Directive 93/68/EEC European Community Conformity Assessment Product Mark IEC 348 Attention, consult Accompanying documents IEC 60417-1-5036 Dangerous voltage IEC 60417-1-5019 Protective earth (e.
ELECTRICAL STANDARDS All company primary standards are either certif ied or are traceable to certification by the National Institute of Standards and Technology. CLAIM FOR DAMAGE IN SHIPMENT This instrument received comprehensive mechanical and electrical inspection before shipment.
9 83-493-001 Rev. K TABLE OF CONTENTS CHAPTER 1 IN TRODUCTION ......................................................................................................... ...............1 1.1 DESCRIPTION ..................................................
10 83-493-001 Rev. K CHAPTER 5 A PPLICATIONS ......................................................................................................... ..............16 5.1 DETERMINING CAPACITOR CHARGE TIME..............................................
83-493-001 Rev. K 1 Cont r o l & Aux . Pow er INPUT/POWER PFC / Fuses Inr ush Limi t High Freq. Res on ant Inver ter Step-u p Tran sfor mer HV Re c t.
83-493-001 Rev. K 2 CHAPTER 2 SPECIFICATIONS 2.1 AVERAGE CHARGING RATE 500J/s, 1000J/s, 1500J/s, 2000J/s at rated Output Voltage 2.2 PEAK CHARGING RATE 550J/s, 1100J/s, 1650J/s, 2200J/s at rated Output Voltage 2.3 NUMBER OF MODELS IN SERIES 12 Standard (others at extra cost) 2.
83-493-001 Rev. K 3 2.9 POWER FACTOR Non PFC PFC All models 0.65 0.98 Table 2-3 Power Factor 2.10 EFFICIENCY Better than 85% 2.11 STORED ENERGY Less than 0.3 Joules all models 2.12 STABILITY 0.2% TO 300 Hz. For higher repetition rates, consult factory 2.
83-493-001 Rev. K 4 2.22 ACCESSORIES • Detachable 8 feet (2.4 meters) HV Cable (see Table 2.1) • 15 pin “D” plug mating control connector • Operating Manual 2.23 OPTIONS 2.23.1 Suffix –SYS Parallel Operation 2.23.2 Suffix –LH “Low Inhibit” - A +10 to 15 volt (high) signal will allow power supply operation.
83-493-001 Rev. K 5 D Figure 2-1 Mechanical Dimensions for 500A, 102A, 152A Outputs up to 6KV (for grounding instructions see SECTION 3.6).
83-493-001 Rev. K 6 Figure 2-2 Mechanical Dimensions for 500A, 102A, 152A Outputs from 7KV to 40KV (for grounding instructions see SECTION 3.6).
83-493-001 Rev. K 7 Figure 2-3 Mechanical Dimensions for 202A Outputs up to 6KV (for grounding instructions see SECTION 3.6).
83-493-001 Rev. K 8 Figure 2-4 Mechanical Dimensions for 202A Outputs from 7KV to 40KV (for grounding instruction see SECTION 3.6).
83-493-001 Rev. K 9 CHAPTER 3 INSTALLATION 3.1 INITIAL INSPECTION The shipping container should contain the following items: power supply, HV output cable, male 15-pin “D” remote control connector and operator’s manual. Examine the items immediately for damage.
83-493-001 Rev. K 10 TB 1 L1 CO M L2 23 0 V A C 11 5 V AC TB 1 L1 CO M L2 11 5-2 3 0 VA C Figure 3-1 Input AC Power Connection NON-PFC Version Figure 3-2 Input AC Power Connection, PFC Version 3.4 POWER CORD SPECIFICATION: Use wire with minimum .064 inches (1.
83-493-001 Rev. K 11 3.5 CONNECTING HIGH VOLTAGE OUTPUT POTENTIAL LETHAL VOLTAGE Ensure that the power supply is off and disconnected from the input power and never operate the power supply without a load capacitor. Make sure that all load capacitors are discharged and shorted to ground before making any connections.
83-493-001 Rev. K 12 3.6 GROUNDING THE PRODUCT 3.6.1 GROUNDING OF INPUT LINE The supply is grounded through the ground terminal of the input connector. A protective ground connection by the way of the grounding conductor in the input terminal is essential for safe operation.
83-493-001 Rev. K 13 CHAPTER 4 OPERATION 4.1 REMOTE CONTROL The Series 500A/102A/152A/202A is easily controlled through the remote connector on the input panel of the unit. Only the ENABLE/RESET, V PROGRAM and GND signals are required for operation. The remaining signals are provided for status monitoring and fault diagnosis.
83-493-001 Rev. K 14 Figure 4-1 Example of Interface Connection.
83-493-001 Rev. K 15 4.2 INITITIAL CHECK-OUT PROCEDURE LETHAL VOLTAGES PRESENT ONLY QUALIFIED PERSONNEL TRAINED IN THE SA FETY ASPECTS OF HIGH VOLTAGE SHOULD PERFORM INITIAL CHE CKOUT PROCEDURES. The power supply should have no visible damage or defects and the cover should be securely fastened.
83-493-001 Rev. K 16 Peak C har ge R ate = C - O U TP U T LO A D C A P A C I TO R 1 2 CV 2 T C V - PRO G R A M M ED OU TPU T V O LT A GE A v e rag e C h ar g e R at e = T C AN D T P A R E SH OW N I N .
83-493-001 Rev. K 17 A series terminating resistor (or series inductor or clamp diode) must be added as shown if the average value of the peak current exceeds 110% of the normal output current. When choosing Rs, ensure it can withstand the full output voltage across it as well as the power dissipation caused by discharging Co (see Table 5.
83-493-001 Rev. K 18 5.4 MEASURING HIGH VOLTAGES A sample of the output voltage is available in the REMOTE connector. If it is desired to measure the HV output externally, care must be taken to understand the accuracy of the measurement.
83-493-001 Rev. K 19 Figure 5-3 HV Bias Measurements 5.5 DETERMINING AC LINE CURRENT IL = Line current P = Average output power VL = Line voltage PF = Power factor (.65 min) EFF = 0.85 Ex: A 152A operating from 115V – 10% and delivering 1000W average.
83-493-001 Rev. K 20 5.7 LONG CHARGE TIME WITH POWER FACTOR CORRECTED (PFC) UNITS It is advised that you consult the factory if this type of operation is required. On supplies with active Power Factor Correction there is a limit to the length of the charge time.
83-493-001 Rev. K 21 CHAPTER 6 MAINTENA NCE AND CALIBRATION 6.1 SAFETY PRECAUTIONS ONLY QUALIFIED PERSONNEL TRAINED IN THE SAFETY ASPECTS OF HIGH VOLTAGE SHOULD PERFORM CALIBRATION. The calibration steps described in this section require operation of the power supply with the cover removed.
Product Name: UNIVOLT N 61 B Revision Date: 20Mar2007 Page 1 of 9 __________________________ __________________________ __________________________ __________________________ ______________ MATERIAL SA.
Product Name: UNIVOLT N 61 B Revision Date: 20Mar2007 Page 2 of 9 __________________________ __________________________ __________________________ __________________________ ______________ SECTION 4 FIRST AID MEASURES INHALATION Remove from further exposure.
Product Name: UNIVOLT N 61 B Revision Date: 20Mar2007 Page 3 of 9 __________________________ __________________________ __________________________ __________________________ ______________ Response Center can be reached at (800)424-880 2. PROTECTIVE MEASURES Avoid contact with spilled material.
Product Name: UNIVOLT N 61 B Revision Date: 20Mar2007 Page 4 of 9 __________________________ __________________________ __________________________ __________________________ ______________ PERSONAL PR.
Product Name: UNIVOLT N 61 B Revision Date: 20Mar2007 Page 5 of 9 __________________________ __________________________ __________________________ __________________________ ______________ Flammable L.
Product Name: UNIVOLT N 61 B Revision Date: 20Mar2007 Page 6 of 9 __________________________ __________________________ __________________________ __________________________ ______________ data for structurally similar materials.
Product Name: UNIVOLT N 61 B Revision Date: 20Mar2007 Page 7 of 9 __________________________ __________________________ __________________________ __________________________ ______________ DISPOSAL RE.
Product Name: UNIVOLT N 61 B Revision Date: 20Mar2007 Page 8 of 9 __________________________ __________________________ __________________________ __________________________ ______________ HYDROTREATE.
Product Name: UNIVOLT N 61 B Revision Date: 20Mar2007 Page 9 of 9 __________________________ __________________________ __________________________ __________________________ ______________ ---------- .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
01000680revD.sch-1 - Wed Jul 22 09:59:20 2009.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il TDK 500A è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del TDK 500A - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso TDK 500A imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul TDK 500A ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il TDK 500A, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del TDK 500A.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il TDK 500A. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo TDK 500A insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.