D500-0 7-00 1 I56-432-1 1R DH500ACDC Intelligent Air Duct Smoke Detector Housing INST ALLA TION AND MAINTENANCE INSTRUCTIONS 3825 Ohio A venue , St. Charles, Illinois 60 174 1-800-SENSOR2, F AX: 63 0-377-6495 www .
D500-0 7-00 2 I56-432-1 1R The DH500A CDCs ar e built to operate on 120/240 V A C or 24 V A C/DC. T wo form-C (SPD T) relay contacts are av ail- able for control purposes. T wo LEDs on each detector latch on to pro vide a local alarm indication. R emote alarm indi- cation is made possible b y using the auxiliary alarm output (see Figur e 5).
D500-0 7-00 3 I56-432-1 1R Exception: Where it is physically impossible to locate the detector accordingly , the detector can be positioned closer than six duct widths , but as far as possible from the open- ing, bend, or deflection plates. Step 3. Mount Duct Housing R emov e the duct housing cover .
A. Installation for Ducts Less Than 8 Feet Wide 1. If the inlet tube is longer than the width of the air duct, drill a 3/4-inch hole in the duct directly opposite the hole alr eady cut for the inlet tube. If the inlet tube is shorter than the width of the air duct, install the end cap into the inlet tube as shown in Figure 3.
av ailable at most plumbing supply houses, may be used. This flange/connector mounting technique makes the initial installation easier because a 1- inch to 1-1/4-inch hole may be drilled where the flange/connector will be used. It is easier to push the inlet tube through the lar ger hole .
ALARM SIGNAL (+) AUX POWER (–) 2 6 (+) (–) DUCT DETECTOR DH500ACDC PA400 (OPTIONAL) AUDIBLE ALERT ALARM SIGNAL (+) AUX POWER (–) 2 6 (+) (–) DUCT DETECTOR DH500ACDC RA400Z (OPTIONAL) REMOTE (L.
Step 7. Per form Detector Check 7.1 Air Flow 1. T o verify sufficient sampling of ducted air , use a manom- eter to measure the differential pr essure created from air flo w acr oss the sampling tubes. The pr essure should measure no less than 0.0 1 inches of w ater and no greater than 1.
Step 8. Install the Cover Install the cover using the four scre ws . Be certain filters are installed as specified in Step 6. Make sure that the cover fits into the base gr oove and that all gaskets ar e in their proper positions. Tighten the four cov er scre ws to 1 0 in-lbs .
1. T urn off power to the system. 2. R emove and inspect sampling tube filter s. 3. If filters ar e heavily coated with dirt, r eplace them with new filter s. If they ar e not heavily coated, use a vacuum cleaner or compressed air nozzle to remo ve dust, then install the filters .
A ccessories P art No. R emote LED RA400ZA Piezo Alert Sounder P A400 R eplacement Filter s F36-05-00 Magnet M02-04-00 End Plug F or Sampling T ube P48-2 1-00 Installation Kit (P arts bag) A2650-0 1 I.
Sy stem Sensor warrants its enclosed air duct smoke detector to be free from defects in materials and workmanship under normal use and ser- vice for a period of three y ears fr om date of manufactur e. S ystem Sensor makes no other e xpress warr anty for this air duct smok e detector .
D500-0 7-00 12 I56-432-1 1R © 200 1 S ystem Sensor DETECTOR TEST LOG Detector Identification Infor mation Manufacturer and Serial Date Detector Model:______________________ Number: __________________.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il System Sensor DH500ACDC è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del System Sensor DH500ACDC - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso System Sensor DH500ACDC imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul System Sensor DH500ACDC ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il System Sensor DH500ACDC, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del System Sensor DH500ACDC.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il System Sensor DH500ACDC. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo System Sensor DH500ACDC insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.