INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS WL423 WL484 WL602 Manual : 2100-400 Supersedes: File: V olume III T ab 16 Date: 01-31-02 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned.
Figures Figure 1 Unit Dimensions ...................................... 3 Figure 2 Fresh Air Damper Assembly ................... 6 Figure 3 Mounting Instructions ............................... 8 Figure 4 Electric Heat Clearance ......................
Manual 2100-400 Page 1 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Manual 2100-400 Page 2 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE WL 42 3 – A 10 X N X X X A NOTE: All vent options are without exhaust capability.
Manual 2100-400 Page 3 FIGURE 1 UNIT DIMENSIONS MIS-1286 l e d o M h t d i W ) W ( h t p e D ) D ( - g i e H t h ) H ( y l p p u Sn r u t e R EF G I JKL M N O P Q R S T A BCB 2 4 L W 8 4 L W 0 6 L W 5 7 0 . 2 42 3 4 . 2 25 7 8 . 4 88 8 . 98 8 . 9 28 8 .
Manual 2100-400 Page 4 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75 ° C copper wire. All wiring must conform to NEC and all local codes. These “ Minimum Circuit Ampacity ” values are to be used for sizing the field power conductors.
Manual 2100-400 Page 5 SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
Manual 2100-400 Page 6 FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel. If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position.
Manual 2100-400 Page 7 INST ALLA TION INSTRUCTIONS W ARNING Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death. WALL MOUNTING INFORMATION 1.
Manual 2100-400 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS-947.
Manual 2100-400 Page 9 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 inch minimum spacing is maintained at all points.
Manual 2100-400 Page 10 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS-1051 SEE FIGURE 3 – MOUNTING INSTRUCTIONS SUPPLY AIR DUCT RETURN AIR OPENING RETURN AIR OPENING SUPPLY AIR OPENING BOTTOM MOUNTING BRACKET. MOUNT ON WALL BEFORE INSTALLING UNIT.
Manual 2100-400 Page 11 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS-1050.
Manual 2100-400 Page 12 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current.
Manual 2100-400 Page 13 FIGURE 8 UNIT 24V TERMINAL BOARD MIS-1373A.
Manual 2100-400 Page 14 THREE PHASE SCROLL COMPRESSOR START UP INFORMATION Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.
Manual 2100-400 Page 15 COMPRESSOR CONTROL MODULE The compressor control module is standard on the WL484 and WL602 models covered by this manual and is optional on the WL423 model. The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.
Manual 2100-400 Page 16 REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. TROUBLESHOOTING The suction line temperatures in table above are based upon 80° F dry bulb / 67° F wet bulb (50% R.
Manual 2100-400 Page 17 TABLE 8 RECOMMENDED AIRFLOW * Rated CFM and ESP on high speed tap. l e d o M d e t a R * M F C d e t a R * P S E d e d n e m m o c e R e g n a R w o l f r i A 3 2 4 L W0 0 4 10 3 .0 5 1 1 - 0 0 6 1 4 8 4 L W0 5 5 10 2 .5 8 2 1 - 0 5 7 1 2 0 6 L W0 0 7 10 3 .
Manual 2100-400 Page 18 TABLE 11 OPTIONAL ACCESSORIES WL423-A WL423-B WL423-C WL484-A WL484-B WL484-C WL602-A WL602-B WL602-C t r a P r e b m u Nn o i t p i r c s e D 5 - P O B 5 - D A F B 5 - D A F M.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Bard WL484 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Bard WL484 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Bard WL484 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Bard WL484 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Bard WL484, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Bard WL484.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Bard WL484. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Bard WL484 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.