3 Cont ents General Information ...................................................................... 4 Installation .................................................................................... 5 Operation ....................................
4 Gener al Infor mation Description The Marley Ultra Low-Noise series of fans represent the top in the new generation of super low noise fans—the FRP blades have been developed to meet the most stringent noise limitations. The fans permit variable pitch adjustment at standstill and feature a simplified design.
5 Installation Rotation and Flow Direction The rotation direction is correct when the airflow moves from the convex back (suction surface) of the blade, to the concave side (pressur e surface). Figure 1 shows the conventional clockwise di- rection of rotation and normal direction of airflow as viewed from the dischar ge face of the rotor .
6 Installation 1 0 B 1 0 A 1 5 9 3 7 2 6 10 4 8 Figure 2.
7 Installation T or que hub assembly bolts 11 according to the following table: Fan Diameter inches Flange T ype Bolt T ype Bolt T or que N·m ft·lb 84" to 96" T ype 115 M16 cl. 8.8 230 169 M16 cl. A4-70 126 93 M16 cl. A4-80 168 124 108" to 168" T ype 190 M20 cl.
8 Installation The drive shaft end must remain recessed at least 1 ⁄ 32 " in the hub bore to prevent dangerous rotor vertical translation once retaining bolt 16 has been tightened to the shaft end. Never power the drive shaft with bushing bolts not torqued or bushing improperly positioned.
9 Installation Rotate the blade on its axis until the requir ed pitch angle is ob - tained. Check there is no gap between each blade shaft shoulder and cor - responding pillow block. T or que pillow block bolts 15 according to the following tables, complying with bolt orientation and tightening order as shown in Figure 4.
10 Installation Fan Diameter inches Bolt 15 Bolt T or que N·m ft·lb 84" to 96" M18 282.5 208 108" to 120" M20 400.3 294 132" to 144" M24 679.8 500 The screw class information is shown in the fan documenta- tion part list.
11 Oper ation Prior to Start-Up 1––Make sur e all the pillow blocks are fixed to the hub boss—if any movement of the blocks is detected, do not operate the fan and check the torque of bolts 15 .
12 Oper ation 3––After the r otor has been running for one hour , check the tor que of the hub screws 15 . 4––Repeat the check of screws 15 after 24 hours fr om start-up.
13 Maint enance Maintenance and Operation 1––Inspect the overall fan condition periodically . Inspection intervals depend on fan operating conditions and may vary from a minimum of 2 weeks to a maximum of 6 months. The following components should be specifically inspected when inspecting the overall fan conditions: - Screw tor que.
14 Maint enance Possible Causes of Vibration The actual causes of vibration may change considerably . Some of the most common are as follows. 1–– Unbalance of one or more blades: the vibration cau.
15 Maint enance 9––W or n output shaft bearing: this condition generates vibration on the tip path plane at a frequency equal to the r otor RPM. 10––The fan and/of the structure bolts are not tightened: in this case all the bolts have to be tightened.
16 P ar ts List Item Figure 6 Description Standard Material Standard Protection 1 Blade FRP –– 2 Coupling Flange Steel Epoxy Paint 3 Hub Disk Steel Epoxy Paint 4 Lower Pillow Block Aluminum ––.
17 P ar ts List 16 10B 10A 14 13 12 3 7 4 6 5 12 15 11 8 2 1 17 16 10 9 8 Figure 6.
18 T r oubleshooting T rouble Cause Remedy Low air flow Low power absorption System congestion. Clean the entire system. Obstacles to the air flow . Check the real obstacles area and the inlet shape towards the original design.
.
M0 7 -1126 7 4 01 WES T 129 STR E ET | OVER LAN D P AR K, KANSAS 66213 U N ITE D ST A TES | 913 664 7 400 | spxcooling@spx.com | spxcooling.com In the interest of technological progress, all products are subject to design and/or material c hange without notice.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il SPX Cooling Technologies 07-1126 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del SPX Cooling Technologies 07-1126 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso SPX Cooling Technologies 07-1126 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul SPX Cooling Technologies 07-1126 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il SPX Cooling Technologies 07-1126, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del SPX Cooling Technologies 07-1126.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il SPX Cooling Technologies 07-1126. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo SPX Cooling Technologies 07-1126 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.