APC by Schneider Electric MGE GALAXY 5000 Data Center Grade Three Phase Uninterruptible Power Supply Parallel Module - Guide Specifications 40-130 kVA UPS 1.0 GENERAL 1.1 SUMMARY This specification describes a three-phase, on-li ne, double conversion, solid state Uninterruptible Power System hereafter referred to as the UPS.
outline, connection diagram for external cabling, internal wiring diagram, and written instruction for installation. 1.4 FINAL SUBMITTALS Upon delivery of the UPS system the following submittals shall be included: A. A complete set of installation drawings showing all the information stated in section 1.
UPS Module Operating : 0° to 40°C (32°F to 104°F) Non-Operating : -20° to +45°C (-4°F to 113°F) B. Relative humidity (operating and storage): 0 to 95% non-condensing C. Barometric Pressure: Up to 1000 meters above sea level (up to 2000 meters with ambient temperature less than 28°C) / (up to 12,000 meters above sea level non operating) D.
static switch, battery plant, graphical stat us/control panel, dry contact and communications ports, and synchronizing circuitry as described herein. 2.2 SYSTEM DESCRIPTION A. UPS Design Requirements 1. Output Pow er Continuous Rating : The continuous output power rating of the UPS shall be [ ] kVA at a 0.
+ 1% for loss or return of AC input power or manual transfer at full load 6. Voltage Recovery Time : Return to within 1% of nominal value within 16.67 milliseconds (one cycle) 7. Phase Angle Displacement : 120° + 1° for balanced load; 120° + 3° for 100% unbalanced load 8.
Incoming AC power shall be converted to a regulated DC output voltage by an IGBT (insulated gate bipolar transistor) power factor co rrection (PFC) rectifier. The PFC rectifier shall provide high quality DC power to charge the batteries and power the inverter and shall have the following characteristics: 1.
1. Uninterrupted Transfer : The static bypass transfer swit ch shall automatically cause the bypass source to assume the critical load wit hout interruption after the logic senses one of the following.
o The graphic display shall assist the user by providing step by step help in the user's language. o LED mimic diagram o The mimic diagram shall enable display of installation parameters, configuration, operating status and alarms and indication of operator instructions for switching operations (e.
Bypass voltage Bypass input frequency UPS output voltage (Ph-Ph and Ph-N) UPS output current per phase UPS output frequency UPS output % load UPS output kVA UPS output .
D. Audible Alarm Reset : The UPS shall provide an audible alarm that can be stopped using the user interface. If a new al arm is sensed after the original alarm has been silenced, it will reactivate the audible alarm.
3.2 BATTERY The UPS module shall use a valve regulated s ealed lead acid heavy-duty industrial battery, designed for auxiliary power service in a UPS applic ation. The primary battery shall be furnished with impact resistant plastic cases and housed in a matching cabinet(s) next to the UPS module.
2. RS232 or RS485 JBus/Modbus Card (66061) : The U-Talk protocol shall be used with Solution-Pac 2 for remote monitoring or gracef ul shutdown for most popular file servers. The JBus protocol is used with third party Building Management Systems (BMS) to monitor detailed three-phase information.
160/320/520kVA depending on model selected. Secondary UPS isolation breakers (2 to 6) are standard – must be determined pre-orderd. In cludes: PM800 Meter for SBC System Level Metering. E. 42” Distribution Cabinet: Distribution Cabinets are an avail able option to the System Bypass Cabinets not individual UPS module.
END OF SECTION APC – MGE Galaxy 5000 Specification (60Hz) 14 Effective: June 1, 2008 REV X0 JJG Parallel Module.
SPECIFICATION KEY 2.2 A–1 OUTPUT POWER RATINGS 40 kVA/ 36 kW 50 kVA/ 45 kW 60 kVA/ 54 kW 80 kVA/ 72 kW 100 kVA/ 90kW 130 kVA /117kW 2.
2.2 D-2 BATTERY DC CURRENT 40 KVA 50 KVA 60 KVA 80 KVA 100 KVA 130 KVA ADC At Max End Voltage 109 137 164 219 273 355 3.1 C WEIGHTS AND DIMENSIONS Dimensions (Inches)/ WEIGHT (Lbs.) KVA UPS 40 to 80kVA UPS 100 to 130kVA TOP Entry Battery Height 75.0 75.
3.2D SYSTEM BYPASS CABINET (SBC) - Parallel 28” SBC Cabinet 42” SBC Cabinet kVA 160/320 160/320/520 Metering No Yes (PM800) Input / output Volts 480V 480V Max UPS Modules Up to Two Up to Six Height 75.0” 75.0” Width 28.0” 42.0” Depth 33.4” 33.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Schneider Electric 5000 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Schneider Electric 5000 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Schneider Electric 5000 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Schneider Electric 5000 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Schneider Electric 5000, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Schneider Electric 5000.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Schneider Electric 5000. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Schneider Electric 5000 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.