Manuale d’uso / di manutenzione del prodotto 3222/5725 del fabbricante Samson
Vai alla pagina of 24
Electric Control Valves/ Controller with Electric Actuator Ty pe 3222/ 5724, T yp e 3222/5725 a nd Ty pe 3222/5757 Mounting and Operating Instructions EB 5766 EN Ed it i on J u ly 2008 Type 3222/5725 .
Contents Page 1 Design and principle of operation . . . . . . . . . . . . . . . . . . . 4 1.1 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2 Installation .
EB 5766 EN 3 General safety instructions General safety instructions 4 The control valves may only be mounted, started up or serviced by fully trained and qualified personnel, observing the accepted industry codes and practices. Make sure employees or third persons are not exposed to any danger.
1 Design and principle of operation The control valves consist of a single-seated Type 3222 Globe Valve and either a Type 5757, Type 5757-7 or Type 5724 Controller with Electric Actuator or a Type 5725 Controller with Electric Actuator with safety function.
EB 5766 EN 5 Design and principle of operation Type 3222/5724 Special version for temperatures up to 200 °C and with plug balanced by a bellows Type 3222/5757 1 Valve body 2 Seat 3 Plug 4 Plug stem 5 Valve spring 6 Guide nipple 7 Balancing bellows 8 Balancing piston 10 Controller with electric actuator Fig.
1.2 Technical data 6 EB 5766 EN Design and principle of operation 1. Single-seated Type 3222 Globe Valve Nominal size DN 15 20 25 32 40 50 Version with threaded ends with flanges as flanged body •.
EB 5766 EN 7 Design and principle of operation Nominal size DN 15 20 25 32 40 50 Thread size G ½¾ 1 ––– K VS coefficients Version with female thread 3.6 5.7 7.2 – – – Version with male thread 4 6.3 8 16 20 25 Reduced K VS coefficients 0.
2. Controllers with electric actuators 8 EB 5766 EN Design and principle of operation Type 5757 5724 5725 5757-7 5757 -10 -13 -20 -23 -10 -13 -20 -23 Nominal size DN 15 to 25 15 to 25 15 to 25 32 to 5.
2 Installation Caution! Versions designed to handle temperatures up to 200 °C must be fitted with the dark gray graphite supplied with the valve. Do not use the UDP seals available as accesso - ries as they are only suitable for tempera - tures up to 150 °C.
3 Attaching the actuator to the valve If the actuator has not already been mounted on the valve by the manufacturer or when the original actuator on a valve is to be replaced with a controller with electric actuator, proceed as follows.
4 Electrical connections Upon installing the electrical cables, you are required to observe the regula - tions concerning electrical power in - stallations according to DIN VDE 0100 as well as the regulations of your local power supplier.
The default setting (WE) is configured for an application with a Pt 1000 flow temperature sensor and water flowmeter (see Fig. 3). 4.3 Type 5724/5725 Controller with Electric Actuator Domestic hot wat.
5 Manual override The direction of action and travel can be read off the travel indication scale. 5.1 Type 5757/-7 Controller with Electric Actuator Caution! Only activate the handwheel when the actu - ator is disconnected from the power supply.
6 Operation The controllers with electric actuators are adapted to the required control task by configuration and parameterization per - formed in TROVIS-VIEW Operator Interface: 4 Type 5757-7 : TROVI.
7 Maintenance The control valve is subject to natural wear. Depending on the conditions the valve is op - erated in, it needs to be checked at regular intervals. If leakage to the atmosphere occurs, remove the valve from the pipeline and replace the damaged parts.
8 Dimensions in mm and weights 16 EB 5766 EN Dimensions in mm and weights Nominal size DN 15 20 25 32 40 50 Thread size G ½¾ 1 ––– Pipe Ød 21.
Weights of controllers with electric actuators Type 5757/-7 5724 5725 Weight without valve, approx. kg 0.7 1.1 1.3 EB 5766 EN 17 Dimensions in mm and weights Type 3222/5757(-7), only up to DN 25 Types 3222/5724 Types 3222/5725 Intermediate insulating piece Fig.
9 Appendix 9.1 Wiring for Type 5757-7 (refer to EB 5757-7 EN) Note! The pump output L´ is non-floating (230 V~). Note: Terminals at point of installation, not included in scope of delivery blk black .
EB 5766 EN 19 Appendix or ye rd br blk gr br bl blk 34 6 5 2 1L L ´ N 230 V, 50 Hz VS Pt 1000 Pt 1000 Pt 1000 AS RüS 100/ 1000 Ω 1000 Ω Application with flow, return flow, and outdoor sensors as well as a potentiometer for adjusting the set points Functions WE Configuration Control w.
9.2 Wiring for Type 5757 (refer to EB 5757 EN) Note: Terminals at point of installation, not included in scope of delivery 1) Water flowmeter 2) Flow switch blk black · bl blue · br brown · gr gree.
EB 5766 EN 21 Appendix or ye rd br gr blk + 4(0)...20mA – 230V, 50Hz 5 V GND L N Pt 1000 Operation with Pt 1000 sensor and external set point over an mA signal Functions WE Configuration Hot water tapping recognition 1 F01 - 0 Current input 0 F05 - 0 Current input function 0 F06 - 1 or ye rd br gr blk + 4(0).
9.3 Wiring for Type 5724/5725 (refer to EB 5724 EN) 1) Water flowmeter 2) Flow switch 3) Pump control output or fault alarm output 4) Electromagnet, Type 5725 Domestic hot water heating in instantaneo.
Mechanical engineering applications Appendix EB 5766 EN 23 Pt 1000 L L1 N 5V IN S1 S2 230V, 50Hz +– 4(0) ... 20mA 3) 4) S1 Operation with Pt 1000 sensor and external set point over an mA signal inpu.
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Samson 3222/5725 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Samson 3222/5725 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Samson 3222/5725 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Samson 3222/5725 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Samson 3222/5725, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Samson 3222/5725.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Samson 3222/5725. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Samson 3222/5725 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.