BURNERS MODEL F10 INSTALLATION MANUAL RIELLO 40 SERIES OIL BURNERS RETROFIT APPLICATIONS ONLY NON-RETROFIT APPLICATIONS If this burner is being installed in a packaged unit (ie.
TABLE OF CONTENTS TECHNICAL DATA ........................................... 1 Dimensions ........................................... 1 Specifications ......................................... 1 OIL BURNER COMPONENTS IDENTIFICATION ...................
RIELLO 40 F10 TECHNICAL DATA !_ B O L) D6012 DIMENSIONS Inches 10 5/16 12 8 1/32 3 15/16 5 10 7/16 mm 262 305 204 100 127 265 El 10 inch long (254 mm) tubes also available. SPECIFICATIONS FUEL: No. 2 Fuel Oil FIRING RATE: 1.45 to 2.95 GPH 4.7 to 9.5kg/h EFFECTIVE OUTPUT: 203,000 to 413,000BTU/h 59.
OIL BURNER COMPONENTS IDENTIFICATION RIELLO 40 SERIES F10 BURNER COMPONENTS 1. Lockout indicator lamp and Reset button 2. Primary control 3. Primary control sub-base 4. Pump pressure regulator adjustment screw 5. Motor 6. Capacitor 7. Air adjustment fixing screws 8.
ASSEMBLY OF AIR TUBE TO BURNER CHASSIS The air tube and drawer assembly are shipped in a carton separate from the burner chassis. Choose the proper air tube length to obtain the tube insertion for the specific installation. A) Remove the AIR TUBE and BURNER CHASSIS from their respective cartons.
B) Position the MOUNTING GASKET (3) between the flat surface of the UNIVERSAL MOUNTING FLANGE (10) and the appliance. Line up the holes in the UNIVERSAL MOUNTING FLANGE with the STUDS (4) on the appliance mounting plate and securely bolt the UNIVERSAL MOUNTING FLANGE to the plate.
METHOD 2 - SEMI-FLANGE COLLAR A) Follow item C from METHOD 1. B) Align the air tube and attached adjustable collar so air tube is centered in the burner access hole of the boiler/furnace unit. Mark the center of the two holes in the ADJUSTABLE COLLAR on to the front plate of the heating unit.
The burner may be controlled using either a DIRECT LINE VOLTAGE control circuit (120V AC 60 cycle) OR a LOW VOLTAGE control (24V AC 60 cycle) using a R8038A Honeywell switching relay or equivalent. Using the appropriate diagram below, make electrical connections to burner.
NOZZLE PLACEMENT A) Determine the proper firing rate for the boiler or furnace unit, consid- ering the specific application, then use the Burner Set-up chart on page 12 to select the proper nozzle and pump pressure to obtain the required input from the burner.
ELECTRODE SETTING IMPORTANT: THESE DIMENSIONS MUST BE OBSERVED AND VERIFIED. D6003 5/32" or 4 mm 5/32" to 13/64" or 4 to 5_ .................... -I-- tt_ TURBULATOR SETTING A) Loosen NUT (1), then turn SCREW (2) until the INDEX MARKER (3) is aligned with the correct index number as per the Burner Set-up chart, on page 12.
Riello manometers and vacuum gauges do not require any adaptors, and can be safely connected to the pump ports. An NPT (metric) adapter must be used when connecting other gauge models. D6179 SINGLE LINE (GRAVITY FEED SYSTEM) A) The burner is shipped configured for use in single line applications.
TWO LINE (LIFT SYSTEM) D6008 n 4 -I- 2 LINE (LIFT) SYSTEM - PIPE LENGTHS H 3/8" OD 1/2" OD FT 0.0 1.5 3.0 5.0 6.5 9.5 11 M 0.0 0.5 1.0 1.5 2.0 3.0 3.5 FT I 1151 1oo I 80 I 65 I 50 I 25 I 20 I M _T I 35 3301 30 3301 25 3301 20 2951 15 2301 8 1001 6 65 I Do not exceed pipe lengths indicated in chart.
PUMP PURGE NOTE: to protect the pump gears, it is advisable to lubricate the pump prior to purging a lift system. Apply oil through the VACUUM PORT (C). A) SINGLE LINE (GRAVITY FEED SYSTEM) A) Loosen the bleeder valve (A) until oil flows out. Tighten the bleeder valve securely and start burner.
SETTING THE AIR ADJUSTMENT PLATE A) Regulation of the combustion air flow is made by adjustment of the manual AIR ADJUSTMENT PLATE (1) after loosening the FIXING SCREWS (2 &3).The initial setting of the air adjustment plate should be made according to Column 5 in the Burner Set-up Chart.
COMBUSTION CHAMBER Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the appropriate installation codes (eg. CSA B139 or NFPA #31 ). NON-RETROFIT APPLICATIONS If this burner is being installed in a packaged unit (ie.
-I1 I 12 11 10 18 20 21 22 32 26 47 33 OPTIONAL 29 m.
-rl O I o"1 SPARE PARTS LIST NO. CODE 1 3007234 2 3006992 3 3006571 4 3006993 5 3005847 6 3007077 7 3007568 8 3007028 9 3007202 10 3007162 11 3005719 12 3006925 13 3007203 14 3007029 15 3007156 1.
FOR CANADA PRECAUTIONS AIR FOR COMBUSTION Do not install burner in room with insufficient air for combustion. Be sure there is an adequate air supply for combustion if the boiler/furnace room is enclosed. It may be necessary to create a window to permit sufficient air to enter the boiler/furnace room.
FOR USA PRECAUTIONS AIR FOR COMBUSTION Do not install burner in room with insufficient air for combustion. Be sure there is an adequate air supply for combustion if the boiler/furnace room is enclosed. An opening of at least twice the area of the flue should be available, or one square foot of area for every gallon of firing rate.
Riello Canada Inc. 2165 Meadowpine Boulevard Mississauga, Ontario L5N 6H6 Telephone :905-542-0303 Facsimile :905-542-1525 Toll Free :1-800-387-3898 Riello Corporation of America 35 Pond Park Road Hing.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Riello Riello F10 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Riello Riello F10 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Riello Riello F10 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Riello Riello F10 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Riello Riello F10, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Riello Riello F10.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Riello Riello F10. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Riello Riello F10 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.