Manuale d’uso / di manutenzione del prodotto RSNA-B Series del fabbricante Rheem
Vai alla pagina of 40
FORM NO. S1 1-933 REV . 2 Supersedes Form No. S1 1-933 Rev . 1 RSNA-B SUPER HIGH EFFICIENCY 1 3-SEER SERIES NOMINAL SIZES 2-5 TONS [7 .0-1 7 .6 kW] P ACKAGE A IR C ONDITIONERS.
2 T ABLE OF CONTENTS Unit Features & Benefits ..............................................................................3-4 Model Identification Options ..........................................................................5 - 6 General Data RSNA-B Series .
3 UNIT FEA TURES & BENEFITS—RSNA-B These qualit y feature s are inc luded in the Rhe em P acka ge Air Conditioner 5.
4 UNIT FEA TURES & BENEFITS—RSNA-B SERIES 1. All models feature Copeland ® Scroll ® compressors for maxi- mum efficiency and quiet operation. 2. Louvered condenser compartment for protecting the coil against yard hazards and/or weather extremes.
R S N A — B 036 J K 010 X X Factory Installed Options (See Next Page) Heating Capacity (Factory Installed) 000 = No Resistance Heat 005 = 05 KW Resistance Heat (018-030) 010 = 10 KW Resistance Heat .
6 OPTIONS—RSNA-B SERIES Option Code Side Flow AA No Option AK x F A CT OR Y INST ALLED OPTION CODES Example: RSNA-B036JK000 XX (where XX is factory installed option) Example: No Options RSNA-B036JK000 Example: Options with Sideflow RSNA-B036JK000AK Note: Factory installed economizer is not available on these models.
7 GENERAL DA T A—RSNA-B SERIES Model RSNA-B Series B024JK B030JK B036CK B036JK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 24,800 [7.27] 31,200 [9.
8 GENERAL DA T A—RSNA-B SERIES Model RSNA-B Series B042CK B042JK B048CK B048JK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 42,500 [12.45] 42,500 [12.
9 GENERAL DA T A—RSNA-B SERIES Model RSNA-B Series B060CK B060JK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 60,000 [17.58] 60,000 [17.58] EER/SEER 2 11.1/13 11.1/13 Nominal CFM/ARI Rated CFM [L/s] 2000/1850 [897/873] 2000/1850 [897/873] ARI Net Cooling Capacity Btu [kW] 58,000 [16.
10 GENERAL DA T A—RSNA-B SERIES NO TES: 1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat.
11 SYSTEMS PERFORMANCE—RSNA-B SERIES GR OSS SYSTEMS PERFORMANCE D A T A—RSNA-B024 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 880 [415] 800 [378] 680 [321] 880 [415] 800 [378] 680 [321] 880 [415] 800 [378] 680 [321] DR ➀ .
12 SYSTEMS PERFORMANCE—RSNA-B SERIES GR OSS SYSTEMS PERFORMANCE D A T A—RSNA-B036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481] DR ➀ .
GR OSS SYSTEMS PERFORMANCE D A T A—RSNA-B048 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1760 [831] 1600 [755] 1360 [642] 1760 [831] 1600 [755] 1360 [642] 1760 [831] 1600 [755] 1360 [642] DR ➀ .
INDOOR AIRFLO W PERFORMANCE—208 V OL TS External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—Wet Coil Nominal Cooling Capacity T ons [kW] Motor Speed from Factory Motor Speed RPM 730 775 820 865 905 940 0.
15 AIRFLOW PERFORMANCE—RSNA-B SERIES INDOOR AIRFLO W PERFORMANCE—230 V OL TS External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Delivery/RPM/Watts—230 Volts Side Discharge—Wet Coil Bl.
ELECTRICAL DA T A – RSNA-B SERIES Minimum Circuit Ampacity Minimum Overcurrent Protection Device Size 16/16 20/20 Maximum Overcurrent Protection Device Size 25/25 Compressor Motor No. 1 Volts 208/230 Phase 1 HP 2 1/6 RPM 3450 Amps (RLA) 10.4/10.4 Amps (LRA) Unit Information Unit Operating Voltage Range 54/54 187-253 Condenser Motor No.
B024JK No Heat — — 16/16 20/25 20/25 A10J 24.57/32.76 34.6/40.0 45/52 45/45 60/60 A05J 12.28/16.38 17.3/20.0 24/27 25/25 30/30 44/50 45/50 — — — — — 16/16 20/25 20/25 22/25 25/25 — — — RXQJ- Heater Kit Nominal kW Heater KBTU/Hr @ 208/240 V Heater Amp.
30% 2% 21% 2% 29% 2% 20% 2% CORNER WEIGHTS % OF TO T AL UNIT WEIGHT THERMOST A T WIRING ENTRANCE ELECTRICAL POWER ENTRANCE BLOWER/ EV APORA T OR ACCESS P ANEL SIDE SUPPL Y DUCT OPENING SIDE RETURN DUC.
52 7 / 16 " [1332 mm] FIL TER ACCESS P ANEL (FOR UNIT MOUNTED FIL TER ACCESSOR Y BLOWER/ EV APORA TOR ACCESS P ANEL OUTDOOR COIL PROTECTIVE GRILLE 25 5 / 16 " [643 mm] 10 3 / 16 " [259 mm] 4 3 / 4 " [121 mm] 5 1 / 16 " [129 mm] 1 1 / 8 " [28.
20 TYPICAL INST ALLA TIONS.
COMMON SUPPL Y/RETURN CONCENTRIC AIR DIFFUSER SUPPL Y AIR/PERFORMANCE NO TE: The location of the combination supply and return diffuser should not exceed 10 feet [3.05 m] above the floor level for units @ 1000 CFM [472 L/s] or less and 12 [3.66 m] to 14 feet [4.
DUCT AD APTERS RECT ANGULAR T O R OUND TRANSITIONS (DO WNFLO W) RXMC-CA03 RXMC-CA02 [ ] Designates Metric Con versions 22 ACCESSORIES.
[ ] Designates Metric Con versions RXRE-CAA30 (3 P osition) Provided with enthalpy control, and mixed air sensor . Settings include fully open, fully closed and adjustable mid point.
CFM [L/s] RSNA-B 680 [321] RSNA-B 850 [401] RSNA-B 1020 [481] RSNA-B 1190 [562] RSNA-B 1275 [602] 1500 [708] 1400 [661] 1200 [566] 1000 [472] 800 [378] 1650 [779] 1540 [727] 1320 [623] 1100 [519] 880 [415] Minimum Airflow Model No. Nominal Airflow Maximum Airflow 510 [241] RSNA-B 600 [283] 660 [311] Airflow Pressure Drop, Inches W .
DUCT AD APTER SIDEFLO W SQU ARE T O R OUND TRANSITION RXMC-B A01 Adapts the side rectangular supply and return openings to 14" [356 mm] diameter round openings. Adapters provided with same finish as unit and also provided with thermal insulation.
RXSG-AAA 14 (1 4" [356 mm] High) RXSG-AAA08 (8" [203 mm] High) R OOFCURB (Full P erimeter) RXSG-AAA08, RXSG-AAA 1 4 and RXSG-AAA24 for RSNA-B Series Hinged corners make for fast, easy set-up. NO T f or use with RQKA/RQLA/RQMA P acka ge Heat Pumps.
R OOFCURB (Full P erimeter) (Cont.) [ ] Designates Metric Con versions RXSG-AAA24 (24" [610 mm] High) 27 ACCESSORIES.
[ ] Designates Metric Con versions P A CKA GE AIR CONDITIONERS & GAS/ELECTRIC P A CKA GE UNITS R OOFCURB INST ALLA TION (Full P erimeter) OLD MODEL OLD CURB MODEL NEW MODEL TO OLD MODEL ROOFCURB A.
LIFT KIT—MODEL NO . RXML-A01 The lift kit is intended for temporary installation while the unit is being lifted into position. Kit includes 4 lift brackets.
W ARNING ONL Y ELECTRIC HEA TER KITS SUPPLIED BY THIS MANUF ACTURER AS DESCRIBED IN THIS PUBLICA TION HA VE BEEN DESIGNED, TESTED, AND EV ALU A TED BY A NA TIONALL Y RECOGNIZED SAFETY TESTING A GENCY FOR USE WITH THIS UNIT .
31 WIRING SCHEMA TICS—RSNA-B SERIES.
32 WIRING SCHEMA TICS—RSNA-B SERIES.
33 WIRING SCHEMA TICS—RSNA-B SERIES.
34 WIRING SCHEMA TICS—RSNA-B SERIES.
35 WIRING SCHEMA TICS—RSNA-B SERIES.
36 WIRING SCHEMA TICS—RSNA-B SERIES.
37 NOTES.
38 NOTES.
39 NOTES.
Before pr oceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Pro vincial, and Local codes, regulations, and practices.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Rheem RSNA-B Series è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Rheem RSNA-B Series - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Rheem RSNA-B Series imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Rheem RSNA-B Series ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Rheem RSNA-B Series, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Rheem RSNA-B Series.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Rheem RSNA-B Series. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Rheem RSNA-B Series insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.