Manuale d’uso / di manutenzione del prodotto HI DELTA 992B-2342B del fabbricante Raypak
Vai alla pagina of 66
INST ALLA TION & OPERA TING INSTR UCTIONS CA T ALOG NO. 1000.51 1E Effective: 08-21-08 Replaces: 05-22-08 P/N 241259 Rev . 6 WARNING: If these instructions are not followed exactly , a fire or explosion may result causing property damage, personal injury or death.
2 Rev . 6 reflects the following: Changes to: the wiring diagrams on pages 50 and 51; The addition of: a Pump T ime Delay section on page 44..
WARNINGS 4 BEFORE INST ALLA TION 5 Product Receipt 5 Model Identification 5 Ratings and Certifications 5 Installations at Elevation 5 Component Locations 6 General Information 7 GENERAL SAFETY 8 T ime.
4 D ANGER: Indicates the presence of immediate hazards which will cause severe person- al injury , death or substantial property damage if ignored. WARNING: Indicates the presence of hazards or unsafe practices which could cause severe personal injury , death or substantial property damage if ignored.
5 BEFORE INST ALLA TION Raypak strongly recommends that this manual be re- viewed thoroughly before installing your Hi Delta heater . Please review the General Safety information before installing the heater . Factory warranty does not apply to heaters that have been improperly installed or operated.
6 OPTIONAL FLUE CONNECTION Component Locations Fig. 1: Component Locations – Back Fig. 2: Component Locations – Left Side Panels removed for clarity Fig.
7 General Infor mation Qua nt it y o f Vent Size (i n.) Mode l No. Bur ne rs Gas Va lve s Blowers Flue Intake 992B 11 2 + 1* 2 10 10 1262B 14 3 + 1* 2 12 10 1532B 17 4 2 12 10 1802B 20 4 2 14 10 2002B 23 5 3 14 10 2072B 23 5 3 14 10 2342B 26 5 3 16 10 Bur ne r s p er Va lv e St age s % F ire at St ag e Mode l No.
8 GENERAL SAFETY T o meet commercial hot water use needs, the high limit safety control on this water heater is adjustable up to 210°F . However , water temperatures over 125°F can cause instant severe burns or death from scalds. When supplying general purpose hot water , the rec- ommended initial setting for the temperature control is 125°F .
9 INST ALLA TION INST ALLA TION Installation Codes Installations must follow these codes: • Local, state, provincial, and national codes, laws, regulations and ordinances • National Fuel Gas Code, ANSI Z223.
10 U.S. Installations 1 Can adian I nstalla tions 2 A Clearance abov e grade , veran da, porch , deck, or balcony 1 ft ( 30 cm) 1 ft ( 30 cm) B Clearance to window or door that may b e opened 4 f t ( 1 .
11 In addition, the heater shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation or service (circulator replacement, control replacement, etc.
12 Fig. 8: Minimum Clearances from Combustible Surfaces – Outdoor Installations Combustion and V entilation Air Indoor Units The heater must be supplied with sufficient quantities of non-contaminated air to support proper combustion and equipment ventilation.
13 three or four sheet metal screws (not supplied) equal- ly distributed around the circumference of the duct. All ducting should be self-supported. The filter housing is not designed to support the air duct.
14 b. Not less than the sum of the areas of all vent connectors in the confined space. WARNING: Do not use one permanent opening method if the equipment room is under negative pressure conditions or the equipment is common vented with other gas-fired appliances.
15 5. Remove all plumbing fittings to the header . This will include both inlet and outlet water pipe unions and the pressure relief valve and drain piping. 6. Remove limits, control bulbs and/or thermocou- ples. 7. Remove the eight flange nuts and the in/out head- er from the left-hand side.
16 Failure to exceed 105ºF (41ºC) within 7 minutes may result in the premature failure of the hot surface ignit- er , remote flame sensor , burners and heat exchanger . It can cause operational problems, bad combustion, sooting, flue gas spillage and reduced service life of the vent system.
17 Pressur e Dr op in F eet of Head F eedwater R e gulator Raypak recommends that a feedwater regulator be in- stalled and set at 12 psi minimum pressure at the highest point of the system. Install a check valve or back flow device upstream of the regulator , with a manual shut-off valve as required by local codes.
18 P ota ble Wa ter and Space Heating 1. All piping materials and components connected to the water heater for the space heating application shall be suitable for use with potable water . 2. T oxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water used for space heating.
19 circulate water through the heater from the main sys- tem piping. T o complete the installation of the pool heater , the pool thermostat needs to be installed in the main return wa- ter line, upstream of the heater . This will ensure that the heater will be energized at the right time.
20 shut-off. Close isolation valves and remove water pip- ing from the in/out header on the heater . Drain the heater and any piping of all water that may experience below-freezing temperatures. P ool/Spa Water Chemistr y Wa ter Har dness W ater hardness is mainly due to the presence of cal- cium and magnesium salts dissolved in the water .
21 Gas Supply Connection The heater must be isolated from the gas supply pip- ing system by closing the manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.
22 9. Install a coupling, nipple, union and sediment trap onto the right-hand end of the main gas line and then install the gas line, making sure that a manu- al shut-off valve has been installed within 10 ft of the heater . 10. Replace the left and right front panels on the heater .
23 CIRCUIT BREAKER WHITE GROUND BLACK GREEN AB C Fig. 18: Wiring Connections Check the power source: AC = 108 V AC Minimum, 132 V AC MAX AB = 108 V AC Minimum, 132 V AC MAX BC = <1 V AC Maximum If the heater does not have a factory-wired stage con- troller , it is factory-wired in an on-off configuration with other stage terminals jumpered.
24 D ANGER: SHOCK HAZARD Make sure electrical power to the heater is discon- nected to avoid potential serious injury or damage to components. Fig. 21: On-Off Wiring Connections Fig. 22: 2-Stage Wiring Connections Fig. 23: 3-Stage Wiring Connections Fig.
25 ured to operate in an on-off firing mode. This means that you will connect a single-pole control to stage one of the CPW board. Then jumper the remaining firing stages. For example, if your heater is a Model 1532B, you will jumper stages two, three and four .
26 Combustion Air Su p ply Exh a ust Configuration Heater Venting Category Certified Mate r ials Combustion Air Inlet M ater ial Ver ti ca l N atu r al Draft Ventin g I “B” Ven t From Ins ide Bu i.
27 8. Locate and guard vent termination to prevent acci- dental contact by people or pets. 9. DO NOT terminate vent in window well, stairwell, alcove, courtyard or other recessed area. 10. DO NOT terminate above any door , window , or gravity air intake.
28 5. Remove the screws, retaining ring and rain gasket from top of heater . 6. Remove the screws, flue collar and gasket from the run side of the tee located in the flue box on top of the heater . 7. Reverse the components and reattach in the new location.
29 T er mination The vent terminal should be vertical and should termi- nate outside the building at least 2 ft above the highest point of the roof that is within 10 ft.
30 speed. Do not operate summer exhaust fan. Close fireplace dampers. 4. Place in operation the appliances being inspected. Follow the manufacturer ’s instructions for lighting each appliance. Adjust thermostat so appliance will operate continuously .
31 Air Inlet Max . Len gth* Mode l No. Certified Vent in g Mate r ial Vent Size Max i mum Eq uiv a le n t Vent Le ngt h* Combustion Air Intake Pipe Mate r ial 10” 12” 992B 10” 1262B 1532B 12” .
32 For installations in extremely cold climate, it is re- quired that: 1. The vent must be installed with a slight upward slope of not more than 1/4 inch per foot of hori- zontal run to the vent terminal. In this case, an approved condensate trap must be installed per applicable codes.
33 Flues supported only by flashing and extended above the roof more than 5 ft should be securely guyed or braced to withstand snow and wind loads. The air inlet opening MUST be installed 1 ft above the roof line or above normal snow levels that might ob- struct combustion air flow .
34 Fig. 31: Status LED Indicator Decal Heater Sequence of Operation Models 992B-1262B 1. The black (hot) wire lead goes directly to the main power switch.
35 Ext er n al L ig ht s Li ght Co lor I ndi cati on Power Blue Main power is on Call For H eat Yellow Thermostat is closed Sa fety Re d One or more safe ties is inopera- tiv e Ign i tion Re d Ig ni t.
36 gized by a 120 V AC signal from S-1 on the ignition module for approximately 30 seconds. (The hot surface igniter must draw greater than 3.1 amps while being energized or ignition lockout will occur after three tries.
37 9. 24 V AC is applied to the blue power light located on the status display board. 10. 24 V AC is also applied to the red LED safety shut- down light on the front status board until the safeties have been proven. 1 1. 24 V AC is applied to the alarm circuit (optional).
38 36. After proper air pressure is received in the air plenum, the air pressure switches will close. 37. If there is insufficient air pressure and the air pres- sure switch does not close, a 24 V AC signal is sent to the Universal Diagnostics Board to indicate the fault.
39 60. If ignition module two locks out, a signal will be sent to the Universal Diagnostics Board and to the status display board to indicate an ignition fault. 61. The coil of relay K-5 (N.O.) is now energized with the (K-5) contacts closing downstream of the stage 4 connections.
40 23. When a CFH occurs, a 24 V AC signal is sent to the CFH light on the status panel located on the lower left front of the control compartment. 24. Power is also sent from pin 2 of the stage 1 con- nection to pin P1-3 of the universal diagnostic board.
41 49. When power is sent to gas valve 1 it is also sent to time delay relay 1 (TD-1) which starts a 5-second countdown. 50. After the 5-second countdown from TD-1 and the internal contacts close, time delay relay 2 (TD-2 ) receives 24 V AC. 51. Gas valve 1a is energized allowing the remainder of stage 1 to fire.
42 Ignition Module When additional heat is needed, the combustion air blower starts to purge air from the combustion cham- ber for about 15 seconds. On proof-of-air flow , the air- proving switch closes and the igniter is energized. T o ensure safe operation, the gas valve cannot open until the igniter is verified.
43 Fig. 35: Operating Control Low W ater Cut-Off (Optional) The low water cut-off automatically shuts down the burner whenever water level drops below the level of the sensing probe. A 5-second time delay prevents premature lockout due to temporary conditions such as power fluctuations or air pockets.
UDB F ault Histor y T o view the fault codes in the UDB history file: 1. Press and hold the switch labeled “SW1” for 5 sec- onds to access the fault history . LED 17 will begin to flash when the history has been accessed. See Fig. 41 above. 2. Press the switch labeled “SW2” to scroll through the recorded faults in history .
45 87%-Ef ficiency Boilers – Special Instr uctions Wa ter Piping An 87%-efficiency boiler requires a minimum inlet water temperature of 120ºF (49ºC) to prevent exces- sive condensation in the combustion chamber .
46 WARNING: Contact the vent material manufacturer if there are any questions about the appliance category or suitability of a vent material for Category II, III or IV applications. Using improper venting materials can result in personal injury , death or property damage.
47 Horizontal Thr ough-the-Wall V enting (Categor y IV) WARNING: V ent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under a positive pressure.
48 The stainless steel direct vent cap must be furnished by the boiler manufacturer in accordance with its list- ing (sales order option D-15). Use only double-wall vent pipe and the special gas vent pipes listed for use with category II or IV gas burn- ing boilers, such as the stainless steel Saf-T vent by Heat Fab Inc.
49 Direct V ent - V er tical Vert ica l Ve nt in g Height* Air I nlet Max . Len gth** Mode l Certified Vent in g Mate r ial Vent Size Min. Max . Combustion Air Intake Pipe Mate r ial 10” 12” 992BE.
50 W iring Dia g r am—Models 992B–1262B.
51 W iring Dia g r am—Models 1532B–2342B.
52 ST ART -UP Pre Star t-up Filling System (Heating Boilers) Fill system with water . Purge all air from the system. Lower system pressure. Open valves for normal sys- tem operation, and fill system through feed pressure. Manually open air vent on the compression tank until water appears, then close vent.
53 Prepar ation Check P ower Supply With multi-meter at incoming power , check voltage between: Hot - Common (≈120 V AC) Hot - Ground (≈120 V AC) Common - Ground (< 1 V AC) Attach Manometers to Measure Pr essur es 1. T urn off main gas valve. 2.
54 Safety Inspection 1. Check all thermostats and high limit settings. 2. During the following safety checks leave manome- ters hooked up, check and record. 3. If other gas-fired appliances in the room are on the same gas main, check all pressures on the Hi Delta with all other equipment running.
55 1. Manually close the downstream leak test valve. 2. Open test point A and connect a manometer to it. V erify that there is gas pressure and that it is with- in the proper range (NOTE: must not exceed 14.0 in. WC). 3. Open test point B and connect a rubber tube to it.
56 10. T o restart system, follow lighting instructions in the Operation section. 1 1. Check to see that the high limit control is set above the design temperature requirements of the system. For multiple zones: Check to make sure the flow is adjusted as required in each zone.
57 TR OUBLESHOO TING Ste p 7 Ste p 6 Ste p 5 Step 1 Step 2 Step 3 Step 4 Is there a Call For Heat? Is Disable j um p er intact? ( J1 ) Is there 120VAC at J8 Connecto r on the CPW board? Do the combust.
58 MAINTENANCE Suggested Minimum Maintenance Schedule Regular service by a qualified service agency and maintenance must be performed to ensure maximum operating efficiency .
59 W eekl y For low-pressure heaters, test low-water cut-off device. (With at least one stage of the appliance on, depress the low water cut-off test button, appliance should shut-off and ignition fault light should come on. Depress reset button to reset).
60 APPENDIX Inside Air Contamination All heaters experience some condensation during start-up. The condensate from flue gas is acidic. Combustion air can be contaminated by certain vapors in the air which raise the acidity of the condensate.
61 LIMITED PARTS WARRANTY HI DELTA – TYPES H AND WH MODELS 992B–2342B SCOP E Ray pak, I nc. ( “Ray pak” ) w ar r ants to th e or ig inal ow ner th at all par ts o f th is h ea ter w hic h a re.
62 LIMITED PARTS WARRANTY HI DELTA – TYPE P MODELS 992B–2342B SCOP E Ray pak, I nc. ( “Ray pak ”) w ar r ants to th e o rig in al ow ner th at al l par ts of th is h ea ter w hic h are ac tu a.
63 START-UP CHECKLIST FOR FAN-ASSISTED RAYPAK PRODUCTS This s tart- u p ch ec k lis t i s to b e c o mp l ete ly fil l ed o ut b y t he se rv ic e te ch n ic ia n s tar ting u p th e Ra yp ak Bo i le r o r He ate r for the first time. All in formation may be used for warra nty p urposes an d to ensure that the ins tallation is corre ct.
64 NOTES: _ _____________ ____________ ____________ ___________ ______________ ____________ ____________ ______ _ _____________ ____________ ____________ ___________ ______________ ____________ ______.
65.
ww w .ra y pak.com Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468 Litho in U.S.A..
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Raypak HI DELTA 992B-2342B è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Raypak HI DELTA 992B-2342B - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Raypak HI DELTA 992B-2342B imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Raypak HI DELTA 992B-2342B ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Raypak HI DELTA 992B-2342B, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Raypak HI DELTA 992B-2342B.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Raypak HI DELTA 992B-2342B. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Raypak HI DELTA 992B-2342B insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.