Manuale d’uso / di manutenzione del prodotto HD401 del fabbricante Raypak
Vai alla pagina of 48
INST ALLA TION & OPERA TING INSTR UCTIONS CA T ALOG NO. 1000.52B Effective: 1 1-19-09 Replaces: 09-25-09 P/N 241356 Rev . 3 WARNING: If these instructions are not followed exactly , a fire or explosion may result causing property damage, personal injury or death .
2 Rev . 3 reflects the following: Changes to: Updated T able E on page 14, T able G on page 18, T roubleshooting flowchart on page 35, T able O on page 38.
WARNINGS 4 Pay Attention to These T erms 4 BEFORE INST ALLA TION 5 Product Receipt 5 Model Identification 5 Ratings and Certifications 5 Installations at Elevation 5 Component Locations 6 General Info.
D ANGER: Indicates the presence of immediate hazards which will cause severe personal injury , death or substantial property damage if ignored. WARNING: Indicates the presence of hazards or unsafe practices which could cause severe personal injury , death or substantial property damage if ignored.
BEFORE INST ALLA TION Raypak strongly recommends that this manual be re- viewed thoroughly before installing your Hi Delta heater . Please review the General Safety information before installing the heater .
Fig. 1: Component Locations — Angle View Fig. 2: Component Locations — Left Side Fig. 3: Component Locations — Front (Panels removed for clarity) 6 Component Locations.
General Infor ma tion T able A: Basic Data Model No. Q uantity of Burners V ent Size (in.) Flue Intake HD101 2 4 4 HD151 3 4 HD201 4 5 HD251 5 5 HD301 6 5 HD401 8 6 7 Fig.
GENERAL SAFETY T o meet commercial hot water use needs, the high limit safety control on this water heater will shut off the main gas valve before the outlet temperature reaches 210°F . However , water temperatures over 125°F can cause instant severe burns or death from scalds.
INST ALLA TION INST ALLA TION Installation Codes Installations must follow these codes: · Local, state, provincial, and national codes, laws, regulations and ordinances. · National Fuel Gas Code, ANSI Z223.1- latest edi- tion (NFGC). · National Electrical Code, ANSI/NFP A 70 - latest edition (NEC).
Fig. 7: Minimum Installed Service Clearances — Indoor/Closet Installations The heater must be installed in a manner that will enable the heater to be serviced without removing any structure around the heater . Outdoor Installations These heaters are design-certified for outdoor installa- tion.
area per 20,000 BTUH (1 1 1 mm 2 per kW) of total input rating of all equipment in the room when the opening is communicating directly with the out- do or s o r t hr ou gh ve rt ic al d uc t( s) . Th e t ot al cross-sectional area shall be at least 1 in.
WARNING: Do not use one permanent opening method if the equipment room is under negative pressure conditions or the equipment is common vented with other gas-fired appliances. 1. V entilation of the space occupied by the heater shall be provided by an opening(s) for ventilation air at the highest practical point communicating with outdoors.
13 WARNING: Pressure relief valve discharge piping must be piped near the floor and close to a drain to eliminate the potential of severe burns. Do not pipe to any area where freezing could occur .
14 Low T emper a tur e System Heater requires minimum inlet temperature of 105°F . Consult the following sections for piping details. T emperature & Pr essure Gauge The temperature and pressure gauge is shipped loose for field installation.
15 Fig. 10: Single Boiler — Low T emperature Application (Heat Pump) Primary/Secondary Piping Fig. 1 1: Dual Boiler—Primary/Secondary Piping *Maximum 4 times the pipe diameter or 12”, whichever is less. *Maximum 4 times the pipe diameter or 12”, whichever is less.
16 T able F: Domestic W ater Heater Flow Rate Requirements ∆ T = T emperature rise, °F . ∆ P = Pressure drop through heat exchanger , ft. SHL = System head loss, ft. (System head loss is based on the heater and tank placed no more than 5 feet apart and 50 feet equivalent length of tubing and fittings.
17 Gas Supply Connection CA UTION: The heater and its manual shutoff valve must be disconnected from the gas supply during any pressure testing of the gas supply system at test pressures in excess of 1/2 psi (3.
18 Fig. 13: Sediment T rap Orientation Gas Supply Pr essure A minimum of 4 in. WC and a maximum of 10.5 in. WC upstream gas pressure is required under load and no load conditions for natural gas. A minimum of 1 1 in. WC and a maximum of 13 in. WC is required for propane gas.
19 Install a separate disconnect means for each load. Use appropriate-sized wire as defined by NEC, CSA and/or local code. All primary wiring should be 125% of minimum rating. It is strongly recommended that all individually-pow- ere d contr ol mod ules an d the hea ter sh ould be supplied from the same power source.
20 SINGLE ST AGE T ANKST A T ST AGE 1 CONNECTION A TT ACH ST AGE 1 CONNECTIONS ON HEA TER T O THE SINGLE ST AGE T ANKST A T AS SHOWN IN THE DIAGRAM ABOVE.
Category II . A heater which operates with a non-posi- ti ve v en t st at ic p re ss ur e an d w it h a ve nt g as temperature that may cause excessive condensate production in the vent. Category III . A heater which operates with a positive vent pressure and with a vent gas temperature that avoids excessive condensate production in the vent.
22 T able I: V enting Category Requirements Combustion Air S upply Exhaust C onfiguration V enting Category Certified A ppliance Material Combustion Air I nlet Material From Inside Building (Non-Direc.
23 U. S. Ins tallations 1 Canad ian Insta llati ons 2 A Clear ance above gr ade , v eranda, p orch , deck, or balcony 1 ft (30 c m) 1 ft (30 c m) B Clear ance to window or do or that may be o pened 4 ft (1.
24 ances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimen- tal to the operation of regulators, relief valves, or other equipment.
25 V enting Installation Tips Support piping: · horizontal runs- at least every five (5) feet. · vertical runs - use braces: · under or near elbows Follow items listed below to avoid personal injury or property damage. · Cut nonmetallic intake pipe with fine-toothed hack- saw .
26 Natural Draft V er tical V enting System Installation Natural draft venting uses the natural buoyancy of the h eated flue products to create a thermal driving head that expels the exhaust gases from the flue. The neg- ative draft must be within the range of –0.
27 each appliance. Adjust thermostat so appliance will operate continuously . e) Check the pressure at a pressure tap located 12 in. above the bottom joint of the first vertical vent pipe.
28 Horizontal Thr u-wall V enting System (Categor y III) Installation T hese installations utilize the heater-mounted blower to vent the combustion products to the outdoors. Combustion air is taken from the space and the vent is installed horizontally through the wall to the outdoors.
29 Fig. 21: Direct V ent Horizontal Thru-Wall V enting (Category III) Model No. Appliance Category Certified V enting Material V ent Size (inches) Max. V enting Length (feet) Combustion Air Intake Pipe Material Air Inlet Size (inches) Max. Air Intake Length (feet) HD101 HD151 III Stainless Steel (Gas T ight) 4 100, 4 Elbows Max.
30 Model No. Appliance Category Certified V enting Material V ent Size (inches) Min./Max. V ertical V enting Height (feet) Combustion Air Intake Pipe Material Air Inlet Size (inches) Max.
31 V er tical Direct V ent System Installation T hese installations utilize the heater mounted blower to draw combustion air from outdoors and uses the natural buoyancy of the heated flue products to create a thermal driving head that expels the exhaust gases f rom the flue.
Modulating T emper a tur e Control (Optional) T his heater can be equipped with a Raypak modulat- ing temperature control. For operation with this control, refer to the T emp-T racker Installation and Operating Instructions, Raypak Catalog number 5000.
33 Lo w Wa ter Cut Of f (Optional) The low water cut off automatically shuts down the burner whenever water level drops below the level of the sensing probe. A 5-second time delay prevents premature lockout due to temporary conditions such as power fluctuations or air pockets.
34 WIRING DIA GRAM—MODELS HD101–HD401.
35 YES Ste p 9 HD101-HD401 Troubleshooting YES YES NO NO YES YES NO YES YES NO YES YES NO NO YES NO Ste p 10 YES NO YES YES NO NO YES NO Yes NO YES YES NO S tep 1 S tep 2 S tep 3 Step 4 Step 5 Step 6 .
36 PRE-ST ART -UP Filling System-Heating Hea ter s F ill system with water . Purge all air from the system using purge valve sequence. After system is purged of air , lower system pressure. Open valves for normal system operation, fill system through feed pressure.
37.
38 Check the Gas Supply Pressur e 1. Slowly turn on main gas shut-off valve. 2. Read the gas supply pressure from the manome- te r; m in im um s up pl y pr es su re i s 4 in . WC , recommended supply is 7 in. WC for natural gas ( minimum 1 1.0 in. WC for LP gas).
39 3. Carefully remove 2-stage solenoid. 4. Skip to Step 9 for LO-fire adjustment only . 5. Locate and remove Lo-fire adjustment cap. 6. Carefully remove the spring & weight. 7. Using an allen wrench, turn clockwise to increase and counterclockwise to decrease the HI-fire man- ifold pressure.
40 F ollo w-Up • Safety checks must be recorded as performed. • T urn unit on. After main burner ignition: • Check Manometer(s) for proper reading(s). • Cycle unit several times and recheck readings. • Re-analyze with unit running record or print results.
41 3. Remove the (4) screws holding the panel in place. 4. Pull the air filter out for inspection. Replace if nec- essary . 5. When replacing, note the direction of the air flow defined on the side of the filter . The arrow should be pointing downward.
heater operating efficiency . Maintenance as outlined below may be performed by the owner . Y ear l y (Beginning of eac h heating season): 1. Annual service call by qualified service agency .
43 2. Visually check top of vent for soot. Call service person to clean. Some sediment at bottom of vent is normal. 3. Visually inspect venting system for proper func- tion, deterioration or leakage. 4. Check that heater area is free from combustible materials, gasoline, and other flammable vapors and liquids.
44 • hydrochloric acid/muriatic acid • cements and glues • antistatic fabric softeners used in clothes dryers • chloride-type bleaches, detergents, and cleaning solvents found in household laundry rooms • adhesives used to fasten building products • .
45 (b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 1. The equipment listed in Chapter 10 entitled "Equipment Not Required T o Be V ented" in the most current edition of NFP A 54 as adopted by the Board; and 2.
46 NOTES: ______________ ____________ __________________ _____________ ____________ __________________ ______ ______________ ____________ __________________ _____________ ____________ ________________.
47.
w w w .r ay pak .co m Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468 Litho in U.S.A..
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Raypak HD401 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Raypak HD401 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Raypak HD401 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Raypak HD401 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Raypak HD401, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Raypak HD401.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Raypak HD401. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Raypak HD401 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.