CATALOG NO. 3000.50D Effective: 01-01-03 Replaces: 03- 01-97 P/N 240687 INST ALLA TION AND OPERA TING INSTRUCTIONS Models 090A, 135A, 195A T ype WH This manual should be maintained in legible condition and kept adjacent to the heater or kept in a safe place for future reference.
These instructions are provided to assure the proper installation and operation of Raypak water heaters. Should questions arise regarding the specifications, installation, operation or servicing of these water heat- ers, we suggest that the local Sales representative or the factory be consulted.
3 1. RECEIVING EQUIPMENT On receipt of your equipment it is suggested that you visually check for external damage to the carton. If the carton is damaged, it is suggested that a note be made on the Bill of Lading when signing for equipment. Remove the heater from the carton and if it is damaged report the damage to the carrier immediately.
4 Be sure to read and understand the entire Instruction Manual before attempting to install or operate this water heater. Pay particular attention to the following general Safety Precautions. Failure to follow these warnings could result in a fire or explosion, causing property damage, bodily injury or death.
5 To meet commercial hot water requirements, the tankstat is adjustable up to 190°F. However, water temperatures over 125°F. can cause severe burns in- stantly or death from scalds. This is the preferred starting point for setting the control for supplying general purpose hot water.
3. INSTALLATION PROCEDURES CODE REQUIREMENTS Installation must be in accordance with local codes , or, in the absence of local codes, with the latest editions of the National Fuel Gas Code , ANSI Z223.1,/ NFPA 54, and the National Electrical Code , ANSI/ NFPA 70.
2 ) If the heater room is located against an outside wall and air openings can communicate directly with the outdoors, the two openings on the outside wall must each have a net free area, in square inches as follows: Model Sq.
8 WARNING: These heaters must not be connected into any portion of mechanical draft systems operating under positive pressure. To do so may cause the flue products to be discharged into the living space causing serious health injury.
9 At the time of removal of an existing heater, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remain- ing connected to the common venting system are not in operation.
10 The gas valve is provided with pressure taps to measure gas pressure upstream of the gas valve and downstream which is the same as the manifold pressure. WATER CONNECTIONS & SYSTEM PIPING The pipe size and fittings between the heater and the tank should be at least 1" for model 90, and 1-1/4" for models 135 and 195.
ELECTRICAL WIRING The electrical power supply requirement for these heaters is 115 volts, 60 Hz. Field wiring connections and electrical grounding must comply with the local codes, or in the absence of local codes, with the latest edition of the National Electrical Code, ANSI/NFPA 70.
See page 11 wiring diagram key information. 12 WIRING DIAGRAM: STANDING PILOT MODELS 90, 135 and 195 WIRING DIAGRAM: INTERMITTENT IGNITION DEVICE (IID) MODELS 90, 135 and 195 *Field Installed WARNING: SHOCK HAZARD LINE VOLTAGE IS PRESENT.
4. SERVICING PROCEDURES GENERAL LOCATION OF CONTROLS CONTROL BOX COMPONENT LOCATIONS Ignition Module (Auto Ignition Only) 13 SEQUENCE OF OPERATION INTERMITTENT IGNITION DEVICE (IID) Heaters equipped with the IID system will automati- cally light the pilot burner first and then the main burner, each time there is a call for heat from the tankstat.
START-UP PROCEDURES SECTION 1 . Filling the System Fill system with water. Purge all air from the system using purge valve sequence. After system is purged of air, lower system pressure. Flush system before putting into operation to assure that foreign material does not damage pump seals.
8. Push down and hold the red reset button in, imme- diately light the pilot with a match. Continue to hold down red reset button for about one minute after the pilot is lighted. Release red reset button and it will pop back up. Pilot should Remain lighted.
16 FOR INTERMITTENT IGNITION (IID) WITH HONEY- WELL OR ROBERTSHAW GAS VALVE 1. STOP! Read the safety information above. 2. Set the tankstat to the lowest setting. 3. Turn off all electric power to the appliance. 4. This heater is equipped with an ignition device which automatically lights the pilot.
Pilot Adjustment Fig.# 8935.0 ROBERTSHAW 7200 GAS VALVE (Models 135 & 180) e. Replace pilot adjustment cover screw, then follow the lighting instructions to get heater ready for operation. FOR AUTOMATIC IGNITION SYSTEMS A . Intermittent Ignition (IID) 1.
BURNER DRAWER REMOVAL 1. Shut off power and gas supply to the heater. Dis- connect union(s) and pilot tubing when present; then loosen and remove burner hold down screws. 2. Disconnect wires at gas valve and slide burner drawer out. MAIN BURNER AND ORIFICE REMOVAL 1.
HEAT EXCHANGER RE-ASSEMBLY 1. Heat exchanger water header O-rings should be replaced with new ones. 2. Install inlet-outlet and return water headers and install header retainer nuts and torque nuts evenly. 3. Replace "V" baffles. 4. Install thermostat sensing bulbs in header wells and replace bulb retaining clips.
20 5. TROUBLE SHOOTING GUIDE IMPORTANT NOTICE These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed.
1) Adjust inlet gas pressure as shown on rating plate. 2) Clean pilot orifice. 3) Replace thermocouple. 1 ) Adjust manifold pressure as shown on rating plate. 2) Clean burners free of debris or in- sects. 3) Clean gas line or increase gas line piping.
22 HONEYWELL PILOT ROBERTSHAW PILOT AIR OPENING PILOT ORIFICE Fig.# 8045.2 PILOT Fig.# 8102.1 ORIFICE ADJUSTMENTS/REPLACEMENTS OF COMPONENTS CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
23 6. REPLACEMENT PARTS LIST NOTE: To supply the correct part it is important that you state the model number, serial number and type of gas when applicable.
24 HONEYWELL STANDING PILOT ROBERTSHAW STANDING PILOT Fig. # 8189.4 Fig. # 8190.3 3-P 1-P 2-P 6-P 8-P 3-P 1-P 2-P 6-P 8-P 1-P 2-P 9-P 6-P 8-P Fig. # 9112 HONEYWELL IID 5-S.
25.
26.
LIMITED PARTS WARRANTY ECONOPAK WATER HEATERS MODELS WH - 90 TO 195 SCOPE: Raypak, Inc. ("Raypak") warrants to the original owner that all parts of this water heater which are actually manuf.
Raypak, Inc. , 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 FAX (800) 872-9725 Raypak Canada LTD , 2805 Slough Street, Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 FAX (905) 677-8036 Litho in U.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Raypak 090A è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Raypak 090A - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Raypak 090A imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Raypak 090A ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Raypak 090A, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Raypak 090A.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Raypak 090A. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Raypak 090A insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.