Manuale d’uso / di manutenzione del prodotto MAXIM INTEGRATED WATER HEATING SYSTEM del fabbricante PVI Industries
Vai alla pagina of 12
PV500 - 17 05 - 2000 Section 17 1 INSTALLATION & MAINTENANCE MANUAL FOR MAXIM INTEGRATED WATER HEATING SYSTEM TABLE OF CONTENTS Start - up Procedures 2 Maintenance & Safety Inspections 3 - 5 Wiring Diagrams 6,7 Burner 8 Burner Start - up 9 - 12 Burner Troubleshooting 13.
PV500 - 17 05 - 2000 Section 17 2 START - UP PROCEDURES CAUTION: DO NOT RELIGHT PILOT OR START BURNER WITH COMBUSTION CHAMBER FULL OF GAS OR OI L VAPOR, OR WITH VERY HOT COMBUSTION CHAMBER. 1. Study the burner start - up information included in this manual carefully.
PV500 - 17 05 - 2000 Section 17 3 MAXIM MAINTENANCE AND SAFETY INSPECTIONS 1. Establ ish a preventive maintenance program to assure a longer water heater life. 2. The tank should be flushed at two - or three - month intervals depending on water conditions in your location.
PV500 - 17 05 - 2000 Section 17 4 MAXIM MAINTENANCE AND SAFETY INSPECTIONS (continued) Periodic Inspection of Operation Components (continued) CAUTION: THE RELIEF VA LVE IS A PRIMARY SAFETY DEVICE.
PV500 - 17 05 - 2000 Section 17 5 MAINTENANCE & SAFETY INSPECTION REPORT DATE BURNER INSPECTION COMBUSTION ANALYSIS TANK INSPECTION TANK FLUSH & CLEANOUT TANK FITTING INSPECTION VENT INSPECTIO.
PV500 - 17 05 - 2000 Section 17 6 MAXIM AXIAL FLOW GAS BURNER CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. PVI recommends a s easonal or annual combustion check - out be performed by a qualified service agency to ensure safe and efficient operation.
PV500 - 17 05 - 2000 Section 17 7 MAXIM AXIAL FLOW GAS BURNER START - UP (Refer to Figure 17 - 2, page 6 to identify burner parts) 1. Remove the enclosure panel cover on the water heater or boiler to expose the control circuit. A wiring diagram, included in this packet, will show the controls used in our circuitry.
PV500 - 17 05 - 2000 Section 17 8 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) PRESSURE PLATE Set up and Tolerances Figure 17 - 3 13. Connect a test meter to the control for reading the flame response signal. NOTE: Some controls read the flame signal in micro amps and some in volts DC.
PV500 - 17 05 - 2000 Section 17 9 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) This section pertains to MC120 control only. When the blower motor starts, the air proving light on the MC - 120 should be on. This indicates a positive air flow condition.
PV500 - 17 05 - 2000 Section 17 10 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) 17. Check flue gases with a flue analyzer to make final settings of the air shutter. a. The readings need to be taken from a hole in the vent several inches above the heater vent connection, but before draft regulator.
PV500 - 17 05 - 2000 Section 17 11 MAXIM TROUBLESHOOTING SUGGESTIONS AXIAL FLOW GAS BURNER 1. BURNER FAILS TO START Defective On/Off switch. Replace switch. A. Control circuit has an open control contact. Check limits, low water cutoff, proof of closure switch and others as applicable.
PV500 - 17 05 - 2000 Section 17 12 MAXIM TROUBLESHOOTING SUGGESTIONS AXIAL FLOW GAS BURNER (continued) C. Defective automatic main or auxiliary gas shut off valves. Check electrical circuitry to valves. Replace valves or correct circuitry a s required.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.