Powerware 9395 UPS and Plus 1 UPS 650–825 kVA Installation and Operation Manual ®.
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com i Table of Contents 1 Introduction 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com ii 4.8 Installing UPS External and Battery Power Wiring 4−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com iii 7.3 Single UPS Operation 7−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com iv 10 Product Specifications 10−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com v List of Figures Figure 1-1. Powerware 9395 UPS (650–825 kVA) 1−2 . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com vi Figure 4-34. REPO Switch 4−39 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com vii Figure 8-1. Optional X−Slot Cards 8−2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com viii This page intentionally left blank.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 1−1 Chapter 1 Introduction Eaton’s Powerware ® 9395 uninterruptible power supply .
INTRODUCTION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 1−2 Power wiring can be routed through the top or bottom of the cabinet with connections made to easily accessible terminals.
INTRODUCTION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 1−3 S Alarm Contact – One alarm contact is provided for connection to equipment at the facility, such as a light, an audible alarm, or a computer terminal.
INTRODUCTION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 1−4 1.2 Options and Accessories Contact an Eaton sales representative for information about the following options. 1.2.1 Field Installed UPM A Field Installed UPM (FI−UPM) provides N+1 redundancy for the UPS system.
INTRODUCTION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 1−5 1.2.5 Single−Feed Kit An optional kit is available for converting the dual−feed rectifier and bypass inputs to a single−feed configuration.
INTRODUCTION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 1−6 1.4 Basic System Configurations The following basic UPS system conf.
INTRODUCTION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 1−7 1.7 Symbols, Controls, and Indicators The following are examples of.
INTRODUCTION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 1−8 1.9 Getting Help If help is needed with any of the following: S Sch.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 2−1 Chapter 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries.
SAFETY WARNINGS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 2−2 S The operating environment should be maintained within the parameters stated in this manual. S Keep surroundings uncluttered, clean, and free from excess moisture.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 2−1 Section I Installation.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 2−2.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−1 Chapter 3 UPS Installation Plan and Unpacking Use the following basic sequence of steps to install the UPS: 1. Create an installation plan for the UPS system (Chapter 3).
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−2 Table 3-1.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−3 Dimensions are in millimeters [inches]. Figure 3-1. UPS Cabinet Dimensions (Front View) Dimensions are in millimeters [inches].
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−4 Figure 3-3.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−5 Front Dimensions are in millimeters [inches]. Figure 3-5. ISBM Section Dimensions (Top View) Front Dimensions are in millimeters [inches].
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−6 Dimensions are in millimeters [inches]. CG CG Figure 3-8. ISBM Section Center of Gravity Dimensions are in millimeters [inches].
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−7 Dimensions are in millimeters [inches]. 115.8 [4.56] 114.3 [4.50] 0.87 [0.22] 88.9 [3.50] Front View 1.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−8 3.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−9 For external wiring requirements, including .
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−10 Table 3-5.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−11 AC input to the UPS with separate rectifier inputs is wired as if each UPM is rated for 275 kVA (see Table 3-6).
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−12 Terminals E1A through E5A and E9A through E12A are stud type terminals. The intercabinet power wiring connections for this equipment are rated at 90 ° C.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−13 For an UPS with common rectifier input terminals, E1 through E12 are 2-hole bus bar mountings for standard NEMA 2-hole barrel lugs.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−14 Table 3-10.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−15 Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See Table 3-13 for conduit requirements.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−16 Table 3-13.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−17 Table 3-15.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−18 There is no manual DC disconnect device within the UPS. A battery disconnect switch is required for battery systems and may also be required by NEC or local codes.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−19 3.2.3 UPS System Interface Wiring Preparation Control wiring for features and options should be connected at the customer interface terminal blocks located inside the UPS.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−20 S The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements. S The maximum distance between the REPO and the UPS cannot exceed 150 meters (500 feet).
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−21 3.3 Inspecting and Unpacking the UPS Cabinets The UPS cabinet is divided into two sections palleted separately for shipping.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−22 4. Remove the protective covering from the cabinets. 5. Remove the packing material, and discard or recycle in a responsible manner.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−23 Figure 3-12.
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 3−24 This page intentionally left blank.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−1 Chapter 4 UPS System Installation 4.1 Preliminary Installation Information W A R N I N G Installation should be performed only by qualified personnel.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−2 NOTE For the following steps, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table 3-1 on page 3−2 for cabinet weight).
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−3 Shipping Bracket Bolts Shipping Bracket Bolts Pallet Right Side Shipping Bracket ISBM Removable Front Panels Figure 4-2.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−4 Shipping Bracket Bolts Shipping Bracket Bolts Pallet Left Side Shipping Bracket UPM Removable Front Panels Wireway Panel Figure 4-3.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−5 Shipping Bracket Bolts Shipping Bracket Bolts Pallet Right Side Shipping Bracket Figure 4-4. Removing the UPM Section Right Side Shipping Bracket 4.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−6 Left Top Panel Wireway Panel Left Middle Panel Corner Channel UPM Section Interior Left Side Panel Figure 4-5.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−7 UPM Wireway (Power wiring harnesses are coiled in this area.) Figure 4-6. ISBM and UPM Sections Joined 10. Reinstall the left top panel (see Figure 4-5) and secure using the retained hardware.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−8 Front View Base Bracket UPM Section Base ISBM Section Ba.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−9 NOTE Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install the first lug on the stud with the raised barrel portion facing the back of the cabinet.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−10 13. Locate the ground braid in the bottom left front corner of the UPM section. The ground braid is secured at the factory to the UPM section ground bolt.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−11 (See Figure 4-9 for detail.) AC Input to UPMs AC Output from UPMs Phase C Phase A Phase B Neutral from UPMs (See Figure 4-13 for detail.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−12 UPM 1 Cable 1G1 & 1G2 Yellow Phase C (E3A) UPM 2 Ca.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−13 (See Figure 4-9 for detail.) AC Input to UPMs AC Output from UPMs Phase C Phase A Phase B Neutral from UPMs (See Figure 4-13 for detail.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−14 UPM 1 Cable 1G1 & 1G2 Yellow Phase C (E3A) UPM 2 Ca.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−15 DC Input to UPMs + Cable 1G3 Black UPM 1 (1E5A) Cable 1.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−16 Wiring Access Location of J50, J51, J61, and J70 Coiled.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−17 ISBM Section Right Side Inside View Pl1 Interface Board Front Figure 4-15. Pl1 Interface Board Location Pl1 Interface Board J39 Inverter CAN Connector Figure 4-16.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−18 4.5 Field Installed UPM Installation If installing a Pl.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−19 Ventilation Grill Debris Shield (Remove shield before operating system.) ISBM Section Front Ventilation Grill Debris Shields (Remove shields before operating system.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−20 Top Entry Conduit Landing for AC Input and Output, and DC Input (Remove panel to drill or punch conduit holes.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−21 4. Locate the external wiring terminal hardware kit packed on the bottom left side of the ISBM section. 5.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−22 NOTE Required parallel system wiring length must be equal to ensure approximately equal current sharing when in Bypass mode.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−23 (See Figure 4-21 for Detail AA.) DC Input from Battery + (E4) – (E5) DC Input from Battery AC Input to UPS Rectifier (A, B, C) AC Input to UPS Bypass (A, B, C) (See Figure 4-21 for Detail AA.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−24 Ground Terminals Phase A (E6) Phase C (E8) Phase B (E7).
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−25 A B C N (See Figure 4-23 for Detail AA.) DC Input from Battery + (E4) – (E5) DC Input from Battery AC Input to UPS Rectifier (A, B, C) AC Input to UPS Bypass (A, B, C) (See Figure 4-23 for Detail AA.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−26 Ground Terminals Phase A (E6) Phase C (E8) Phase B (E7) AC Input to UPS Bypass ‘ NOTE AC Input to Bypass terminals are not applicable to an IOM configuration.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−27 AC Input to UPM Rectifiers Phase A (E1) Phase C (E3) Ph.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−28 4.8.2 Battery Power Wiring C A U T I O N When sizing the battery system, do not exceed the internal battery charger capabilities.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−29 DC Input from Battery + (E4) – (E5) DC Input from Battery Section B–B Front Figure 4-25.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−30 DC Input from Battery + (E4) – (E5) DC Input from Bat.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−31 4.9 Installing Interface Connections W A R N I N G Hazardous voltages are present near the user interface terminal area if the UPS is not totally disconnected.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−32 11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. Close the door and secure the latch.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−33 Table 4-1. TB1, TB2, and TB3 Interface Connections Terminal TB1 Name Description 1 REPO NC Input: Normally-closed dry contact used to activate UPS EPO from a remote switch.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−34 X−Slot Communication Bays TB1 TB2 See Figure 4-30 for terminal assignments.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−35 UPS Building Alarm 3 Building Alarm 3 Return Building A.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−36 4.9.2 TB1 Battery Interface Connections To install wiring to connections: 1. Verify the UPS system is turned off and all power sources are removed.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−37 Battery Disconnect TB1 Battery Aux Battery Aux Common 48 Vdc Battery Shunt Trip + 48 Vdc Battery Shunt Trip – UPS ST 5 6 7 8 NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−38 4.9.3 X−Slot Connections NOTE LAN and telephone drops for use with X−Slot cards must be provided by the customer.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−39 4.10 Installing a REPO Switch A latching−type Remote .
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−40 5. To gain access to terminal block TB1 and the interface entry conduit landing plate, remove the screws securing the top internal safety shield panel and remove the panel.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−41 12. If required, install wiring from the REPO switch to the trip circuitry of the upstream protective devices.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−42 3 (NO) UPS TB1 REPO Switch (NO) Twisted Wires 1 (NC) 2 (Return) 4 (Return) REPO Switch (NC) NOTE REPO switch rating is 24 Vdc, 1A minimum.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−43 Installation Checklist - All packing materials and restraints have been removed from each cabinet. - Each cabinet in the UPS system is placed in its installed location.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−44 Distributed Bypass Installation Checklist - Each cabinet in the distributed bypass system is placed in its installed location.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−45 Notes _________________________________________________.
UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 4−46 This page intentionally left blank.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−1 Chapter 5 Installing Options and Accessories 5.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−2 4. Read and understand the following notes while planning and performing the wiring installation: S Conduit must be installed between the UPS cabinet and the device for signal wiring.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−3 Connections for Parallel System Control Connections for RMP II, RIM II, or SCM II Alarm J3 Connections for Bypass Status Figure 5-2.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−4 5.2 Installing Distributed Bypass Control Wiring NOTE When installing external wiring to the Powerware Hot Sync CAN Bridge Card, conduit must be installed to the UPS cabinet.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−5 UPS 1 UPS 2 UPS 3 UPS 4 CAN (If Installed) (If Installed) Pull Chain NOTE This drawing is for distributed bypass wiring purposes and is not a floor layout plan.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−6 1 2 3 4 5 7 8 6 9 10 UPS 1 Twisted Pair Twist.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−7 NOTE NC and NO designations on MOB AUX contacts are defined with breaker in OFF (open) position.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−8 Table 5-4.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−9 5.3 Installing an Optional Remote Monitor Panel II To install RMP II wiring: 1. Verify the UPS system is turned off and all power sources are removed.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−10 Terminal TB1 Signal Connections from the UPS Ground Terminal Terminal TB3 120 Vac Power Figure 5-7.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−11 NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−12 10. Restart the UPS. See Chapter 7, UPS Operating Instructions," for startup instructions.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−13 5.5 Installing an Optional Supervisory Contact Module II To install SCM II wiring: 1. Verify the UPS system is turned off and all power sources are removed.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−14 NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−15 5.6 Accessory Mounting Dimensions Figure 5-12 through Figure 5-14 show the dimensions of the RMP II, the RIM II, and the SCM II.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−16 Knockouts Provided on Five Surfaces Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−17 Knockouts Provided on Five Surfaces Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.
INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−18 This page intentionally left blank.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−19 Section II Operation.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 5−20.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−1 Chapter 6 Understanding UPS Operation 6.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−2 The emergency bypass consists of a momentary−duty static switch, a wraparound bypass breaker, and a backfeed protection contactor K5.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−3 Static Switch Rectifier Inverter K1 K3 Battery Conve.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−4 6.2.3 Bypass Mode NOTE Bypass mode is not available on an UPS configured as an IOM. The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−5 The internal bypass is comprised of a solid−state, silicon−controlled rectifier (SCR) static switch (SSW), a motorized wraparound bypass breaker CB4, and a backfeed protection contactor K5.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−6 Static Switch K5 Rectifier Inverter K1 K3 Battery Co.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−7 6.3 Single UPS Unit System Oneline Configurations The system oneline drawings in this section show the simplified internal structure of the UPS, battery supply, and basic maintenance bypass.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−8 Input Breaker (CB1) (optional) X−Slot Interface E1, E2, E3 E6, E7, E8, E12 48V Battery Shunt Trip NOTE Callout letters A , B , C , and D map to Table 3-4 on page 3−9.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−9 Input Breaker (CB1) (optional) X−Slot Interface E1, E2, E3 E6, E7, E8, E12 48V Battery Shunt Trip NOTE Callout letters A , B , C , and D map to Table 3-5 on page 3−10.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−10 Input Breaker (CB1) (optional) X−Slot Interface E1, E2, E3 E6, E7, E8, E12 48V Battery Shunt Trip NOTE Callout letters A , B , C , and D map to Table 3-4 on page 3−9.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−11 Input Breaker (CB1) (optional) E1, E2, E3 E6, E7, E8, E12 NOTE Callout letters A , B , C , and D map to Table 3-5 on page 3−10.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−12 Input Breaker (CB1) (optional) X−Slot Interface E1, E2, E3 48V Battery Shunt Trip NOTE Callout letters A , B , C , and D map to Table 3-4 on page 3−9.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−13 Input Breaker (CB1) (optional) X−Slot Interface E1, E2, E3 48V Battery Shunt Trip NOTE Callout letters A , B , C , and D map to Table 3-5 on page 3−10.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−14 Input Breaker (CB1) (optional) X−Slot Interface E1, E2, E3 48V Battery Shunt Trip NOTE Callout letters A , B , C , and D map to Table 3-4 on page 3−9.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−15 Input Breaker (CB1) (optional) E1, E2, E3 NOTE Callout letters A , B , C , and D map to Table 3-5 on page 3−10.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−16 E1, E2, E3 E6, E7, E8, E12 NOTE Callout letter A maps to Table 3-6 on page 3−11 . Callout letters B , C , and D map to Table 3-5 on page 3−10.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−17 NOTE Callout letter A maps to Table 3-6 on page 3−11 . Callout letters B , C , and D map to Table 3-5 on page 3−10 .
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−18 E1, E2, E3 NOTE Callout letter A maps to Table 3-6 on page 3−11 . Callout letters B , C , and D map to Table 3-5 on page 3−10 .
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−19 NOTE Callout letter A maps to Table 3-6 on page 3−11 . Callout letters B , C , and D map to Table 3-5 on page 3−10 .
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−20 MAINTENANCE BYPASS PANEL Output from UPS MIS To UPS.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−21 6.4 Multiple UPS Distributed Bypass System Distributed bypass parallel operation extends the normal operation of Powerware 9395 UPSs by offering increased capacity and/or redundant capability.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−22 The UPSs continually monitor themselves and the inc.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−23 If the utility AC power is interrupted or is out of specification, the UPSs automatically switch to Battery mode to support the critical load without interruption.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−24 In a distributed bypass system, each UPS operates similar to a single UPS, but in parallel with each other.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−25 Main Power Flow UPS 1 UPS 2 UPS 3 UPS 4 Output to C.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−26 6.
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−27 Battery Breaker Battery Converter Inverter K3 Fuse .
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−28 Battery Breaker Battery Converter Inverter K3 Fuse .
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−29 Battery Breaker Battery Converter Inverter K3 Fuse .
UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 6−30 This page intentionally left blank.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−1 Chapter 7 UPS Operating Instructions This section describes how to operate the UPS.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−2 7.1.1 Control Panel The control panel is used to set up and control the UPS, and to monitor UPS operation.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−3 7.2.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−4 7.2.3 Using the LCD and Pushbuttons The LCD on the control panel provides an operator interface with the UPS system.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−5 7.2.4 Using the Menu The UPS menu bar allows you to display data in the information area to help you monitor and control UPS operation.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−6 7.2.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−7 Table 7-3. Display Menu Operation (continued) Operation Subfunction Function Contrast Adjust Select CONTRAST from the System Setup Level 0 menu to display the Contrast Adjust screen.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−8 Table 7-3. Display Menu Operation (continued) Operation Subfunction Function Com Port Selection The Com Port Setup screen allows selection of the serial COM port to set up.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−9 Table 7-4.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−10 7.2.8 Load Off Screen The Load Off screen (Figure 7-6) is displayed when the LOAD OFF pushbutton is selected from the main menu bar, the UPS Control Command screen, or the Bypass Control Command screen.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−11 7.3 Single UPS Operation NOTE A Field Installed UPM (FI−UPM) is always designated as UPM 4. 7.3.1 Starting the UPS in Normal Mode To start the UPS system: 1.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−12 7.3.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−13 10. Press the CONTROLS pushbutton on the System Status menu bar. The UPM 1 Control Command screen is displayed.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−14 7.3.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−15 7.3.6 Transfer from Normal to Bypass Mode and Shut Down UPS To transfer the critical load to Bypass mode and shut down the UPS: 1.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−16 7.3.8 UPS and Critical Load Shutdown To perform maintenance or service on the critical load, shut down power to the load: 1.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−17 7.3.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−18 C A U T I O N All power to the critical load is lost when the LOAD OFF is selected in the following step.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−19 C A U T I O N Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and cleared.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−20 7.4 Multiple UPS Distributed Bypass Operation 7.4.1 Starting the Distributed Bypass System in Normal Mode To start the distributed bypass system: 1.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−21 7.4.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−22 8. On the System Status screen, select the UPM command. 9. On the UPS Control Command screen, select the UPM 1 command.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−23 20. Repeat Steps 8 through 19 for each UPS in the distributed bypass system. NOTE To transfer to Normal mode after starting individual UPMs, follow the procedure in paragraph 7.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−24 7.4.6 Transfer from Normal to Bypass Mode and Shut Down all UPSs To transfer the critical load to Bypass mode and shut down all UPSs: 1.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−25 7.4.8 UPS and Critical Load Shutdown To perform maintenance or service on the critical load, shut down power to the load: 1.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−26 7.4.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−27 C A U T I O N All power to the critical load is lost when the LOAD OFF is selected in the following step.
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 7−28 C A U T I O N Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and cleared.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 8−1 Chapter 8 Communication This chapter describes the communication features of the Powerware 9395 650–825 kVA UPS and provides information about connecting hardware and using Terminal mode.
COMMUNICATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 8−2 LAN and telephone drops for use with X−Slot connectivity cards must be provided by facility planners or the customer.
COMMUNICATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 8−3 The eNotify Service relies on a ConnectUPS−X Web/SNMP Card (or P.
COMMUNICATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 8−4 Remote Notification differs from the basic Terminal mode with the .
COMMUNICATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 8−5 8.5.2 Event History Log This key sequence prints the entire Event History Log of the UPS at the time the data is requested.
COMMUNICATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 8−6 MODEL: POWERWARE 9395 CTO: TF12710000000 SERIAL: MCU DSP: 70.81.14 MCU BOOTLOADER: 80.40 MCU PLD: 1.00 PMF 1 DSP: 80.
COMMUNICATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 8−7 8.6 Building Alarm Monitoring This standard feature lets you connect the UPS to your building alarms, such as smoke detectors or overtemperature alarms.
COMMUNICATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 8−8 The RMP II contains a local horn and the backlit status indicators listed in Table 8-1.
COMMUNICATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 8−9 8.9 Relay Interface Module II An optional Relay Interface Module II (RIM II) uses relay contact closures to indicate the operating status and alarm condition of the UPS system.
COMMUNICATION EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 8−10 8.10 Supervisory Contact Module II An optional Supervisory Contact Module II (SCM II) establishes an interface between the UPS system and the customer’s monitor.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 9−1 Chapter 9 UPS Maintenance The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little disassembly.
UPS MAINTENANCE EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 9−2 S Proper disposal of batteries is required. Refer to your local codes for disposal requirements. S Do not dispose of batteries in a fire.
UPS MAINTENANCE EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 9−3 ISBM Air Filters Figure 9-1. ISBM Section Air Filter Locations C A U T I O N Verify washed filters are thoroughly dry before reinstalling.
UPS MAINTENANCE EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 9−4 UPM Air Filters Figure 9-2. UPM Section Air Filter Locations 3. If the UPS is a Plus 1 model, check the Field Installed UPM (FI−UPM) air filter (located behind the front panel) and wash or replace as necessary.
UPS MAINTENANCE EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 9−5 FI−UPM Air Filter Figure 9-3.
UPS MAINTENANCE EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 9−6 9.4 Recycling the Used Battery or UPS Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or UPS.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 10−1 Chapter 10 Product Specifications 10.1 Model Numbers The UPS is housed in a free-standing cabinet, divided into two sections with safety shields behind the door and front panels.
PRODUCT SPECIFICATIONS EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com 10−2 10.2.2 UPS Output UPS Output Capacity 100% rated current.
EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com W−1 Warranty LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE ® UPS PRODUCTS WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Corporation, a Delaware Corporation (Eaton").
WARRANTY EATON Powerware ® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com W−2 This page intentionally left blank.
.
*1642017252* 164201725 2.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Powerware Powerware 9395 UPS and Plus 1 UPS 650825 kVA è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Powerware Powerware 9395 UPS and Plus 1 UPS 650825 kVA - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Powerware Powerware 9395 UPS and Plus 1 UPS 650825 kVA imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Powerware Powerware 9395 UPS and Plus 1 UPS 650825 kVA ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Powerware Powerware 9395 UPS and Plus 1 UPS 650825 kVA, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Powerware Powerware 9395 UPS and Plus 1 UPS 650825 kVA.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Powerware Powerware 9395 UPS and Plus 1 UPS 650825 kVA. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Powerware Powerware 9395 UPS and Plus 1 UPS 650825 kVA insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.