Manuale d’uso / di manutenzione del prodotto WV Series del fabbricante PB Heat
Vai alla pagina of 26
WB V/WV Boilers Series Oil Installation, Operation & Maintenance Manual As an E NERGY S TA R ® Partner, PB Heat, LLC has determined that certain firing rates of this product meet the E NERGY S TA R ® guidelines for energy efficiency .
USING THIS MANUAL 1 A . INST ALLA TION CLEARANCE . . . . . . . . . . . . .1 B . SPECIAL A TTENTION BOXES . . . . . . . . . . . .1 1. PREINST ALLA TION 2 A . CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . .2 B . AIR FOR COMBUSTION AND VENTILA TION .
1 A. INST ALLA TION CLEARANCE F ollow the installation instructions provided in this manual in the order shown. The order of these instructions has been set in order to provide the installer with a logical sequence of steps that will minimize potential interferences and maximize safety during boiler installation.
2 A. CLEARANCES Unit may be installed on combustible flooring, provided the boiler is not set on carpet and a metal drip pan is placed under the appliance. Unit may be installed in a closet with the above clearances. See also Section B, Air for Combustion and V entilation.
3 C. CHIMNEY / VENT AND DRAFT CONTROL 1. Draft Requirement – Minimum draft r equir ed in the vent system is -.03" to -.06" W .C. depending on boiler model, see T able 7.1 (Section 7). This draft is necessary to provide the necessar y draft over fire of -.
4 A. SETTING THE BOILER 1. Provide a level foundation, located as close as possible to the center of the heating system. 2. Refer to Figur es 2.1 and 2.
BOILER PLA CEMENT AND ASSEMBL Y (See T able 8.1 for parts identification). Figure 2.1: Steam boiler 5 Figure 2.2: W ater boiler.
A. PRESSURE TEST BLOCK ASSEMBL Y 1. Make up cold water supply connection to the boiler . 2. Install pressur e gauge or pr essure-temperatur e gauge in tapping provided. See Boiler Dimensional drawing, Figur es 7.1 and 7.2 (Section 7) 3. Plug all open tappings in the boiler and fill with water .
7 E. T ANKLESS HEA TER OR CO VERPLA TE 1. If a tankless coil is used (item 9), install as pictured. On water boilers, install in opening in front section. On steam boilers, install in opening in rear section. F or suggested piping of tankless water heaters refer to Figur es 3.
8 Figure 3.6: Piping with P eerless Indirect Water T ank Figure 3.7: Float Low Water Cut -off PIPING AND CONTROLS Figure 3.5: Piping to Isolate Boiler from Chilled Medium on Chiller Systems.
9 A. GENERAL All electrical wiring shall be done in accordance with the National Electrical Code and Local Requirements. Single pole switches including those of safety controls or protective devices shall not be wired in a grounded line. B. BURNER WIRING 1.
10 ELECTRICAL Figure 4.3: Water Boilers, P ackaged Figure 4.2: Water Boilers, Knockdown.
11 ELECTRICAL Figure 4.5: Steam with Probe Low W ater Cut -off Figure 4.4: Steam with Float Low Water Cut - Off.
12 ELECTRICAL Figure 4.6: Zoning with Circulators Figure 4.7: Zoning with Zone V alves.
13 BURNER SETUP & BOILER OPERA TION A. BURNER INST ALLA TION 1. The oil burner is supplied with a mounting flange fixed in position. 2. Mount the burner to the bur ner mounting plate (item 5) with four (4) 5/16" studs and nuts provided.
14 BURNER SETUP & BOILER OPERA TION E. CLEAN THE BOILER (STEAM BOILERS ONL Y) 1. Clean the boiler within one week after initial start-up. Cleaning will be more effective if boiler operates a day or two to loosen sediment and impurities in system. 2.
15 BURNER SETUP & BOILER OPERA TION BECKETT BURNER SPECIFIC A TIONS Boiler Model No . Burner Model No . Burner Head Static Plate Nozzle Size Pum p Pressure Start-up Settings Head Setting Air Shutter Air Band WBV -03-085 AFG- F3¹ F3 3-3/8" 0.
16 MAINTENANCE 6. MAINTENANCE W ARNING Product Saf ety Inf ormation Refractory Ceramic Fiber Product This appliance contains materials made from refractory ceramic fiber s (RCF). Airborne RCF , when inhaled, ha ve been c lassified by the International Agency f or Resear ch on Cancer (IARC), as a possib le carcinogen to humans.
17 MAINTENANCE A. GENERAL 1. Check pipes adjacent to cold walls or in unheated spaces. Insulate and tape them if necessary to be sure they can't fr eeze up.
18 MAINTENANCE 2. T o thoroughly clean the boiler it must be brushed down from the top. Alternatively , for limited space or minimum clearance to combustible installations, cleaning the heat e xchanger from the combustion chamber side is acceptable. If unit is e xtremely dirty , it may be necessary to brush from both directions.
19 BOILER DIMENSIONS & RA TINGS 7. BOILER DIMENSIONS & RA TINGS Figure 7.1: Boiler Dimensions, Water Boiler Figure 7.2: Boiler Dimensions, Steam Boiler Boiler Model Number Jack et Depth ".
20 T able 7.1: Boiler Ratings ✸ As an ENERG Y ST AR ® P artner , PB Heat, LLC has determined that these firing rates meet the ENERG Y ST AR guidelines for energy efficiency . ✝ T op venting only . ✚ Nozzles for these firing rates not provided as standard equipment.
21 R E PA I R PA R T S 8. REP AIR P ARTS Repair par ts are available from your installer or by contacting PB Heat, LLC, 131 S. Church St, Bally , P A 19503. Note: Remember to include boiler model number and serial number when ordering par ts. T able 8.
22 NOTES.
23 NOTES.
PP8046 R26 (8/08-10M) Pri nte d i n U.S.A . ©2008 WB V/WV Boilers Series Oil Installation, Operation & Maintenance Manual TO THE INST ALLER: This manual is the property of the owner and must be affixed near the boiler for future reference. TO THE OWNER: This boiler should be inspected annually by a Qualified Service Agency.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il PB Heat WV Series è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del PB Heat WV Series - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso PB Heat WV Series imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul PB Heat WV Series ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il PB Heat WV Series, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del PB Heat WV Series.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il PB Heat WV Series. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo PB Heat WV Series insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.