© Panasonic HA Air-Conditioni ng (M) Sdn. Bhd. 2011. Unauthorized copying and distribu tion is a violation of law. Order No: PHAAM1111121 A1 Outdoor Unit CU-2S18NBU-1 Please file and use this manual together with the service manual for Model No. CS-S9NKUW-1, CS -S12NKUW-1 Order No.
2 12.12 Valve close detect ion control ......................23 12.13 Compressor discha rge high pressure protection co ntrol ........................................23 13. Servicing Mode .................................................24 13.1 Pump Down O peration .
3 1. Safety Precautions • Read the following “SAFETY PRECAUTIONS” carefully before per form any servicing. • Electrical work must be installed or servic ed by a licensed elec trician. Be sure to use the correct rating o f the power plug a nd main circuit for the model installed.
4 WARNING 20. During pump down operation, stop the compressor before remove the refrigeration piping. (Removal of refrigeration piping while compressor is operating and valves are opened condition will cause su ck-in of air, abnormal high pressure in refrigeration cycl e and result in explosion, injury etc.
5 2. S pecification Model Outdoor Unit CU-2S18 NBU-1 Indoor Unit Combination 3.2kW + 3.2kW Power Source 1 Phase, 208-230V, 60Hz (Power supply from outdoor unit) kW 4.89 (2.10 ~ 5.86) Capacity BTU/h 16700 (7200 ~ 20000) Running Current A 7.6 - 6.9 Power Input kW 1.
6 • Multi split combination possibility: o A single outdoor unit enables air con ditioning of up to two separate rooms for CU-2S 18NBU-1. Ou tdoor Unit CU-2S18NBU-1 A B 2.8 kW CS-S9NKUW-1 ● ● Wall 3.2 kW CS-S12NKUW-1 ● ● Capacity range of connectable indoor units From 5.
7 3. Dimensions.
8 4. Refrigeration Cycle Diagram.
9 5. Block Diagram.
10 6. Wiring Connection Diagram.
11 7. Electronic Circuit Diagram.
12 8. Printed Circuit Board 8.1 Main Printed Circuit Board.
13 8.2 Noise Filter Printed Circuit Board.
14 9. Inst allation Information 9.1 Check Points QUICK GUIDE PIPING & ELECTRICAL SPECIFICATION Piping size Indoor(ID) & Outdoor( OD) units: Possible Combinatio n Patterns Capacity (Btu/h) Refrigeran t Gas Liquid Standard pipe length Max. Elevation Min.
15 10. Inst allation Instruction 10.1 SELECT THE BEST LOCATION 10.1.1 OUTDOOR UNIT • If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radia tion from the condenser is not obstru cted. • There should not be any animal or plant which could be affected by hot air discha rged.
16 Outdoor Unit Installation Guidelines • Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below. • For any of the below installation patterns, the wall height on the exhaust side should be 47 1/4" or less.
17 10.2 INSTALL THE OUTDOOR UNIT • After selecting the best location, start installa tion to Indoor/Outdoor Unit Installation Diagram. 1. Fix the unit on concrete or rigid frame firmly and horizontally with b olt nut (ø13/32"). 2. When installing on a roof, please con sider strong winds and earthq uakes.
18 10.4 EVACUATION OF THE EQUIPMENT WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. 1. Connect a charging hose with a push pin to the Low side of a charging set and the service po rt of the gas side 3-way valve.
19 8. For wire stripping and co nnection requirement, refer to the diagram below. 9. Secure the power supply cord an d connecting cabl es onto the control board with the holder. 10. Attach the control board cover (metal and resin) a nd valve cover b ack to the original position with screw.
20 11. Operation Control 11.1 Cooling Operation 11.1.1 Outdoor fan control • When cooling operation is enabled, ba sed on outdoor am bient temperature, fan motor control will be adju sted according to figure below: 11.
21 12. Protection Control 12.1 Freeze Prevention control (Cool) • When received freeze prevention signal from indoor uni t, the compressor frequency change s according to indoor heat exchanger temperature. • When indoor unit request capability OFF due to freeze c ondition , immediately the capability supply to targeted indoor unit stops.
22 12.5 Cooling overload control (Cool) • This control detect outdoor pipe temperature and perfo rm the compressor frequency restriction durin g cooling operation. 12.6 Time Delay Safety Control (Restart Control) • The compressor will not restart within three minutes after compressor is stopped.
23 12.10 Compressor Protection Cont rol (Gas leak detection control 1) • Control start conditions o For 5 minutes, the compressor continuou sly operates and total current is low. o During Cooling or Soft Dry operation: Indoor intake temperature — indoor pipi ng temperature is below 39.
24 13. Servicing Mode 13.1 Pump Down Operation • Operate the pump down according to the following procedures. 1 Confirm the valve on the liquid side and gas side is open. 2 Press PUMP DOWN swit ch (SW1) on the display printed circuit board for more than 5 seconds.
25 NOTE 1. For two rooms, LED 4 and 5 are not illuminated after wiring operation complete. 2. If the outdoor air temperature is less than 41°F or unit has abnormalit y, wiring operation will not start. 3. After wiring check operation is complete, LED i ndication will illuminated until normal operation starts.
26 14. T roubleshooting Guide 14.1 Self Diagnosis Function • The display screen of wireless remote control unit an d the self-diagnosis LEDs (green) on the outdoor pri nted circuit board in the outdoor unit can be used to identify the location of the problem.
27 Diagnosis display Abno rmality or Protection control LED 6 LED 5 LED 4 LED 3 LED 2 LED 1 A bnormal ity Judgment Protecti on Operation Problem Check location H98 Indoor high pressure protection ○ .
28 WA RN ING 15. Disassembly and Assembly Instructions High Voltages are generated in the electrical parts area b y the capacitor. Ensure t hat the capacitor has discharged sufficientl y before proceeding with repair work. Failure to heed this c aution may result in electric shocks.
29 15.1.3 Removing the Control P.C. Board 6. Remov e the drip proof cover. 7. Disconnect the connectors (le ad wires of the compressor, sensor, and others). 8. Remov e the screw at the ri ght side of the control box, and pull out the entir e control bo x.
30 3. Disconnect the fan motor connector from the control P.C. Board. 4. Loosen the 4 fan motor mounting scre ws then remove the fan motor..
31 16. T echnical Dat a 16.1 Operation Characteristics 16.1.1 CS-S9NKUW-1 CU-2S18NBU-1 • Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping length: 24.
32 • Piping Length Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F (DBT) o Compressor Freq: Fc.
33 16.1.2 CS-S9NKU W-1x2 CU-2S18NBU-1 • Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping length: 24.
34 • Piping Length Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F (DBT) o Compressor Freq: Fc.
35 16.1.3 CS-S12NKUW-1 CU-2S18NBU-1 • Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping length: 24.
36 • Piping Length Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F (DBT) o Compressor Freq: Fc.
37 16.1.4 CS-S12NKUW -1x2 CU-2S18NBU-1 • Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping length: 24.
38 • Piping Length Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F (DBT) o Compressor Freq: Fc.
39 16.1.5 CS-S12NKUW-1+CS- S9NKUW-1 CU-2S18NBU-1 • Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping length: 24.
40 • Piping Length Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F (DBT) o Compressor Freq: Fc.
41 17. Exploded View and Replacement Part s List Note The above exploded view is for the purp os e of parts disassembly and replaceme nt. The non-numbered pa rts are not kept as standard service parts.
42 REF. NO. DESCRIPTION & NAME QTY. CU-2S18NBU-1 REMARK 1 BASE PAN ASS'Y 1 CWD52K1240A 2 SOUND-PROOF BOARD 1 CWH151230 3 FAN MOTOR BRACKET 1 CWD541127 5 CONDENSER COMPLETE 1 CWB32C2925 6 FAN .
43 REF. NO. DESCRIPTION & NAME QTY. CU-2S18NBU-1 REMARK 69 SHOCK ABSORBER (LEFT) 1 CWG712880 70 C.C.CASE 1 CWG565609 76 TERMINAL COVER 1 CWH171035 77 NUT - TERMINAL COVER 2 CWH7080300J (Note) • All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488).
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Panasonic CU-2S18NBU-1 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Panasonic CU-2S18NBU-1 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Panasonic CU-2S18NBU-1 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Panasonic CU-2S18NBU-1 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Panasonic CU-2S18NBU-1, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Panasonic CU-2S18NBU-1.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Panasonic CU-2S18NBU-1. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Panasonic CU-2S18NBU-1 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.